Fault
Code
No.
OLED Message
Description
Corrective Action
Ph-Sq
45
Incorrect Supply
Phase Sequence
L1-L2-L3 Phase
sequence is incorrect
Applies to Frame Size 8 drives only, indicates that the incoming power supply
phase sequence is incorrect. Any 2 phases may be swapped.
P-o
48
Feedback Pressure
Low
Low Pressure
Detected by Pipe Fill
Function
Check the pump system for leaks for burst pipes.
Check the Pipe fill function has been commissioned correctly (P3-16 & P3-17).
t-Ph
49
Output Phase Loss
Output (Motor)
Phase Loss
One of the motor output phases is not connected to the drive.
S-F
50
Modbus Comms
fault
Modbus
communication error
detected
S-F
52
Option Module Fault Fitted communication
Module Fault
Internal communication to the inserted Communications Option Module has
been lost. Check the module is correctly inserted.
S-F
53
IO Card Comms
fault
IO card comms trip
Internal communication to the inserted I/O Option Module has been lost.
Check the module is correctly inserted.
S-F
54
BACnet Comms fault BACnet comms loss
trip
A valid BACnet telegram has not been received within the watchdog time limit
set in P5-05.
Check the network master / PLC is still operating.
Check the connection cables.
Increase the value of P5-05 to a suitable level.