background image

50

   |   Optidrive Eco User Guide   |   

Version 3.06

www.invertekdrives.com

9.5.2. Parameter Group 7 – Motor Control

Par.

Function

Setting Range

Default

Notes

P7-01

Motor Stator Resistance

0.000 – 65.535

Drive

Dependent

Motor data, measured or calculated curing 

the autotune.
P7-04 is not used for PM & BLDC Motors.
P7-06 is used only for PM motors.

P7-03

Motor Stator Inductance (d)

0.0000 – 1.0000

P7-04

Magnetising Current (id)

Drive Dependent

P7-05

Motor Leakage Coefficient (Sigma)

0.000 – 0.250

P7-06

Motor Q Axis Inuctance (Lsq)

0.0000 – 1.0000

P7-09

Over Voltage Current Limit

0.0 – 100.0%

5.0%

P7-10

Load Inertia Constant

0 - 600

10

P7-11

Pulse Width Minimum Limit

0 - 500

P7-12

V/F Mode Magnetising Delay Time

0 – 5000ms

Drive

Dependent

Sets the motor magnetising period in V/F Mode.
Sets the motor alignment time in PM modes.

P7-14

Low Frequency Torque Boost

0.0 – 100.0%

0.0%

For PM Motors, applies a torque boost current 

at low frequency, % x P1-08.

P7-15

Torque Boost Frequency Limit

0.0 – 50.0%

0.0%

For PM motors, determines the frequency, % x 

P1-09 when the boost current is removed.

P7-18

Over Modulation

0

Disable

0

1

Enable

P7-19

BLDC Light Load Optimization

0

Disable

1

When P4-01 = 4 (BLDC control) and P7-19 = 1 

(Enable) the drive will reduce the output voltage 

during light load operation in order to improve 

motor efficiency. This setting has no effect if 

the motor is driven close to its nominal current, 

where the nominal flux level will be applied.

1

Enable

P7-20

Modulation Mode

0

3-Phase Modulation

0

1

2-Phase Modulation

9.6. Parameter Group 8 – Application Function Specific Parameters

Par.

Name

Minimum

Maximum

Default

Units

P8-01

Pump Stir Interval Duration

0

60000

0

Minutes

This parameter can be used to set a pre-defined period of inactivity, whereby if the drive remains in standby mode for a period of time 

exceeding the limit, stir function is activated, and the drive will operate at preset speed 7 (P2-07) for the time set in P8-02. This allows 

the pump to stir, preventing sediment from settling and avoiding a blockage.

P8-02

Pump Stir Activation Time

1

6000

10

Seconds

Set the time period that the stir function will be active once triggered (excludes time for deceleration to stop).

P8-03

Pump Clean Function Select

0

3

-

-

This parameter configures the drive conditions that will cause activation of the automatic pump clean function. When activated, the 

pump clean will operate the pump at preset speed 5 (P2-05) for the time period set in P8-04, followed by Preset Speed 6 (P2-06) 

(Providing P2-06 <> 0) for the time set in P8-04, before resuming normal operation. During the cleaning cycle, the ramp time set in P8-

05 is used for both acceleration and deceleration, and overrides P1-03 and P1-04.
Where possible, P2-05 and P2-06 may be set to negative values, to allow the pump to be reversed. For best results, it is recommended 

to use as high a speed as possible, and to adjust P8-05 to allow a short acceleration time whilst avoiding over current trips.

0 : Disabled.
1 : Active on start-up only.

 The pump cleaning function operates every time the pump is started.

2 : Active on start-up and high current detection.

 The pump cleaning function operates every time the pump is started, 

and also in the event that the drive detects a possible pump blockage during normal operation. This requires the Motor Current Profile 

Monitoring function to be active and commissioned for correct operation, see parameter P8-06.

3 : Active on high current detection only.

 The pump cleaning function operates only when a possible pump blockage is 

detected during normal operation. This requires the Motor Current Profile Monitoring function to be active and commissioned for 

correct operation, see parameter P8-06.

NOTE

 The pump clean function can also be activated by digital input configured in group 9 parameters.

P8-04

Pump Clean Time

0

600

0

Seconds

Sets the time period for the operation of the pump cleaning cycle. When bi-directional pump cleaning is selected, the time interval is 

used twice, once in each direction.

P8-05

Pump Clean Function Ramp Time

0

6000

30

Seconds

Independent ramp rate used only for the pump automatic cleaning function (see P8-03) when the motor is Accelerated as part of the 

cleaning cycle.

9

Extended P

arameters

Содержание Optidrive Eco ODV-3-220043-1F12-TN

Страница 1: ...nput General Information and Ratings Introduction Mechanical Installation Electrical Installation LED Keypad and Display Operation Commissioning Parameters Extended Parameters Serial Communications Co...

Страница 2: ...TFT OLED Display 32 5 3 Additional Display Messages 32 5 4 Changing Parameters 33 5 5 Parameter Factory Reset User Reset 34 5 6 Resetting the Drive Following a Trip 34 5 7 Selecting Between Hand and A...

Страница 3: ...year warranty against manufacturing defects from the date of manufacture The manufacturer accepts no liability for any damage caused during or resulting from transport receipt of delivery installation...

Страница 4: ...control cables whilst power is applied to the drive or to the external control circuits Danger Indicates a potentially hazardous situation other than electrical which if not avoided could result in da...

Страница 5: ...621 100 3F12 MN 6A 30 40 1 10 No ODV 3 621500 3F12 MN 6A 37 50 150 No ODV 3 621800 3F12 MN 6B 45 60 180 No ODV 3 622020 3F12 MN 6B 55 75 202 No 380 480 Volt 3 Phase Input Model Code Frame kW HP Amps...

Страница 6: ...3F1X TN ODV 3 220070 3F1D TN 2A 1 5 2 7 Yes ODV 3 220105 3F1X TN ODV 3 220105 3F1D TN 2A 2 2 3 10 5 Yes ODV 3 320180 3F1X TN ODV 3 320180 3F1D TN 3 4 5 18 Yes ODV 3 320240 3F1X TN ODV 3 320240 3F1D T...

Страница 7: ...4 18 5 25 39 Yes ODV 3 440460 3F1N TN 4 22 30 46 Yes ODV 3 540610 3F1N TN 5 30 40 61 Yes ODV 3 540720 3F1N TN 5 37 50 72 Yes ODV 3 540900 3F1N TN 5 45 60 90 Yes ODV 3 641 100 3F1N TN 6 55 75 1 10 No O...

Страница 8: ...firmation In short this means that the low harmonic drives do not require an input choke and should not have one installed drives outside of the above frame sizes and supply voltage number of phases a...

Страница 9: ...o date list of UL compliant products please refer to UL listing NMMS E226333 The drive can be operated within an ambient temperature range as stated in section 1 1 1 Environmental on page 67 For IP20...

Страница 10: ...200 7 87 32 70 5 6B 726 28 58 330 13 320 12 59 680 26 77 225 8 85 43 94 8 8 995 39 17 480 18 89 477 18 77 942 37 08 432 17 130 286 6 Mounting Bolts Tightening Torques Frame Size Metric UNF Frame Size...

Страница 11: ...270 10 63 515 20 28 175 6 89 23 50 7 6 865 34 06 330 12 99 330 12 99 830 32 68 200 7 87 55 121 2 7 1280 50 39 330 12 99 360 14 17 1245 49 02 200 7 87 89 196 2 Mounting Bolts Tightening Torques Frame...

Страница 12: ...mm in mm in kg Ib 2 257 10 12 188 7 40 239 9 41 200 7 87 178 7 01 4 8 10 6 3 310 12 20 21 1 8 29 266 10 47 252 9 90 200 7 87 7 7 16 8 Mounting Bolts Tightening Torques Frame Size Metric UNF Frame Size...

Страница 13: ...s or liquids conductive contaminants such as condensation carbon dust and metallic particles and sprays or splashing water from all directions High moisture salt or chemical content environments shoul...

Страница 14: ...uitable flat blade screwdriver to pull the release tab downwards and lift the bottom of the drive away from the rail first 3 8 Guidelines for Mounting IP55 Units Before mounting the drive ensure that...

Страница 15: ...ling Drive Size X Above Below mm in 2 200 7 87 3 200 7 87 The use of a suitable gland system is required to maintain the appropriate IP Nema rating Cable entry holes will need to be drilled to suit th...

Страница 16: ...ting environment this should include Ambient temperature is at or below that set out in the section 1 1 1 Environmental on page 67 with any relevant derating applied Heat sink fans where fitted freely...

Страница 17: ...s com 3 12 IP66 NEMA 4X Lock Off Mains switch disconnector Lock Off On the switched models the mains switch disconnector can be locked in the Off position using a 20mm standard shackle padlock not sup...

Страница 18: ...eactor dV dT filter Sinewave filter Shielded Motor Cable with PE Connection Additional information in section 4 6 on page 23 NOTE Enclosed drives are not suitable for rigid conduit system connection T...

Страница 19: ...nnected to a suitable ground location to maintain touch potentials within safe limits In addition the motor ground must be connected to one of the ground terminals on the drive 4 2 4 Ground Fault Moni...

Страница 20: ...U V W PE For Best Practice use 360 bonding EMC cable gland shielded to motor chassis 4 3 2 Recommended Cable Types by EMC Category Number of Input Phases Rated Supply Voltage Frame Size IP rating Max...

Страница 21: ...est possible surface area The shield must also be terminated at the drive end as close as practically possible to the drive output terminals Where drives are mounted in a steel control panel enclosure...

Страница 22: ...L2 L3 L3 failure to do so will result in a Ph Seq trip 4 5 Input Chokes The majority of the Optidrive Eco product range is based on a low harmonic solution using film capacitor technology to achieve c...

Страница 23: ...signed with low impedance to HF signals are recommended as a minimum Installation within a suitable steel or copper tube is generally also acceptable The cable screen should be terminated at the motor...

Страница 24: ...the oversizing of the drive makes no difference to the available duration of the overload condition NOTE The 45kW 400V Eco model ODV 3 540900 3 overload capability follows that shown in the variable t...

Страница 25: ...0 2 26 5 10V DC 10Volt DC Output On board 10V DC Supply 10 mA 6 AI 1 DI 4 Analog Input 1 Digital Input 4 Speed Reference 1 0 10V 4 10 3 26 7 0V COM 0 Volt Common 0V Common for AI AO DI DO 8 AO 1 Analo...

Страница 26: ...igital Input Configuration Parameter P1 13 on page 39 The function of the analog input e g for speed reference or PID feedback for example is defined by parameters P1 12 and P1 13 The function of thes...

Страница 27: ...lies with the definition of Safe torque off as defined by IEC 61800 5 2 2007 The STO Function also corresponds to an uncontrolled stop in accordance with category 0 Emergency Off of IEC 60204 1 This m...

Страница 28: ...on Sto F 29 A fault has been detected within either of the internal channels of the STO circuit Refer to your Invertek Sales Partner 4 11 5 STO Function response time The total response time is the ti...

Страница 29: ...urce 1 7 Safety relay Protective Capped Trunking or equivalent to prevent STO Cable short circuit to an external Voltage source Safety relay Protected shielded cables 24V DC Wires should be protected...

Страница 30: ...selected in P1 13 o De energise the STO inputs Drive will display InHibit o Give a start command as per the start source method selected in P1 13 and check that the drive still displays Inhibit and th...

Страница 31: ...s Auto Button Used to place drive in Auto Remote mode Up Button Used to increase speed in real time mode or to increase parameter values in parameter edit mode Down Button Used to decrease speed in re...

Страница 32: ...opped Disabled Drive is enabled running display shows the output frequency Hz Press the Navigate key to select alternative displays Press the Navigate key for 1 second The display will show the motor...

Страница 33: ...lay ECO 01 ECO 01 ECO 01 ECO 01 ECO 01 Stop P1 01 P1 08 30 0A P1 08 Stop 15kW 400V 3Ph 50 0Hz 30 0A P1 08 30 0 3 0 30 0A 15kW 400V 3Ph Press and hold the Navigate key 2 seconds Use the Up and Down key...

Страница 34: ...l parameters are reset to Factory defaults 5 6 Resetting the Drive Following a Trip Optidrive ECO has many protection features designed to protect both the drive and motor from accidental damage When...

Страница 35: ...D Display Maximum frequency Speed limit Maximum frequency Speed limit 1500 rpm 0 rpm P1 01 7500 rpm 0 rpm P1 01 7500 rpm 0 rpm Whilst editing a parameter value press the Up and Down keys simultaneousl...

Страница 36: ...r through a boiler it may be necessary to set a speed to ensure the boiler does not run dry during operation 6 1 3 Acceleration and Deceleration Ramp Times Optidrive Eco units are factory set with acc...

Страница 37: ...mum Default Units P1 01 Maximum Frequency Speed Limit P1 02 500 0 50 0 60 0 Hz Rpm Maximum output frequency or motor speed limit Hz or Rpm If P1 10 0 the value entered displayed is in Rpm NOTE The max...

Страница 38: ...current This parameter is also effective when using alternative motor types P4 01 3 4 or 5 In this case the boost current level is defined as 4 x P1 1 1 x P1 08 P1 12 Primary Command Source 0 6 0 0 Te...

Страница 39: ...eset 2 8 O Stop C Run Enable O Fire Mode 1 C Normal Operation 1 O Remote Ctrl C Local Ctrl Analog In 1 O Preset 1 C Preset 2 9 3 Keypad Speed Reference O Stop C Run Enable O Normal Operation C Preset...

Страница 40: ...hen disabled Preset speed 8 can be selected as per preset speeds 1 4 P2 09 Skip Frequency Centre Point P1 02 P1 01 0 0 Hz Rpm Defines the centre point of the skip frequency band The width of the skip...

Страница 41: ...en the motor current exceeds the adjustable limit 6 Motor torque limit Logic when the motor torque exceeds the adjustable limit 7 Analog input 2 limit Logic when the signal applied to the Analog Input...

Страница 42: ...he upper limited value for P2 1 1 and P2 15 please refer to P2 1 1 or P2 15 P2 17 Relay 1 AO1 Lower Limit 0 P2 16 0 0 Setting the lower limited value for P2 1 1 and P2 15 please refer to P2 1 1 or P2...

Страница 43: ...unction using the OptiTools Studio Suite PC software In addition if P2 25 0 P1 02 0 P2 10 0 and P2 09 P1 02 this ramp time is applied to both acceleration and deceleration when operating below minimum...

Страница 44: ...ly start if Digital Input 1 is closed to Following a trip the drive will make up to 5 attempts to restart at 20 second intervals The drive must be powered down to reset the counter The numbers of rest...

Страница 45: ...P3 03 is set to 0 by default which disables the differential time constant Care must be taken when adjusting this value outside of its default value P3 04 PID Operating Mode 0 1 0 0 Direct operation...

Страница 46: ...o pressure low trip P3 17 Burst Pipe Threshold 0 0 100 0 0 0 PID feedback threshold for the burst pipe detection In direct PID mode PID feedback should be equal to or greater than this threshold befor...

Страница 47: ...ulator When P4 12 is enabled the value is retained during power off P4 13 Output Phase Sequence 0 1 0 0 U V W 1 U W V Direction of motor rotation when operating in a forward direction will be reversed...

Страница 48: ...Select 0 7 0 When using an optional Fieldbus interface this parameter configures the parameter source for the 3rd process data word transferred from the drive to the network master during cyclic commu...

Страница 49: ...0 0 25 0 0 3 P6 08 Max Speed Reference Frequency 0 20kHz 0 kHz P6 10 Function Block Program Enable 0 Disabled 0 1 Enabled P6 11 Speed Hold Time on Enable 0 600s 0s P6 12 Speed Hold DC Injection Time...

Страница 50: ...ckage P8 02 Pump Stir Activation Time 1 6000 10 Seconds Set the time period that the stir function will be active once triggered excludes time for deceleration to stop P8 03 Pump Clean Function Select...

Страница 51: ...0 1 0 When Fire mode is assigned to a digital input on the drive then the logic configuration for the input is set by P8 09 to allow normally open or normally closed activation Default behaviour is f...

Страница 52: ...0 P8 17 30 0 Hz Rpm This parameter defines the speed at which an Assist Pump is stopped when using the Pump Cascade or Optiflow feature When the drive output decreases below this threshold one of the...

Страница 53: ...e P9 19 Speed Reference Select Input 1 P9 20 Speed Reference Select Input 2 P9 21 Preset Speed Select Input 0 P9 22 Preset Speed Select Input 1 P9 23 Preset Speed Select Input 2 P9 28 Motorised Pot Up...

Страница 54: ...plays the output level of the PID controller P0 11 Motor Voltage Volts Displays the instantaneous output voltage from the drive to the motor P0 12 Output Torque Nm Displays the instantaneous output to...

Страница 55: ...29 Drive Type Displays the type details of the drive Three entry display First display Frame size and input voltage level Second display Power rating Third display Output phase count P0 30 Drive Seri...

Страница 56: ...easured levels within the drive at various regular time intervals prior to a trip The values are frozen when a fault occurs and can be used for diagnostic purposes P0 41 Over Current Fault Counter P0...

Страница 57: ...is only used for connection of Invertek peripherals and inter drive communication The Modbus interface allows connection to a Modbus RTU network as described in section 10 2 Modbus RTU Communications...

Страница 58: ...ing a suitable dual twisted pair shielded cable with a wave impedance of 120R Use one of the twisted pairs to connect to the RS485 and RS485 of each drive Use one conductor of the remaining pair to co...

Страница 59: ...p Bit 2 Reset request Set to 1 in order to reset any active faults or trips on the drive This bit must be reset to zero once the fault has been cleared Bit 3 Coast stop request Set to 1 to issue a coa...

Страница 60: ...parameters cannot be changed whilst the drive is enabled for example When accessing a drive parameter via Modbus the Register number for the parameter is the same as the parameter number e g Paramete...

Страница 61: ...controlled by the drive internal parameters P1 03 Acceleration Time P1 04 Deceleration Time or controlled directly from the BACnet MSTP network In most cases using the drive internal parameters is th...

Страница 62: ...of digital input 2 ON OFF BV14 Digital Input 3 R Status of digital input 3 ON OFF BV15 Digital Input 4 R Status of digital input 4 ON OFF BV16 Digital Input 5 R Status of digital input 5 ON OFF BV17 D...

Страница 63: ...ercent AV15 Speed Reference C Speed reference value object Hertz AV16 User Ramp Time W User ramp value Seconds AV17 User PID Reference W PID controller user reference Percent AV18 User PID Feedback W...

Страница 64: ...ftware Revision Protocol Version Protocol Revision Protocol Services Supported Protocol Object Type Supported Object List Max APDU Length Accepted Segmentation Supported APDU Timeout Number of APDU Re...

Страница 65: ...d Object Types Supported An object type is supported if it may be present in the device For each standard Object Type supported provide the following data 1 Whether objects of this type are dynamicall...

Страница 66: ...s No Does the BBMD support network address translation Yes No Network Security Options Non secure Device is capable of operating without BACnet Network Security Secure Device is capable of using BACne...

Страница 67: ...lies Model Number Supply Voltage Phases Frequency ODV 3 x2xxxx 1xxx xx 200 240 Volts 10 1 50 60 Hz ODV 3 x2xxxx 3xxx xx 200 240 Volts 10 3 50 60 Hz ODV 3 x4xxxx 3xxx xx 380 480 Volts 10 3 50 60 Hz ODV...

Страница 68: ...5 3 380 480 Volt 10 3 Phase Input 3 Phase Output Frame Size Power Rating Input Current Fuse or MCB Type B Maximum Cable Size Rated Output Current Maximum Motor Cable Length kW HP A Non UL UL mm AWG kc...

Страница 69: ...derated The maximum cable lengths stated here are based on hardware limitations and do NOT take into consideration any requirements for compliance to any EMC standards Please see section 4 13 EMC Comp...

Страница 70: ...r and Current ratings and the National Electrical Code or other applicable local codes Motor Cable 75 C Copper must be used Power cable connections and tightening torques are shown in sections 3 7 Mou...

Страница 71: ...screw is clearly labelled VAR Frame Sizes 2 3 The EMC Filter and Varistor disconnect screws are located on the left side of the product when viewed from the front Remove both screws completely Frame S...

Страница 72: ...able Frame Size 4kHz 8kHz 10kHz 12kHz 14kHz 16kHz 18kHz 20kHz 24kHz 32kHz IP66 2 N A N A 0 0 0 0 0 0 N A N A 3 N A N A 0 0 0 6 N A N A N A N A IP55 4 N A N A 0 0 12 23 33 41 N A N A 5 N A N A 0 0 1 1...

Страница 73: ...red at 256ms intervals prior to a trip in parameter P0 36 This fault is generally caused by excessive regenerative energy being transferred from the load back to the drive When a high inertia or over...

Страница 74: ...Guidelines for Enclosure mounting IP20 Units thru 3 8 Guidelines for Mounting IP55 Units has been observed and that the cooling airflow path to and from the drive is not restricted Increase the coolin...

Страница 75: ...Loss Output Motor Phase Loss One of the motor output phases is not connected to the drive 50 Modbus Comms fault Modbus communication error detected 52 Option Module Fault Fitted communication Module F...

Страница 76: ...82 HEMAN IN_V3 06f 82 HEMAN IN_V3 06 Invertek Drives Ltd Offa s Dyke Business Park Welshpool Powys SY21 8JF United Kingdom Tel 44 0 1938 556868 Fax 44 0 1938 556869 www invertekdrives com...

Отзывы: