Optidrive E3 Advanced Technical Manual Issue 05.Docx
19 / 69
2
. Opt
id
rive
E3
Par
amet
er
Set Ov
er
vi
ew
2.6.5
Macro Functions - Keypad Mode (P-12 = 1 or 2)
P-15
DI1
DI2
DI3 / AI2
DI4 / AI1
Diagram
0
1
0
1
0
1
0
1
0
STOP
ENABLE
-
INC SPD
-
DEC SPD
FWD
REV
8
˄------------------ START -----------------˄
1
STOP
ENABLE
PI REF
2
STOP
ENABLE
-
INC SPD
-
DEC SPD
KPD REF
P-20 REF
8
˄------------------ START -----------------˄
3
STOP
ENABLE
-
INC SPD
E-TRIP
(NC)
-
DEC SPD
9
˄---------------------------------------- START -------------------------------˄
4
STOP
ENABLE
-
INC SPD
KPD REF
AI1 REF
Analog Input AI1
10
5
STOP
ENABLE
FWD
REV
KPD REF
AI1 REF
Analog Input AI1
1
6
STOP
ENABLE
FWD
REV
E-TRIP
(NC)
KPD REF
P-20 REF
11
7
STOP
RUN FWD
STOP
RUN REV
E-TRIP
(NC)
KPD REF
P-20 REF
11
˄-----------FAST STOP (P-24)--------------˄
8
STOP
RUN FWD
STOP
RUN REV
KPD REF
AI1 REF
Analog Input AI1
1
14
STOP
RUN
-
-
E-TRIP
(NC)
-
-
15
STOP
RUN
PR REF
KPD REF
Fire Mode
P-23
P-21
2
16
STOP
RUN
P-23 REF
KPD REF
Fire Mode
FWD
REV
2
17
STOP
RUN
KPD REF
P-23 REF
Fire Mode
FWD
REV
2
18
STOP
RUN
AI1 REF
KPD REF
Fire Mode
Analog Input AI1
1
9,10,11,12, 13 = 0
2.6.6
Macro Functions - Fieldbus Control Mode (P-12 = 3, 4, 7, 8 or 9)
P-15
DI1
DI2
DI3 / AI2
DI4 / AI1
Diagram
0
1
0
1
0
1
0
1
0
STOP
ENABLE
FB REF (Fieldbus Speed Reference, Modbus RTU / CAN / Master-Slave defined by P-12)
14
1
STOP
ENABLE
PI REF
15
3
STOP
ENABLE
FB REF
P-20 REF
E-TRIP
(NC)
Analog Input AI1
3
5
STOP
ENABLE
FB REF
PR REF
P-20
P-21
Analog Input AI1
1
˄------START (P-12 = 3 or 4 Only)--------˄
6
STOP
ENABLE
FB REF
AI1 REF
E-TRIP
(NC)
Analog Input AI1
3
˄------START (P-12 = 3 or 4 Only)--------˄
7
STOP
ENABLE
FB REF
KPD REF
E-TRIP
(NC)
Analog Input AI1
3
˄------START (P-12 = 3 or 4 Only)--------˄
14
STOP
ENABLE
-
-
E-TRIP
(NC)
Analog Input AI1
16
15
STOP
ENABLE
PR REF
FB REF
Fire Mode
P-23
P-21
2
16
STOP
ENABLE
P-23 REF
FB REF
Fire Mode
Analog Input AI1
1
17
STOP
ENABLE
FB REF
P-23 REF
Fire Mode
Analog Input AI1
1
18
STOP
ENABLE
AI1 REF
FB REF
Fire Mode
Analog Input AI1
1
2,4,8,9,10,11,12,13 = 0
2.6.7
Macro Functions - User PI Control Mode (P-12 = 5 or 6)
P-15
DI1
DI2
DI3 / AI2
DI4 / AI1
Diagram
0
1
0
1
0
1
0
1
0
STOP
ENABLE
PI REF
P-20 REF
Analog Input AI2
Analog Input AI1
4
1
STOP
ENABLE
PI REF
AI1 REF
Analog Input AI2 (PI FB)
Analog Input AI1
4
3, 7
STOP
ENABLE
PI REF
P-20
E-TRIP
(NC)
Analog Input AI1 (PI FB)
3
4
(NO)
START
(NC)
STOP
Analog Input AI2 (PI FB)
Analog Input AI1
12
5
(NO)
START
(NC)
STOP
PI REF
P-20 REF
Analog Input AI1 (PI FB)
5
6
(NO)
START
(NC)
STOP
E-TRIP
(NC)
Analog Input AI1 (PI FB)
8
STOP
RUN
FWD
REV
Analog Input AI2 (PI FB)
Analog Input AI1
4
14
STOP
RUN
-
-
E-TRIP
(NC)
Analog Input AI1 (PI FB)
16
15
STOP
RUN
P-23 REF
PI REF
Fire Mode
Analog Input AI1 (PI FB)
1
16
STOP
RUN
P-23 REF
P-21 REF
Fire Mode
Analog Input AI1 (PI FB)
1
17
STOP
RUN
P-21 REF
P-23 REF
Fire Mode
Analog Input AI1 (PI FB)
1
18
STOP
RUN
AI1 REF
PI REF
Fire Mode
Analog Input AI1 (PI FB)
1
2,9,10,11,12,13 = 0