Optidrive E3 Advanced Technical Manual Issue 05.Docx
66 / 69
9
. G
ene
ra
l Tech
ni
cal
an
d P
er
fo
rma
nce
D
at
a
9.2.2
230V Input
Frame
Size
Supply
Voltage
Power
Rating
(kW)
Input
Current
(A)
iTHD
(%)
AC
Line
Choke
Input
Current
(A)
iTHD
(%)
Output
Current
(A)
1
230V, 1ph
0.37
3.7
<175%
OPT-2-L1016-20
2.9
2.3
0.75
7.5
<175%
OPT-2-L1016-20
6.6
4.3
1.5
12.9
<175%
OPT-2-L1016-20
9.7
7.0
230V, 3ph
0.37
3.4
<85.0
OPT-2-L3006-20
3.4
2.3
0.75
5.6
<85.0
OPT-2-L3006-20
5.6
4.3
1.5
9.5
<85.0
OPT-2-L3010-20
6.3
7.0
2
230V, 1ph
1.5
12.9
<125.0
OPT-2-L1016-20
11.4
7.0
2.2
19.2
<100.0
OPT-2-L1025-20
17.0
10.5
230V, 3ph
1.5
8.9
<85.0
OPT-2-L3006-20
7.0
7.0
2.2
12.1
<85.0
OPT-2-L3010-20
9.9
10.5
3
230V, 1ph
4.0
29.2
<125.0
-
25.9
15.3
230V, 3ph
4.0
20.9
<85.0
OPT-2-L3036-20
13.5
18
5.5
26.4
<85.0
OPT-2-L3036-20
17.4
24
4
230V, 3ph
5.5
26.9
<85.0
OPT-2-L3036-20
22.0
24
7.5
33.3
<85.0
OPT-2-L3036-20
27.7
30
11
50.1
<85.0
OPT-2-L3050-20
41.7
46
The data above is provided to show typical values. Results measured at the point of installation may vary according to the installation site and
load conditions Test results are measured under the following conditions:-
230 Volt RMS AC Supply Voltage
Operating IE2 motor with matching power rating according to the drive
Operated at full rated output current capacity
9.2.3
400 / 460 Volt Input
Frame
Size
Supply
Voltage
Power
Rating
(kW)
Input
Current
(A)
iTHD
(%)
AC
Line
Choke
Input
Current
(A)
iTHD
(%)
Output
Current
(A)
1
400V, 3ph
0.75
3.5
<85.0
OPT-2-L3006-20
1.5
2.2
1.5
5.6
<85.0
OPT-2-L3006-20
2.7
4.1
2
1.5
5.6
<85.0
OPT-2-L3006-20
4.5
4.1
2.2
7.5
<85.0
OPT-2-L3006-20
5.5
5.8
4.0
11.5
<85.0
OPT-2-L3010-20
9.2
9.5
3
5.5
17.2
<85.0
OPT-2-L3036-20
14.5
14
7.5
21.2
<85.0
OPT-2-L3036-20
17.2
18
11
27.5
<85.0
OPT-2-L3036-20
21.7
24
4
15
34.2
<85.0
OPT-2-L3036-20
27.0
30
18.5
44.1
<85.0
OPT-2-L3050-20
34.8
39
22
51.9
<85.0
OPT-2-L3050-20
40.9
46
The data above is provided to show typical values. Results measured at the point of installation may vary according to the installation site and
load conditions Test results are measured under the following conditions:-
400 Volt RMS AC Supply Voltage
Operating IE2 motor with matching power rating according to the drive
Operated at full rated output current capacity
9.3
Standby Power Consumption
The following table shows the power consumption of the drive under the following conditions.
Drive is powered from the nominal rated mains supply voltage (e.g. 230 or 400 Volt)
Output disabled
Cooling fan off
No external power drawn from the control terminals
Frame Size
Voltage
Phase
Consumption
1
230
1
3.07W
230
3
3.07W
400
3
4.55W
2
230
1
4.51W
230
3
4.51W
400
3
6.44W
3
230
1
5.16W
230
3
5.16W
400
3
6.42W
4
230
3
7.54W
400
3
14.6W