DIGITAL INPUTS – TERMINAL MODE (P-12 = 0, 3 or 4) 

P-19 

Input 1 function 

Input 2 function 

Input 3 function Additional 

Information 

 

Open: 

Stop (disable) 

Closed:

 Run (enable) 

Open: 

Analog input 

Closed:

 Speed Preset 1  

Volts / Current analog input 

The format of the current analog input is 
defined by P-16, if P-16 is set to 0-10V a 4-
20mA  format will be assumed when input 3 
closed

 

 

Open: 

Stop (disable) 

Closed:

 Run (enable) 

Open: 

Analog input 

Closed: 

Speed Preset 1/2, 

 (Digital Input 3 selects) 

Open:   

Speed Preset 1 

Closed:

 Speed Preset 2 

 

 

2

 

Open: 

Stop (disable) 

Closed:

 Run (enable) 

Digital Input 2: 

Open

   \ 

Digital Input 3: 

Open 

  / 

Digital Input 3: 

Open   \ 

Digital Input 2: 

Closed /

 

Digital Input 3: 

Closed \ 

Digital Input 2: 

Open

   / 

Digital Input 3: 

Closed

 \ 

Digital Input 2: 

Closed / 

 Selects Speed Preset 1 

 

 Selects Speed Preset 2 

 

 Selects Speed Preset 3 

 

 Selects Speed Preset 4 

 

 

Open: 

Stop (disable) 

Closed:

 Run (enable) 

External trip input: 

Open: 

TRIP; 

Closed:

 OK 

Open: 

Analog Input 

Closed:

 Speed Preset 1 

 

 

Normally Open (N.O.) 
Momentarily Close to run 

Normally Closed (N.C.) 
Momentarily Open to stop 

Open: 

Analog Input 

Closed:

 Speed Preset 1 

 

 

Open: 

Stop (disable) 

Closed:

 Run (enable) 

Close to run 
Open to fast stop (P-07) 

Open: 

Analog Input 

Closed:

 Speed Preset1 

Wire break mode. Fast stop (P-07) activated 
when input 1 & input 2 closed at same time. 

 

DIGITAL INPUTS – KEYPAD MODE (P-12 = 1 or 2) 

P-19 

Input 1 function 

Input 2 function 

Input 3 function Additional 

Information 

 

0,1,2,4,5 

Open: 

Stop (disable) 

Closed:

 Run (enable) 

Closed:

 remote up pushbutton 

Closed:

 remote down pushbutton 

Closing inputs 2 & 3 at same time 
starts the drive. 
 

 

Open: 

Stop (disable) 

Closed:

 Run (enable) 

External trip input: 

Open: 

TRIP; 

Closed:

 no trip 

Open: 

Keypad speed reference 

Closed:

 Preset / Jog Speed 1 

Speed reference is set by 
pushbuttons. 

 

 

TROUBLESHOOTING 
TO CLEAR A TRIP CONDITION

 

Remove the condition which caused the trip and press the STOP key or re-enable the drive. 

The drive will restart according to the mode selected by P-30. 
If the motor is stopped and the display shows STOP, there is no fault; the drive output is disabled and the drive is ready to run.  
 

Fault Code 

What has happened 

What to do 

P-deF Default 

parameters loaded 

Press STOP key, drive is ready to configure for particular application 

O-I 

 

Over current on drive output. 
Excess load on the motor. 
Over temperature on the 
heatsink  

Motor at constant speed: investigate overload or malfunction. Motor 
starting:
 load stalled or jammed. Check for star-delta motor wiring error.  
Motor accelerating/decelerating:
 The accel/decel time too short 
requiring too much power. If P-03 or P-04 cannot be increased, a bigger 
drive is needed  

O-Uolt 

Over voltage on DC bus 

Supply problem, or increase decel ramp time P-04. 

U-Uolt 

Under voltage on DC bus 

This occurs routinely when power is switched off. If it occurs during 
running, check power supply voltage. 

I.t-trP 

The drive has tipped on 
overload after delivering 
greater than 100% load for a 
period of time.  

Check to see when the decimal points are flashing (drive in overload) 
and either decrease acceleration rate or load. Check cable length is 
within specification. 

th-Flt Faulty 

thermistor 

on 

heatsink. 

Refer to your IDL Authorised Distributor. 

E-triP 

External trip (on dig. input 2 or 
3) 

External trip on digital input – see P-19 (motor  thermistor?)  

EE-F 

EEPROM fault. Parameters not 
saved, defaults reloaded. 

Try again. If problem recurs, refer to your IDL Authorised Distributor. 

PS-Trp 

Internal power stage fault 

Check wiring to motor, look for ph-ph or ph-Earth short circuit. 
Check drive ambient temp, additional space or cooling needed? 
Check drive is not forced into overload. 

O-t 

Heatsink over temperature 

Check drive ambient temp.  Additional space or cooling needed? 

Iin-F 

Current analog input out of 
range 

Check input current in range defined by P-16 

PARAMETER ZERO

 

Provides a read only window into the motor control software 

allowing key internal values to be viewed. This is useful for 
following signals through the drive control system when 
troubleshooting. 

 

 Access, scroll, change and exit are as for any other parameter. 

The selected variable is at the left hand side of the display. 

 

There are 9 different windows listed below: 

 

1 Unscaled analog input (%)                   7 Applied motor voltage (V) 
2 Speed ref. via scaled analog I/P(Hz)  8 DC bus voltage (V) 
3 Pre-ramp speed ref. (Hz)                       9 Internal thermistor  
4 Post-ramp speed ref. (Hz)                       (NTC) value 
5 Not used 
6 Stator field frequency (Hz) 

OPTIDRIVE E1/EF1 SIZE 1 - 115V Input Voltage                                       OPTIDRIVE E1/EF1 SIZE 1 - 230V Input Voltage                                    

             OPTIDRIVE E1/EF1 SIZE 2  - 110V/240V Input Voltage

 

GENERAL TECHNICAL 
DATA 

 

Supply frequency 48 

to 62 Hz. 

 

Max. permissible 3-

phase supply 
imbalance 3%. 

 

Max. ambient 

temperature 50 

o

C. 

 

Max. altitude 2000 m. 

 

Derate above 1000 m, 

1% / 100 m. 

 

Derate output current 

5%/

 o

C above max. 

ambient temp up to 
55

o

C  

 

I

 

x t protection above 

100% output current. 

 

150% overload 

protection for 60 sec. 

 

175% overload 

allowable for 2 sec. 

 

Storage temperature -

40 to +60 

o

 

OPTIDRIVE DIMENSIONS & TORQUE SETTINGS

 

Size 1 

Size 2 

Length  mm / in 

155 / 6.10” 

260 / 10.24” 

Width mm / in 

80 / 3.15” 

100 / 3.98” 

Depth  mm / in 

130 / 5.12” 

175 / 6.89” 

Weight kg / lb 

1.1 / 2.42 

2.6 / 5.72 

A  mm / in 

72 / 2.83” 

92 / 3.62” 

B  mm / in 

4 / 0.16” 

C  mm / in 

25 / 0.98” 

D  mm / in 

105 / 4.13” 

210 / 8.27” 

Fixings 

2 * M4 (2 x 8-32) 

Power terminal torque settings 

1 Nm/ 8.86 in.lbs 

1 Nm/ 8.86 in.lbs 

 
ENCLOSURE - NON VENTED DIMENSIONS 

SEALED UNIT 

DRIVE POWER RATING 

W H  D 

Size 1    115V / 230V 

300/11.81” 

400/15.75” 

200/9.84” 

Size 2    115V / 230V 

450/17.72” 

600/23.62” 

300/11.81” 

 
ENCLOSURE – VENTED DIMENSIONS 

VENTED UNIT 

DRIVE POWER RATING 

W H D 

Size 1 All ratings 

300/ 

11.81” 

400/ 

15.75” 

150/ 

5.91” 

Size 2 All ratings 

400/ 

15.75” 

600/ 

23.62” 

250 

9.42” 

 

DRIVE 

POWER 
RATING 

FORCE VENTED (WITH 

FAN) 

 

W H  D 

Air 

Flow  

Size 1 All 
ratings 

200/ 

7.87” 

300/ 

11.81” 

150/ 

5.91” 

> 15m

3

 

/ h 

Size 2 All 
ratings 

300 

11.81” 

  400/ 

15.75” 

250/ 

9.84” 

> 45m

3

 

/ h 

Model  

ODE1-xxxxx-IN/USA 

12037 / 

12050 

12075 / 

12100 

Supply voltage 

+/- 10% 

220-240 

Phases  

Motor output rating  
 

kW Hp 

0.37 

0.5 

0.75 

Output Amps 

4.3 

Fuse or Circuit Breaker 
rating 

A 10 

20 

Max ambient temperature 

o

C 8kHz

 

o

C 16kHz

 

o

C 32kHz 

 

40 
30 

 

40 
30 

Motor cable size, Cu 75C 

AWG 

16 

14 

Max motor cable length  

m/ ft 

50 / 160’ 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

STANDARD PARAMETER SET 

Par. Description 

Range 

Default 

Explanations 

Set to 

P-01 

Maximum speed  

P-02 to 5*P-09 (max 500Hz) 

50Hz 

Maximum speed limit – Hz or rpm. See P-10 

 

P-02 

Minimum speed 

0 to P-01 (max 500Hz) 

10Hz 

Minimum speed limit – Hz or rpm. See P-10 

 

P-03 

Accel ramp time (s) 

0 to 3,000s 

5s 

Acceleration ramp time from 0 to base speed (P-9) in seconds 

 

P-04 

Decel ramp time (s) 

0 to 3,000s 

5s 

Deceleration ramp time from base speed (P-9) to 0 in seconds 

 

P-05 

Stop mode select 

0, 2: Ramp stop 
1: Coast to stop 

If the supply is lost and P-05=0 then the drive will try to continue running by reducing 
the speed of the load using the load as a generator.  
If P-05=2, the drive ramps at P-07 to stop. 

 

P-06 V/F 

characteristic 

0: Constant torque, 

INDUSTRIAL

    

1..10: Pump/fan, 

HVAC

 

Either V = kf (linear) or V = kf 

2

 (pumps / fans with HVAC rating). Note when P-06 is set 

to 1 the ramps are automatically set to 60 s. 

 

P-07 

Fast stop (s) 

0.0 to 25s.   (Disabled when 0.0s) 

0.0s 

Deceleration ramp time after mains loss (P-05 = 0 or 2) or when fast stop activated 
(see P-19).  
When P-05 = 2 and P-07 = 0, activating the fast stop disables the drive without braking 
(effectively coasting to stop). 

 

P-08 

Motor rated current  

25% -100% of drive current rating  

Drive rating 

Rated (nameplate) current of the motor (Amps). In HVAC (P-06 = 1) mode, the rated 
motor current limit is increased, allowing P-08 to be set to a higher level  

 

P-09 

Motor rated frequency 

25Hz to 500Hz 

50 Hz 

(60Hz - HP) 

Rated (nameplate) frequency of the motor. Changing P-09 resets P-02, P-10, P-26 & P-
28 to 0, & P-01=P-09. 

 

P-10 

Motor rated speed 

0, P-09*12 to P-09*60 
eg for 50Hz motor, range is 600 to 
3000 rpm 

When non-zero, speed is displayed in rpm in parameters P-01, P-02, P-20…P-23,  
P-27 and P-28 

 

P-11 

Voltage boost 

0 to 25% of max output voltage 

3% 

Applies an adjustable boost to the Optidrive voltage output at low speed to assist 
with starting ‘sticky’ loads. For continuous applications at low speed use a forced 
ventilated motor. 

 

P-12 

Terminal or Keypad control  

0: Terminal control 
1: Keypad control – fwd only 
2: Keypad control 

 fwd and rev 

3: Terminal control  
4: Not used 

0  (Terminal 

control) 

When P-12 = 2, the keypad START key toggles between forward and reverse. When 
stopped, target speed can be accessed / changed using the STOP &   , 

buttons. 

 
3: Terminal control  

 

P-13 

Trip log 

Last four trips stored 

Read only 

Most recent 4 trips stored in order of occurrence, ie on entry, display shows most 
recent first. Press   or 

to step through all four 

 

P-14 

Extended menu access  

Code 0 to 9999 

Set to “101” (default) for extended menu access. Change code in     P-37 to prevent 
unauthorised access to the Extended Parameter Set 

 

 

EXTENDED PARAMETER SET 

Par. Description 

Range 

Default 

Explanations 

Set to  

P-15 

Motor rated voltage 

115V product: 40V to 150V 
230V product: 40V to 250V 

115V for 115V 
230V for 230V 

When P-15 is non-zero, the applied motor voltage is controlled and scaled so that 
the specified voltage is achieved at rated freq (P-09) 

 

P-16 

Analog input format (V / mA) 

Voltage: 0-10V, 10-0V  
Current: 4-20mA, 0-20mA, 20-4mA 

0-10V 

Analog input format (on terminal 6). If a current input format is set & P-19=0, Digital 
input 3 must be closed for the current input to be configured. 

 

P-17 

Switching frequency 

8, 16, 32 kHz  

16 kHz 

Effective power stage switching frequency. Improvements in acoustic noise and 
output current waveform occur with increasing switching frequency at the expense 
of increased losses within the drive  

 

P-18 

Relay output function 

0: Drive enabled 
1: Drive healthy (not tripped) 
2: Motor at set speed  
3: Motor speed > zero   
4: Motor at max speed (P-01) 
5: Motor current overload 

Relay output function. Contacts closed if selected condition is true. 
When P-18= 3, (zero speed), the relay contacts close when the output frequency is 
greater than 5% of base frequency. 
The drive is in overload when the motor current exceeds P-08 

 

P-19 

Digital inputs function 
select 

0 to 5, See digital input table 

Defines function of digital inputs (see also P-16 and Digital Inputs table) 

 

P-20 

Preset speed 1 

-P-02 (min) to P-01 (max) 

50hz/rpm 

Defines  Speed Preset1 

 

P-21 

Preset speed 2 

-P-02 (min) to P-01 (max) 

0 Hz/rpm 

Defines  Speed Preset 2 

 

P-22 

Preset speed 3 

-P-02 (min) to P-01 (max) 

0 Hz/rpm 

Defines  Speed Preset 3 

 

P-23 

Preset speed 4 

-P-02 (min) to P-01 (max) 

0 Hz/rpm 

Defines  Speed Preset 4 

 

P-24 Reserved 

 

 

 

 

 

P-25 
 

Analog output function 
 

(A) 0:Motor Speed  1:Motor current 
(D) 2:Drive enabled  3: Set speed 

 

Analog output select. When P-25 = 0 then 10V = 100% of P-01, or if P-25 =1 then 10V 
= 200% of P-08. 
P-25 = 2 or 3 gives a 10V digital output. 

 

P-26 Reserved 

 

 

 

 

P-27 

Skip freq / speed 

P-02 (min)  to P-01 (max) 

0 (inactive) 

Centre point for skip frequency band. The skip frequency band defined by P-27, P-
28 is mirrored around zero for negative speeds. 

 

P-28 

Skip freq / speed band 

0 to100% of rated speed/freq. P-09 

0 Hz / rpm 

Width of skip frequency band, the center of which is defined by P-27. 

 

P-29 Reserved 

 

 

 

 

P-30 

Drive start mode 

Edge-r: Close Digital input 1 after 
             power up to start drive 
Auto-0: drive runs whenever 
Digital input 1 closed. 
Auto-1..4: as Auto-0, except 1..4  
             Attempts to restart after a 
             trip 

Auto-0 

When set to Edge-r, if drive is powered up with Digital Input 1 closed (enabled), 
drive will not run. The switch must be opened & closed after
 power up or after a 
clearing a trip for the drive to run. 
When set to Auto-0, drive will run whenever digital input 1 is closed (if not tripped).  
Auto-1..4 makes 1..4 attempts to automatically restart after a trip (25s between 
attempts). If fault has cleared drive will restart. Drive must be powered down, reset 
on the keypad or reset by re-enabling the drive to reset auto-reset counter. 
When P-12 is set to 1 or 2, P-30 changes automatically to Edge-r. 

 

P-31 

Boost frequency 

0 to 250Hz 

50Hz 

Optidrive1ph start up frequency maintained during the startup boost period 

 

P-32 

Boost duration 

0 to 25s 

2s 

Time for which the startup boost period is maintained 

 

P-33 

Boost start voltage 

0 to 100% 

20% 

% of operational motor voltage applied at start of startup boost period. The applied 
voltage is increased to the operational voltage at end of startup boost period. 

 

P-34 Reserved 

 

 

 

 

P-35 

Analog input scaling factor 

25% to 500% 

80% at 50Hz, 

84% at 60Hz 

Scales the analog input at control terminal 6 up or down, or the digital reference in 
keypad (or Slave) mode up or down (see P-12).   

 

P-36 

Drive address (s-comms) 

0 to 63  (0=disable) 

Distinct drive address for serial comms. 0 = comms disabled 

 

P-37 

Access code definition 

0 to 9999 

101 

Defines Extended Parameter Set access code, P-14 

 

P-38 

Parameter access lock 

0: Parameters can be changed, 

auto-saved on power down  

1: Parameter changes not saved 

on power down 

2: Read-only. No changes allowed.  

0 (write 

access and 

auto-save are 

enabled) 

Controls user access to parameters. WhenP-38 = 0, all parameters can be changed 
and these changes will be stored automatically. When P-38 = 1, changes may be 
made but these will not be stored when the Optidrive1ph powers down. When P-38 
= 2, parameters are locked and cannot be changed thus preventing unauthorised 
access. 

 

P-39 

Hours run meter 

0 to 99999 hours 

Read only 

Not affected by reset-to-default command 

 

P-40 

Software checksum 

0000 to FFFF (hex) 

Read only 

Drive rating, drive type and software version codes 

 

 

OPTIDRIVE - E OPTIONS

The following additional 
products are available: 

ƒ

 

Internal and external 

EMC filters to meet EN 
61000-6-3 / -4 for 
conducted emissions 

ƒ

 

Dual relay output and 

dual analog input, 
2ROUT& 2ANIN  

ƒ

 

Feedback control card, 

PICON 

ƒ

 

Enclosed (IP55) 

Optidrives 

ƒ

 

Optidrive Coolplate 

with heatsink removed 
for mounting to a cooled 
surface 

FURTHER INFORMATION

The Website, 

www.invertek.co.uk

, contains the following 

information: 

ƒ

 

General product information, including Product and Options 

Manuals 

ƒ

 

Application notes and Software product upgrade files 

ƒ

 

Company and IDL authorised dealer information 

Voltage / Frequency (V/f) 
Characteristic 

 
The V/f characteristic is defined by 
parameter P-06 as shown. 
Increasing the value of P-06 
decreases the volts applied to the 
motor at a given frequency;  
reducing the voltage reduces the 
amount of current flowing in the 
motor hence the torque at the 
motor shaft.  This feature is used to 
save energy in applications where 
the torque required at low speeds 
is less than at higher speeds. A 
particular value of P-06 should be 
determined by trial and error. 

Optidrive E  V/F Curves

0.0%

10.0%

20.0%

30.0%

40.0%

50.0%

60.0%

70.0%

80.0%

90.0%

100.0%

0

10

20

30

40

50

60

Frequency

% of

 F

ull O

ut

put

 V

olt

age

 

P-06=0 

P-06=5 

P-06=10 

Model  

ODE1-xxxxx-USA 

11050 

Supply  voltage 

+/- 10% 

110-115 

Phases  

 

Motor output rating  
 

KW  

HP  

0.37 

0.5 

Output Amps 

7.0 

Fuse or Circuit Breaker 
rating 

A 10 

Max ambient temperature 

o

C 8kHz

 

o

C 16kHz

 

o

C 32kHz 

 

40 
30 

Motor cable size, Cu 75C 

AWG 

14 

Max motor cable length  

m/ ft 

50 / 160’ 

Model  

ODE1-xxxxx-IN/USA 

21075 

22110 / 

22150 

Supply voltage 

+/- 10% 

110-115 

220-240 

Phases  

Motor output rating 

HP  

kW 

3/4 

0.55 

1.5 
1.1 

Output current  

10.5 

10.5 

Fuse or circuit breaker 
rating  

A 20 

20 

Max ambient 
temperature 

o

C 8kHz

 

o

C 16kHz 

o

C 32kHz 

 

40 
30 

 

40 
30 

Motor cable size, Cu 75C 

AWG 

14 

14 

Max motor cable length  

m/ft 

100 / 320’ 

100 / 320’ 