Optidrive ODE-3 1Ph Output User Guide Revision 1.00 

20 

www.invertekdrives.com 

 

 

6

 

Pa

ra

m

eter

6.3.

 

P-00 Read Only Status Parameters 

Par.

 

Description

 

Explanation

 

P00-01

  1

st

 Analog input value (%) 

100% = max input voltage 

P00-02

  2

nd

 Analog input value (%) 

100% = max input voltage 

P00-03

  Speed reference input (Hz / RPM) 

Displayed in Hz if P-10 = 0, otherwise RPM 

P00-04

  Digital input status 

Drive digital input status 

P00-05

  User PI output (%) 

Displays value of the User PI output 

P00-06

  DC bus ripple (V) 

Measured DC bus ripple 

P00-07

  Applied motor voltage (V) 

Value of RMS voltage applied to motor 

P-00-08

  DC bus voltage (V) 

Internal DC bus voltage 

P00-09

  Heatsink temperature (ᵒC) 

Temperature of heatsink in ᵒC 

P00-10

  Run time since date of manuf. (Hours) 

Not affected by resetting factory default parameters 

P00-11

  Run time since last trip (1) (Hours) 

Run-time clock stopped by drive disable (or trip), reset on next enable only if a trip 
occurred.  Reset also on next enable after a drive power down. 

P00-12

  Run time since last trip (2) (Hours) 

Run-time clock stopped by drive disable (or trip), reset on next enable only if a trip 
occurred (under-volts not considered a trip)  –  not reset by power down / power up 
cycling unless a trip occurred prior to power down 

P00-13

  Trip Log 

Displays most recent 4 trips with time stamp 

P00-14

  Run time since last disable (Hours) 

Run-time clock stopped on drive disable, value reset on next enable 

P00-15

  DC bus voltage log (V) 

8 most recent values prior to trip, 256ms sample time 

P00-16

  Heatsink temperature log (ᵒC) 

8 most recent values prior to trip, 30s sample time 

P00-17

  Motor current log (A) 

8 most recent values prior to trip, 256ms sample time 

P00-18

  DC bus ripple log (V) 

8 most recent values prior to trip, 22ms sample time 

P00-19

  Internal drive temperature log (ᵒC) 

8 most recent values prior to trip, 30 s sample time 

P00-20

  Internal drive temperature (ᵒC) 

Actual internal ambient temperature in ᵒC 

P00-21

  CANopen process data input 

Incoming process data  (RX PDO1) for CANopen: PI1, PI2, PI3, PI4 

P00-22

  CANopen process data output 

outgoing process data (TX PDO1) for CANopen:  PO1, PO2, PO3, PO4 

P00-23

  Accumulated time with heatsink > 85ᵒC 

(Hours) 

Total accumulated hours and minutes of operation above heatsink temp of 85ᵒC 

P00-24

  Accumulated time with drive internal temp > 

80ᵒC (Hours) 

Total accumulated hours and minutes of operation with drive internal ambient above 
80C 

P00-25

  Estimated rotor speed (Hz) 

In vector control modes, estimated rotor speed in Hz 

P00-26

  kWh meter / MWh meter 

 

Total number of kWh / MWh consumed by the drive.   

P00-27

  Total run time of drive fans (Hours) 

Time displayed in hh:mm:ss.   First value displays time in hrs, press up to display 
mm:ss. 

P00-28

  Software version and checksum 

Version number and checksum.  “1” on LH side indicates I/O processor, “2“ indicates 
power stage 

P00-29

  Drive type identifier 

Drive rating, drive type and software version codes 

P00-30

  Drive serial number 

Unique drive serial number 

P00-31

  Motor current Id / Iq 

Displays the magnetising current (Id) and torque current (Iq). Press UP to show Iq 

P00-32

  Actual PWM switching frequency (kHz) 

Actual switching frequency used by drive 

P00-33

  Critical fault counter – O-I 

These parameters log the number of times specific faults or errors occur, and are 
useful for diagnostic purposes. 
  
  
  
  
  
  
  
  
  

P00-34

  Critical fault counter – O-Volts 

P00-35

  Critical fault counter – U-Volts 

P00-36

  Critical fault counter – O-temp (h/sink) 

P00-37

  Critical fault counter – b O-I (chopper) 

P00-38

  Critical fault counter – O-hEAt (control) 

P00-39

  Modbus comms error counter 

P00-40

  CANbus comms error counter 

P00-41

  I/O processor comms errors 

P00-42

  Power stage uC comms errors 

P00-43

  Drive power up time (life time) (Hours) 

 Total lifetime of drive with power applied 

P00-44

  Phase U current offset & ref 

 Internal value 

P00-45

  Phase V current offset & ref 

 Internal value 

P00-46

  Phase W current offset & ref 

 Internal value 

P00-47

  Index 1 : Fire mode total active time 

Index 2 : Fire Mode Activation Count 

 Total activation time of Fire Mode 
Displays the number of times Fire Mode has been activated 

P00-48

  Scope channel 1 & 2 

 Displays signals for first scope channels 1 & 2 

P00-49

  Scope channel 3 & 4 

 Displays signals for first scope channels 3 & 4 

P00-50

  Bootloader and motor control 

 Internal value 

 

 

 

Содержание optidrive E IP20

Страница 1: ...h Output User Guide Revision 1 00 www invertekdrives com 1 1 Quick Start Up User Guide Single Phase Output IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 1 1kW 0 5 1 5HP 110 230V Installation and Oper...

Страница 2: ...ection Diagram 13 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 14 4 10 Control Terminal Connections 14 5 Operation 15 5 1 Managing the Keypad 15 5 2 Changing Parameters 15 5 3 Read On...

Страница 3: ...h EMC standards is dependent on a number of factors including the environment in which the drive is installed motor switching frequency motor cable lengths and installation methods adopted Compliance...

Страница 4: ...t which normally will be limited by the fuses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work...

Страница 5: ...4X Enclosed Units Guidelines for mounting IP66 Units 8 8 8 9 5 Select the correct power and motor cables according to local wiring regulations or code noting the maximum permissible sizes 9 2 Rating T...

Страница 6: ...to Start Open to Stop Connect a potentiometer 5k 10k between terminals as shown to vary the speed from P 2 0Hz default to P 01 50 60 Hz default 0 10V 0 50 60Hz Quick Start IP66 Switched Switch the uni...

Страница 7: ...c Brake Transistor 1 Not Fitted 4 Internal Transistor Frame Size Filter Type 0 No Filter F Internal EMC Filter Input Voltage 1 110 115 2 200 240 No Of Input Phases Output Current x 10 2 2 Drive Model...

Страница 8: ...environments according to IEC 664 1 For pollution degree 2 or higher environments drives should be mounted in a suitable control cabinet with sufficient ingress protection to maintain a pollution deg...

Страница 9: ...t be mounted vertically on a suitable flat surface The minimum mounting clearances as shown in the table below must be observed The mounting site and chosen mountings should be sufficient to support t...

Страница 10: ...conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for installation using rigid conduit system Power Isolator Lock Off On t...

Страница 11: ...der joist a floor ground rod or bus bar Grounding points must comply with national and local industrial safety regulations and or electrical codes Motor Ground The motor ground must be connected to on...

Страница 12: ...mains supply for motors which have been wound for operation with a variable speed drive then there is no preventative measures required however if the quality of insulation is unknown then the motor...

Страница 13: ...ons A Incoming Power Supply B External Isolator Disconnect C External MCB or Fuse D Optional Input Choke E Optional Input Filter F Optional Brake Resistor G Shielded Motor Cable H Analog Digital Outpu...

Страница 14: ...d 1 STOP Run PI Control 5 6 0 Selectable PI control or preset speed Run Pot STOP Run PI Control 5 6 0 Selectable PI control or Pot speed control Enable STOP Enable 7 8 0 Control from CAN interface Run...

Страница 15: ...Read Only Parameter Access 5 4 Resetting Parameters Press and hold the Navigate key 2 seconds Press and hold the Navigate key 2 seconds To reset parameter values to their factory default settings pre...

Страница 16: ...um Speed Preset Speeds etc will also be displayed in RPM Note If P 09 value is changed P 10 value is reset to 0 P 11 Start Boost Voltage 0 0 100 0 3 0 This parameter sets the initial voltage applied t...

Страница 17: ...mit set in P 19 9 Drive Ready to Run Logic 1 when the drive is ready to run no trip present P 19 Relay Threshold Level 0 0 200 0 100 0 Adjustable threshold level used in conjunction with settings 4 to...

Страница 18: ...inal Enable 3 Previous Speed Terminal Enable 4 Current Speed Keypad Start 5 Preset Speed 4 Keypad Start 6 Current Speed Terminal Start 7 Preset Speed 4 Terminal Start P 32 Starting Boost Frequency 0 0...

Страница 19: ...for the PID Reference Setpoint 0 Digital Preset Setpoint P 45 is used 1 Analog Input 1 Setpoint Analog input 1 signal level readable in P00 01 is used for the setpoint P 45 PI Digital Setpoint 0 0 10...

Страница 20: ...process data output outgoing process data TX PDO1 for CANopen PO1 PO2 PO3 PO4 P00 23 Accumulated time with heatsink 85 C Hours Total accumulated hours and minutes of operation above heatsink temp of...

Страница 21: ...Set the Boost Period Duration P 33 to the maximum allowed value of 150 seconds 5 Start the drive and display the motor current press the Navigate button until the display shows x x where x is the mot...

Страница 22: ...reference selected according to other digital input status FAST STOP P 24 When both inputs are active simultaneously the drive stops using Fast Stop Ramp Time P 24 E TRIP External Trip input which mu...

Страница 23: ...9 P 15 DI1 DI2 DI3 AI2 DI4 AI1 Diagram 0 1 0 1 0 1 0 1 0 STOP ENABLE FB REF Fieldbus Speed Reference Modbus RTU CAN Master Slave defined by P 12 1 1 STOP ENABLE PI Speed Reference 5 3 STOP ENABLE FB R...

Страница 24: ...llowing protection features in the drive O t Heat sink Over Temperature U t Drive Under Temperature Th FLt Faulty Thermistor on Heat sink E trip External Trip 4 20 F 4 20mA fault Ph Ib Phase Imbalance...

Страница 25: ...2 Bytes Register Address 2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Che...

Страница 26: ...er a 24 hour period for 200 240V 2 2kW and 3HP IP20 drives is 45 C 9 2 Rating Tables Frame Size kW HP Input Current Fuse MCB Type B Maximum Cable Size Output Current Recommended Brake Resistance Non U...

Страница 27: ...stated in section 9 1 For IP20 units installation is required in a pollution degree 1 environment For IP66 Nema 4X units installation in a pollution degree 2 environment is permissible Electrical Ins...

Страница 28: ...the drive and that the bottom entry and top exit vents are not blocked or obstructed 09 Under temperature Trip occurs when ambient temperature is less than 10 C Temperature must be raised over 10 C i...

Отзывы: