Optidrive ODE-3 1Ph Output User Guide Revision 1.00 

28 

www.invertekdrives.com 

 

 

10

 

Tr

o

u

b

le

 Sh

oo

ti

n

10.

 

Trouble Shooting 

10.1.

 

Fault Code Messages 

Fault 
Code

 

No.

 

Description

 

Suggested Remedy 



00 

No Fault 

Not required 



01 

Brake channel over current 

Check external brake resistor condition and connection wiring 



02 

Brake resistor overload 

The drive has tripped to prevent damage to the brake resistor 



03 

Output Over Current 

Instantaneous Over current on the drive output. Excess load or shock load on the motor. 



04 

Motor Thermal Overload (I2t) 

The drive has tripped after delivering >100% of value in P-08 for a period of time to prevent damage to 
the motor. 



05 

Power stage trip 

Check for short circuits on the motor and connection cable 



06 

Over voltage on DC bus 

Check the supply voltage is within the allowed tolerance for the drive. If the fault occurs on deceleration 
or stopping, increase the deceleration time in P-04 or install a suitable brake resistor and activate the 
dynamic braking function with P-34 



07 

Under voltage on DC bus 

The incoming supply voltage is too low. This trip occurs routinely when power is removed from the drive. 
If it occurs during running, check the incoming power supply voltage and all components in the power 
feed line to the drive. 



08 

Heatsink over temperature 

The drive is too hot. Check the ambient temperature around the drive is within the drive specification. 
Ensure sufficient cooling air is free to circulate around the drive.  
Increase the panel ventilation if required. Ensure sufficient cooling air can enter the drive, and that the 
bottom entry and top exit vents are not blocked or obstructed. 



09 

Under temperature 

Trip occurs when ambient temperature is less than -10°C.  Temperature must be raised over -10°C in 
order to start the drive. 



10 

Factory Default parameters loaded   



11 

External trip 

E-trip requested on digital input 3.  Normally closed contact has opened for some reason. If motor 
thermistor is connected check if the motor is too hot. 



12 

Optibus comms loss 

Check communication link between drive and external devices. Make sure each drive in the network has 
its unique address. 



13 

DC bus ripple too high 

Check incoming supply phases are all present and balanced 



14 

Input phase loss trip 

Check incoming power supply phases are present and balanced. 



15 

Output Over Current 

Check for short circuits on the motor and connection cable 



16 

Faulty thermistor on heatsink 

 



17 

Internal memory fault. (IO) 

Press the stop key. If the fault persists, consult you supplier. 



18 

4-20mA Signal Lost 

Check the analog input connection(s). 



19 

Internal memory fault. (DSP) 

Press the stop key. If the fault persists, consult you supplier. 



21 

Motor PTC thermistor trip  

Connected motor thermistor over temperature, check wiring connections and motor 



22 

Cooling Fan Fault (IP66 only) 

Check / replace the cooling fan 



23 

Drive internal temperature too high  Drive ambient temperature too high, check adequate cooling air is provided 



50 

Modbus comms loss fault 

Check the incoming Modbus RTU connection cable 
Check that at least one register is being polled cyclically within the timeout limit set in P-36 Index 3 



51 

CANopen comms loss trip 

Check the incoming CAN connection cable 
Check that cyclic communications take place within the timeout limit set in P-36 Index 3 

 
 
 
 
 
 
 
 
 
 
 
 



 

 82-E31PH-IN_V1.00 

Содержание optidrive E IP20

Страница 1: ...h Output User Guide Revision 1 00 www invertekdrives com 1 1 Quick Start Up User Guide Single Phase Output IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 1 1kW 0 5 1 5HP 110 230V Installation and Oper...

Страница 2: ...ection Diagram 13 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 14 4 10 Control Terminal Connections 14 5 Operation 15 5 1 Managing the Keypad 15 5 2 Changing Parameters 15 5 3 Read On...

Страница 3: ...h EMC standards is dependent on a number of factors including the environment in which the drive is installed motor switching frequency motor cable lengths and installation methods adopted Compliance...

Страница 4: ...t which normally will be limited by the fuses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work...

Страница 5: ...4X Enclosed Units Guidelines for mounting IP66 Units 8 8 8 9 5 Select the correct power and motor cables according to local wiring regulations or code noting the maximum permissible sizes 9 2 Rating T...

Страница 6: ...to Start Open to Stop Connect a potentiometer 5k 10k between terminals as shown to vary the speed from P 2 0Hz default to P 01 50 60 Hz default 0 10V 0 50 60Hz Quick Start IP66 Switched Switch the uni...

Страница 7: ...c Brake Transistor 1 Not Fitted 4 Internal Transistor Frame Size Filter Type 0 No Filter F Internal EMC Filter Input Voltage 1 110 115 2 200 240 No Of Input Phases Output Current x 10 2 2 Drive Model...

Страница 8: ...environments according to IEC 664 1 For pollution degree 2 or higher environments drives should be mounted in a suitable control cabinet with sufficient ingress protection to maintain a pollution deg...

Страница 9: ...t be mounted vertically on a suitable flat surface The minimum mounting clearances as shown in the table below must be observed The mounting site and chosen mountings should be sufficient to support t...

Страница 10: ...conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for installation using rigid conduit system Power Isolator Lock Off On t...

Страница 11: ...der joist a floor ground rod or bus bar Grounding points must comply with national and local industrial safety regulations and or electrical codes Motor Ground The motor ground must be connected to on...

Страница 12: ...mains supply for motors which have been wound for operation with a variable speed drive then there is no preventative measures required however if the quality of insulation is unknown then the motor...

Страница 13: ...ons A Incoming Power Supply B External Isolator Disconnect C External MCB or Fuse D Optional Input Choke E Optional Input Filter F Optional Brake Resistor G Shielded Motor Cable H Analog Digital Outpu...

Страница 14: ...d 1 STOP Run PI Control 5 6 0 Selectable PI control or preset speed Run Pot STOP Run PI Control 5 6 0 Selectable PI control or Pot speed control Enable STOP Enable 7 8 0 Control from CAN interface Run...

Страница 15: ...Read Only Parameter Access 5 4 Resetting Parameters Press and hold the Navigate key 2 seconds Press and hold the Navigate key 2 seconds To reset parameter values to their factory default settings pre...

Страница 16: ...um Speed Preset Speeds etc will also be displayed in RPM Note If P 09 value is changed P 10 value is reset to 0 P 11 Start Boost Voltage 0 0 100 0 3 0 This parameter sets the initial voltage applied t...

Страница 17: ...mit set in P 19 9 Drive Ready to Run Logic 1 when the drive is ready to run no trip present P 19 Relay Threshold Level 0 0 200 0 100 0 Adjustable threshold level used in conjunction with settings 4 to...

Страница 18: ...inal Enable 3 Previous Speed Terminal Enable 4 Current Speed Keypad Start 5 Preset Speed 4 Keypad Start 6 Current Speed Terminal Start 7 Preset Speed 4 Terminal Start P 32 Starting Boost Frequency 0 0...

Страница 19: ...for the PID Reference Setpoint 0 Digital Preset Setpoint P 45 is used 1 Analog Input 1 Setpoint Analog input 1 signal level readable in P00 01 is used for the setpoint P 45 PI Digital Setpoint 0 0 10...

Страница 20: ...process data output outgoing process data TX PDO1 for CANopen PO1 PO2 PO3 PO4 P00 23 Accumulated time with heatsink 85 C Hours Total accumulated hours and minutes of operation above heatsink temp of...

Страница 21: ...Set the Boost Period Duration P 33 to the maximum allowed value of 150 seconds 5 Start the drive and display the motor current press the Navigate button until the display shows x x where x is the mot...

Страница 22: ...reference selected according to other digital input status FAST STOP P 24 When both inputs are active simultaneously the drive stops using Fast Stop Ramp Time P 24 E TRIP External Trip input which mu...

Страница 23: ...9 P 15 DI1 DI2 DI3 AI2 DI4 AI1 Diagram 0 1 0 1 0 1 0 1 0 STOP ENABLE FB REF Fieldbus Speed Reference Modbus RTU CAN Master Slave defined by P 12 1 1 STOP ENABLE PI Speed Reference 5 3 STOP ENABLE FB R...

Страница 24: ...llowing protection features in the drive O t Heat sink Over Temperature U t Drive Under Temperature Th FLt Faulty Thermistor on Heat sink E trip External Trip 4 20 F 4 20mA fault Ph Ib Phase Imbalance...

Страница 25: ...2 Bytes Register Address 2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Che...

Страница 26: ...er a 24 hour period for 200 240V 2 2kW and 3HP IP20 drives is 45 C 9 2 Rating Tables Frame Size kW HP Input Current Fuse MCB Type B Maximum Cable Size Output Current Recommended Brake Resistance Non U...

Страница 27: ...stated in section 9 1 For IP20 units installation is required in a pollution degree 1 environment For IP66 Nema 4X units installation in a pollution degree 2 environment is permissible Electrical Ins...

Страница 28: ...the drive and that the bottom entry and top exit vents are not blocked or obstructed 09 Under temperature Trip occurs when ambient temperature is less than 10 C Temperature must be raised over 10 C i...

Отзывы: