Version 1.00
| Fieldbus Guide |
41
www.invertekdrives.com
11
Additional Status Registers
Modbus
RTU
Register
CAN
Open
Index
Sub
Index
PDO
Map
Parameter
Number
Upper byte Lower Byte Format Type Scaling
-
280Bh
0
N
P0-17
Motor Current Log 8
U16
R
1dp, e.g. 100 = 10.0A
-
280Ch
0
N
P0-18
DC Ripple Log 1
U16
R
1 = 1 Volt
-
280Dh
0
N
P0-18
DC Ripple Log 2
U16
R
1 = 1 Volt
280Eh
0
N
P0-18
DC Ripple Log 3
U16
R
1 = 1 Volt
-
280Fh
0
N
P0-18
DC Ripple Log 4
U16
R
1 = 1 Volt
-
2810h
0
N
P0-18
DC Ripple Log 5
U16
R
1 = 1 Volt
-
2811h
0
N
P0-18
DC Ripple Log 6
U16
R
1 = 1 Volt
-
2812h
0
N
P0-18
DC Ripple Log 7
U16
R
1 = 1 Volt
-
2813h
0
N
P0-18
DC Ripple Log 8
U16
R
1 = 1 Volt
-
2814h
0
N
P0-25
Estimated Rotor Speed
S16
R
-
2815h
0
N
P0-32
Actual PWM Frequency
U16
R
-
2816h
0
N
P0-31
Motor Current iD
U16
R
-
2817h
0
N
P0-31
Motor Current iQ
U16
R
-
2818h
0
N
P0-33
O-I Trip Counter
U16
R
-
2819h
0
N
P0-34
O-V Trip Counter
U16
R
-
281Ah
0
N
P0-35
U-V Trip Counter
U16
R
-
281Bh
0
N
P0-36
O-T Trip Counter
U16
R
-
281Ch
0
N
P0-37
bO-I Trip Counter
U16
R
-
281Dh
0
N
P0-38
O-Heat Trip Counter
U16
R
11.4.1. High Resolution Speed Reference
This register allows the user to set the speed reference value in the internal format, e.g. 3000 = 50.0Hz. This allows control resolution
to 1 RPM with a 2-pole motor. The maximum allowed value is limited by P-01.
Either register 2 or register 5 can be used for speed reference control, however only one reference should be used in any control
system, otherwise unexpected behaviour can result.
11.4.2. Scope Channel Data Values
These registers show the scope present data sample value for the first two scope channels. The channel data source selection is
carried out through Optitools Studio.
11.4.3. Modbus RTU Registers 25 - 28: Drive Serial Number
The drive serial number may be read using these four registers. The serial number has 11 digits, stored as follows:
Register 28
Register 27
Register 26
Register 25
x
x
x
x
x
x
x
x
x
x
x
e.g.
Register 25
1
Register 26
1
Register 27
8745
Register 28
57
Drive Serial Number
5
7
8
7
4
5
0
1
0
0
1
11.4.4. Parameter Checksum Modbus Register 46
A checksum is calculated based on the present value of all user adjustable parameters and stored in Modbus Register 46. This may
be read to determine if parameter settings have been adjusted.