Optidrive E3 Advanced Technical Manual Issue 05.Docx
34 / 69
4
. Fi
el
db
us
Int
er
face
Support
Modbus
RTU
Register
CAN
Open
Index
Par.
Description
Format
Min
Max
Data format / scaling
172
2090h
44
User PI reference select
U16
0
1
See parameter description for details
173
2091h
45
User PI digital reference
U16
0
1000
1dp, e.g. 100 =10.0%
174
2092h
46
User PI feedback select
U16
0
3
See parameter description for details
175
2093h
47
Analog Input 2 Format
U16
0
6
0: 0...10V
1: 0…20mA
2: t 4...20mA
3: r 4...20mA
4: t 20...4mA
5: r 20...4mA
6: Ptc-th
176
2094h
48
Standby Mode Timer
U16
0
250
1dp, e.g. 250 = 25.0s
177
2095h
49
PI Wake Up Error Level
U16
0
1000
1dp, e.g. 50 = 5.0%
178
2096h
50
User Relay Output Hysteresis
U16
0
1000
1dp e.g. 100 = 10.0%
179
2097h
51
Motor Control Mode
U16
0
5
0 : IM Vector
1 : V/F
2 : PM Motor
3 : BLDC Motor
4 : SynRM Motor
180
2098h
52
Motor Parameter Autotune
U16
0
1
181
2099h
53
Vector Mode Gain
U16
0
2000
1dp, e.g. 500 = 50.0%
182
209Ah
54
Maximum Current Limit
U16
0
1750
1dp, e.g. 1000 = 100.0%
183
209Bh
55
Motor Stator Resistance
U16
0
65535
2dp, e.g. 100 = 1.00R
184
209Ch
56
Motor Stator d-axis
Inductance (Lsd)
U16
0
65535
1dp, e.g. 1000 = 100.0mH
185
209Dh
57
Motor Stator q-axis
Inductance (Lsq)
U16
0
65535
1dp, e.g. 1000 = 100.0mH
186
209Eh
58
DC Injection Speed
U16
0
P-01
3000 = 50.0Hz
187
209Fh
59
DC Injection Current
U16
0
1000
1dp, e.g. 100 = 10.0%
188
20A0h
60
Thermal Overload Retention
U16
0
1
4.7
Additional Information
4.7.1
Drive Control Word Format
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
High byte
Low byte
Bit 0:
Run/Stop command: Set to 1 to enable the drive. Set to 0 to stop the drive.
Bit 1:
Fast stop request. Set to 1 to enable drive to stop with 2
nd
deceleration ramp.
Bit 2:
Reset request. Set to 1 in order to reset the drive if drive is under trip condition.
User must clear this bit when drive is under normal condition to prevent un-expected reset.
Bit 3:
Coast stop request. Set to 1 to issue a coast stop command.
For normal operation, Bit 3 has the highest priority, bit 0 has the lowest priority (bit 3>bit 1>bit 0). For example if user set command as 0x0009,
drive will do a coast stop rather than run. For normal run/start, just set this register to 1.
Note that stat/stop (bit 0), fast stop (bit 1) and coast stop (bit 3) only works if P-31= 0 or 1. Otherwise, start/stop function is controlled by drive
control terminals. Reset function (bit 2) works all the time as long as drive is operated under Modbus control mode (P-12=3 or 4).
4.7.2
Speed Reference Format (Standard resolution)
Speed reference value is transferred with one decimal place (200 = 20.0Hz). The maximum speed reference value is limited by P-01. Either
register 2 or register 5 can be used for speed reference control, however only one reference should be used in any control system, otherwise
unexpected behaviour can result.
4.7.3
Acceleration / Deceleration Ramp Time
Active only when P-12 = 4, this register specifies the drive acceleration and deceleration ramp time. The same value is applied simultaneously
to the acceleration and deceleration ramp times. The value has two decimal places, e.g. 500 = 5.00 seconds.
4.7.4
High Resolution Speed Reference
This register allows the user to set the speed reference value in the internal format, e.g. 3000 = 50.0Hz. This allows control resolution to 1 RPM
with a 2 pole motor. The maximum allowed value is limited by P-01.
Either register 2 or register 5 can be used for speed reference control, however only one reference should be used in any control system,
otherwise unexpected behaviour can result.