![Invertek Drives Optidrive Compact 2-Basic OPC-2 E Series Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/invertek-drives/optidrive-compact-2-basic-opc-2-e-series/optidrive-compact-2-basic-opc-2-e-series_user-manual_2085095012.webp)
12
| Fieldbus Guide |
Version 1.00
www.invertekdrives.com
5
CAN
5.4. PDO Default Mapping
Objects
No.
Mapped
Object
Length
Mapped Function
Transmission Type
For information
on the values
RX
PDO1
1
2000h
Unsigned 16
Control command register*
254
Valid immediately
2
2001h
Integer 16
Speed reference
3
2003h
Unsigned 16
User ramp reference
4
0006h
Unsigned 16
Dummy
TX
PDO1
1
200Ah
Unsigned 16
Drive status register
254
Send after receiving
RX PDO 1
2
200Bh
Integer 16
Motor speed Hz
3
200Dh
Unsigned 16
Motor current
4
2010h
Integer 16
Drive temperature
RX
PDO2
1
0006h
Unsigned 16
Dummy
254
2
0006h
Unsigned 16
Dummy
3
0006h
Unsigned 16
Dummy
4
0006h
Unsigned 16
Dummy
TX
PDO2
1
2011h
Unsigned 16
DC bus voltage
254
2
2012h
Unsigned 16
Digital input status
3
2013h
Integer 16
Analog input 1 (%)
4
2014h
Integer 16
Analog input 2 (%)
* Drive control can only be achieved when P-12=7 or 8 provided that P-31 = 0, 1, 4 or 5.
5.5. PDO Transmission Type
Various transmission modes can be selected for each PDO. For RX PDO, the following modes are supported:
Transmission Type
Mode
Description
0 – 240
Synchronous
The received data will be transferred to the drive active control register when the next sync
message is received.
254, 255
Asynchronous
The received data will be transferred to the drive active control register immediately without delay.
For TX PDO, the following modes are supported:
Transmission Type
Mode
Description
0
Acyclic synchronous TX PDO will only be sent out if the PDO data has changed and PDO will be transmitted on
reception of SYNC object.
1-240
Cyclic synchronous
TX PDO will be transmitted synchronously and cyclically. The transmission type indicates the
number of SYNC object that are.
254
Asynchronous
TX PDO will only be transferred once corresponding RX PDO has been received.
255
Asynchronous
TX PDO will only be transferred anytime if PDO data value has changed.
5.6. CAN Specific Object Table
Index
Sub Index
Function
Access
Type
PDO Map
Default Value
1000h
0
Device Type
RO
U32
N
0
1001h
0
Error Register
RO
U8
N
0
1002h
0
Manufacturer Status Register
RO
U16
N
0
1005h
0
COB-ID Sync
RW
U32
N
00000080h
1008h
0
Manufacturer Device Name
RO
String
N
ODE3
1009h
0
Manufacturer Hardware Version
RO
String
N
x.xx
100Ah
0
Manufacturer Software Version
RO
String
N
x.xx
100Ch
0
Guard Time (1ms)
RW
U16
N
0
100Dh
0
Lifetime Factor
RW
U8
N
0
1014h
0
COB-ID EMCY
RW
U32
N
00Node ID
1015h
0
Inhibit Time Emergency (100μs)
RW
U16
N
0