6.2.

 

Extended Parameters 

Par. 

Description 

Minimum 

Maximum 

Default 

Units 

P-15 

Digital Input Function Select 

17 

Defines the function of the digital inputs depending on the control mode setting in P-12.  See section 7 Analog and Digital Input 
Macro Configurations for more information. 

P-16 

Analog Input 1 Signal Format 

See Below 

U0-10 



 = Uni-polar 0 to 10 Volt Signal. The drive will remain at minimum speed (P-02) if the analog reference after scaling and 

offset are applied is =<0.0%. 100% signal means the output frequency / speed will be the value set in P-01. 



 = 0 to 20mA Signal 



 =  4 to 20mA Signal, the Optidrive will trip and show the fault code 



 if the signal level falls below 3mA 



 = 4 to 20mA Signal, the Optidrive will run at Preset Speed 1 (P-20)  if the signal level falls below 3mA 



 = 20 to 4mA Signal, the Optidrive will trip and show the fault code 



 if the signal level falls below 3mA 



 = 20 to 4mA Signal, the Optidrive will run at Preset Speed 1 (P-20)   if the signal level falls below 3mA 



 = 10 to 0 Volt Signal (Uni-polar). The drive will operate at Maximum Frequency / Speed if the analog reference after scaling 

and offset are applied is =<0.0% 

P-17 

Maximum Effective Switching Frequency 

32 

kHz 

Sets maximum effective switching frequency of the drive. If “rEd” is displayed when the parameter is viewed, the switching frequency has 
been reduced to the level in P00-32 due to excessive drive heatsink temperature.

 

P-18 

Output Relay Function Select 

Selects the function assigned to the relay output. The relay has two output terminals, Logic 1 indicates the relay is active, and 
therefore terminals 10 and 11 will be connected. 

0

 

: Drive Enabled (Running)

. Logic 1 when the motor is enabled 

1 : Drive Healthy

. Logic 1 when power is applied to the drive and no fault exists 

2

 

: At Target Frequency (Speed)

. Logic 1 when the output frequency matches the setpoint frequency 

3 : Drive Tripped

. Logic 1 when the drive is in a fault condition 

4

 

: Output Frequency >= Limit

. Logic 1 when the output frequency exceeds the adjustable limit set in P-19 

5

 

: Output Current >= Limit

. Logic 1 when the motor current exceeds the adjustable limit set in P-19 

6

 

: Output Frequency < Limit

. Logic 1 when the output frequency is below the adjustable limit set in P-19 

7

 

: Output Current < Limit

. Logic 1 when the motor current is below the adjustable limit set in P-19 

8 : Analog Input 2 > Limit

. Logic 1 when the signal applied to analog input 2 exceeds the adjustable limit set in P-19 

9 : Drive Ready to Run

. Logic 1 when the drive is ready to run, no trip present. 

P-19 

Relay Threshold Level 

0.0 

200.0 

100.0 

Adjustable threshold level used in conjunction with settings 4 to 8 of P-18 

P-20 

Preset Frequency / Speed 1 

0.0 

P-01 

5.0 

Hz / RPM 

P-21 

Preset Frequency / Speed 2 

0.0 

P-01 

25.0 

Hz / RPM 

P-22 

Preset Frequency / Speed 3 

0.0 

P-01 

40.0 

Hz / RPM 

P-23 

Preset Frequency / Speed 4 

0.0 

P-01 

P-09 

Hz / RPM 

Preset Speeds / Frequencies selected by digital inputs depending on the setting of P-15 
If P-10 = 0, the values are entered as Hz. If P-10 > 0, the values are entered as RPM. 

Note

 

 Changing the value of P-09 will reset all values to factory default settings 

P-24 

2nd Ramp Time (Fast Stop) 

0.00 

600.0 

0.00 

This parameter allows a 2

nd

 ramp time to be programmed into the drive. 

This ramp time is automatically selected in the case of a mains power loss if P-05 = 2 or 3. When set to 0.00, the drive will coast to 
stop. 
When using a setting of P-15 that provides a “Fast Stop” function, this ramp time is also used. 

P-25 

Analog Output Function Select 

10 

Digital Output Mode. Logic 1 = +24V DC  

0 : Drive Enabled (Running)

. Logic 1 when the Optidrive is enabled (Running) 

1 : Drive Healthy

. Logic 1 When no Fault condition exists on the drive 

2 : At Target Frequency (Speed)

. Logic 1 when the output frequency matches the setpoint frequency 

3: Drive Tripped

. Logic 1 when the drive is in a fault condition 

4

 

: Output Frequency >= Limit

. Logic 1 when the output frequency exceeds the adjustable limit set in P-19 

5

 

: Output Current >= Limit

. Logic 1 when the motor current exceeds the adjustable limit set in P-19 

6

 

: Output Frequency < Limit

. Logic 1 when the output frequency is below the adjustable limit set in P-19 

7

 

: Output Current < Limit

. Logic 1 when the motor current is below the adjustable limit set in P-19 

Analog Output Mode 

8 : Output Frequency (Motor Speed)

. 0 to P-01, resolution 0.1Hz 

9 : Output (Motor) Current

. 0 to 200% of P-08, resolution 0.1A 

10 : Output Power

. 0 – 200% of drive rated power. 

P-26 

Skip frequency hysteresis band 

0.0 

P-01 

0.0 

Hz / RPM 

P-27 

Skip Frequency Centre Point 

0.0 

P-01 

0.0 

Hz / RPM 

The Skip Frequency function is used to avoid the Optidrive operating at a certain output frequency, for example at a frequency 
which causes mechanical resonance in a particular machine. Parameter P-27 defines the centre point of the skip frequency band, 
and is used in conjunction with P-26. The Optidrive output frequency will ramp through the defined band at the rates set in P-03 and 
P-04 respectively, and will not hold any output frequency within the defined band. If the frequency reference applied to the drive is 
within the band, the Optidrive output frequency will remain at the upper or lower limit of the band. 
 
 
 

Содержание optidrive E IP20

Страница 1: ...h Output User Guide Revision 1 00 www invertekdrives com 1 1 Quick Start Up User Guide Single Phase Output IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 1 1kW 0 5 1 5HP 110 230V Installation and Oper...

Страница 2: ...ection Diagram 13 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 14 4 10 Control Terminal Connections 14 5 Operation 15 5 1 Managing the Keypad 15 5 2 Changing Parameters 15 5 3 Read On...

Страница 3: ...h EMC standards is dependent on a number of factors including the environment in which the drive is installed motor switching frequency motor cable lengths and installation methods adopted Compliance...

Страница 4: ...t which normally will be limited by the fuses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work...

Страница 5: ...4X Enclosed Units Guidelines for mounting IP66 Units 8 8 8 9 5 Select the correct power and motor cables according to local wiring regulations or code noting the maximum permissible sizes 9 2 Rating T...

Страница 6: ...to Start Open to Stop Connect a potentiometer 5k 10k between terminals as shown to vary the speed from P 2 0Hz default to P 01 50 60 Hz default 0 10V 0 50 60Hz Quick Start IP66 Switched Switch the uni...

Страница 7: ...c Brake Transistor 1 Not Fitted 4 Internal Transistor Frame Size Filter Type 0 No Filter F Internal EMC Filter Input Voltage 1 110 115 2 200 240 No Of Input Phases Output Current x 10 2 2 Drive Model...

Страница 8: ...environments according to IEC 664 1 For pollution degree 2 or higher environments drives should be mounted in a suitable control cabinet with sufficient ingress protection to maintain a pollution deg...

Страница 9: ...t be mounted vertically on a suitable flat surface The minimum mounting clearances as shown in the table below must be observed The mounting site and chosen mountings should be sufficient to support t...

Страница 10: ...conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for installation using rigid conduit system Power Isolator Lock Off On t...

Страница 11: ...der joist a floor ground rod or bus bar Grounding points must comply with national and local industrial safety regulations and or electrical codes Motor Ground The motor ground must be connected to on...

Страница 12: ...mains supply for motors which have been wound for operation with a variable speed drive then there is no preventative measures required however if the quality of insulation is unknown then the motor...

Страница 13: ...ons A Incoming Power Supply B External Isolator Disconnect C External MCB or Fuse D Optional Input Choke E Optional Input Filter F Optional Brake Resistor G Shielded Motor Cable H Analog Digital Outpu...

Страница 14: ...d 1 STOP Run PI Control 5 6 0 Selectable PI control or preset speed Run Pot STOP Run PI Control 5 6 0 Selectable PI control or Pot speed control Enable STOP Enable 7 8 0 Control from CAN interface Run...

Страница 15: ...Read Only Parameter Access 5 4 Resetting Parameters Press and hold the Navigate key 2 seconds Press and hold the Navigate key 2 seconds To reset parameter values to their factory default settings pre...

Страница 16: ...um Speed Preset Speeds etc will also be displayed in RPM Note If P 09 value is changed P 10 value is reset to 0 P 11 Start Boost Voltage 0 0 100 0 3 0 This parameter sets the initial voltage applied t...

Страница 17: ...mit set in P 19 9 Drive Ready to Run Logic 1 when the drive is ready to run no trip present P 19 Relay Threshold Level 0 0 200 0 100 0 Adjustable threshold level used in conjunction with settings 4 to...

Страница 18: ...inal Enable 3 Previous Speed Terminal Enable 4 Current Speed Keypad Start 5 Preset Speed 4 Keypad Start 6 Current Speed Terminal Start 7 Preset Speed 4 Terminal Start P 32 Starting Boost Frequency 0 0...

Страница 19: ...for the PID Reference Setpoint 0 Digital Preset Setpoint P 45 is used 1 Analog Input 1 Setpoint Analog input 1 signal level readable in P00 01 is used for the setpoint P 45 PI Digital Setpoint 0 0 10...

Страница 20: ...process data output outgoing process data TX PDO1 for CANopen PO1 PO2 PO3 PO4 P00 23 Accumulated time with heatsink 85 C Hours Total accumulated hours and minutes of operation above heatsink temp of...

Страница 21: ...Set the Boost Period Duration P 33 to the maximum allowed value of 150 seconds 5 Start the drive and display the motor current press the Navigate button until the display shows x x where x is the mot...

Страница 22: ...reference selected according to other digital input status FAST STOP P 24 When both inputs are active simultaneously the drive stops using Fast Stop Ramp Time P 24 E TRIP External Trip input which mu...

Страница 23: ...9 P 15 DI1 DI2 DI3 AI2 DI4 AI1 Diagram 0 1 0 1 0 1 0 1 0 STOP ENABLE FB REF Fieldbus Speed Reference Modbus RTU CAN Master Slave defined by P 12 1 1 STOP ENABLE PI Speed Reference 5 3 STOP ENABLE FB R...

Страница 24: ...llowing protection features in the drive O t Heat sink Over Temperature U t Drive Under Temperature Th FLt Faulty Thermistor on Heat sink E trip External Trip 4 20 F 4 20mA fault Ph Ib Phase Imbalance...

Страница 25: ...2 Bytes Register Address 2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Che...

Страница 26: ...er a 24 hour period for 200 240V 2 2kW and 3HP IP20 drives is 45 C 9 2 Rating Tables Frame Size kW HP Input Current Fuse MCB Type B Maximum Cable Size Output Current Recommended Brake Resistance Non U...

Страница 27: ...stated in section 9 1 For IP20 units installation is required in a pollution degree 1 environment For IP66 Nema 4X units installation in a pollution degree 2 environment is permissible Electrical Ins...

Страница 28: ...the drive and that the bottom entry and top exit vents are not blocked or obstructed 09 Under temperature Trip occurs when ambient temperature is less than 10 C Temperature must be raised over 10 C i...

Отзывы: