10.7. Profibus DP Gateway Features – OD-PROFB-IN
Complete PROFIBUS-DP slave functionality according to IEC 61158.
Supports all common baud rates up to 12 Mbit (detected automatically).
Up to 64 bytes of I/O data in each direction, allowing up to 8 Optidrives to be connected to a single gateway.
Galvanically isolated bus electronics.
10.7.1. Installation
10.7.1.1. Overview - Module Front
Configuration Switches
PROFIBUS Connector
LED Indicators
1
2
3
4
5
6
A
B
1
Online
Green
Online
Off
Not Online
2
Offline
Red
Offline
Off
Not Offline
3
Not Used
-
-
4
Fieldbus
Diagnostics
Off
No diagnostics present
Red, Flashing 1Hz
Configuration Error
Red, Flashing 2Hz
User parameter data error
Red, Flashing 4Hz
Initialisation Error
5
Subnet Status Flashing Green
Running, but one or more transaction errors
Green
Running
Red
Transaction error / subnet stopped
6
Device Status Off
Power Off
Alternating Red / Green
Invalid / missing configuration
Green
Initialising
Flashing Green
Running
Red
Bootloader Mode
Flashing Red
Diagnostic Code
A
Set the PROFIBUS node address by using the switches as follows:
Node address = (switch B * 10) + (switch A * 1)
B
Example:
Setting node address 42
Switch A
Switch B
2
4
01
2345
678
9
01
2345
678
9
1
2
4
5
1
6
9
Bottom View
PC Connector:
1. GND
2. GND
3. RS232 Rx
4. RS232 Tx
Power:
1. +24 V DC
2. GND
1
DB9
Profibus Connector
Pin no Description
1
+5V
5
Female
1
9
6
1
Shield
2
RS232 Rx (Not Used)
3
B-line
3
RS232 Tx (Not Used)
4
RTS
4
NC
5
GND bus
5
Signal 0V
6
+5V bus out
6
RS422 Rx+ (Not Used)
8
A-line
7
RS422 Rx- (Not Used)
2, 7, 9
NC
8
RS485+ Modbus RTU
9
RS485- Modbus RTU
Power
1
+24VDC, 300mA
2
0V