background image

10

Round Duct connector Installation

1. Apply a bead of caulking, mastic, or other approved 

sealant around bottom side of connector.

2. Install and center the duct connector in the floor opening.

3. Install the mounting plate under the back side of the 

duct connector. See 

Figure 13

notE:

 Align the screw 

holes in both components.

4. Secure the duct connector and the mounting plate to 

the wood floor with appropriate size screws.

5. Connect the round supply duct to the underside of the 

duct connector and secure them with field supplied 

sheet metal screws.

6. Seal all connections with industrial grade sealing tape 

or liquid sealant.

notE: 

Requirements for sealing ductwork vary 

from region to region. Consult with local codes for 

requirements specific to your area.

Installing the Furnace

Sides and back of the furnace may be enclosed by wall 

framing such as in a closet or alcove. The dimensions 

of the room or alcove must be able to accommodate the 
overall size of the furnace shown in 

Figure 4 (page 6)

 

and the installation clearances outlined on 

page 5

. The 

furnace shall be appropriately connected to the supply 
and return air distribution system as shown in 

Figure 14 

(page 10) 

Figure 15 (page 11)

.

1. Remove furnace outer door(s) and bottom fuel line 

knockout.

2. Place furnace onto duct connector and center with floor 

opening.

3. Slide onto mounting plate. (Bottom rear slots on furnace 

should engage with mounting plate tabs.)

4. Secure front with one (1) fastener at each corner. See 

Figure 14 

Figure 15

.

notE:

 Additional fasteners may be used at rear, sides 

or through door frame, as desired, to secure furnace to 

closet or alcove framing.

Figure 10

DUCT CONNECTOR

SUPPLY 

AIR DUCT

BEND TABS TIGHTLY 

AGAINST SUPPLY AIR DUCT

Figure 10. Duct Connector Tabs

Figure 11

Figure 11. narrow air Duct openings

OPTION 1

OPTION 2

Supply 

Air Duct

F

old Flap Here

F

old Flap Here

Remove 

this

Flap

Remove 

this

Flap

Cut Here

Cut Here

Cut Here

Cut Here

Cut Here

Cut Here

Cut Here

Cut Here

Cut Here

F

old Flap Here

F

old Flap Here

Figure 12

Narrow

Duct

Narrow

Duct

Duct connector tabs

Staples or sheet metal screws 

Duct 
Flap

Narrow  

Duct

Duct

Connector

Sheet metal 

screws 

Figure 12. Narrow Ducts

Figure 13

DUCT

CONNECTOR

MOUNTING 

PLATE

SCREWS

FUEL LINE

HOLES

14” SUPPLY CONNECTION

Figure 13. Round Duct connector Installed

Figure 14

MTG. PLATE TABS

SLIDE FURNACE 

ALL THE WAY BACK 

ONTO MTG. PLATE

SUPPLY AIR DUCT

Knockout Over Holes

SECURE FURNACE 

WITH 2 FASTENERS AT FRONT 

CORNER HOLES

Figure 14. “a” & “B” cabinet Furnaces

Содержание M1B Series

Страница 1: ...gas suppliers instructions If you cannot reach your gas supplier call the fire department RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissements de s curit pourrait entra ner des blessure...

Страница 2: ...0 Flue Gas Sampling 21 startup adjustments 22 M1M Operating Instructions 23 How to Shut Off Gas Direct Ignition 23 M5S Operating Instructions 23 M1B Operating Instructions 23 How to Shut Off Gas Oil G...

Страница 3: ...on of the National Fuel Gas Code NFPA54 ANSIZ223 1 ortheNaturalGasandPropane Installation Code CAN CGA B149 1 CEg n rateurd airchauddoit treinstall conform ment aux instructions du fabricant et aux co...

Страница 4: ...equipment where the bottom of the vent terminal and the air intake is installed below four feet above grade the following requirements must be satisfied a Acarbonmonoxide CO detectorandalarmshallbe p...

Страница 5: ...the overall size of the furnace and the installation clearances listed in Table 1 and in Figure 4 page 6 Alcove installations minimum 18 clearance at front of furnace shall be provided for future serv...

Страница 6: ...t or side wall 2 a fully louvered door may be used CLOSET DOOR 6 152 mm 1 25 mm 0 Side Clearance to Furnace Cabinet or in closet door Figure 2 Closet Installation Figure 1 Alcove Installation Figure 4...

Страница 7: ...floor or ceiling registers serving the return air duct system must be at least 235 in2 At least one register should be located where it is not likely to be covered by carpeting boxes and other objects...

Страница 8: ...holesmustbecarefullylocated to avoid misalignment of the furnace and vent piping To locate standard ducts see Figure 6 page 9 For round ducts see Figure 7 1 Measure 10 from the rear wall or alcove and...

Страница 9: ...quirements for sealing ductwork vary from region to region Consult with local codes for requirements specific to your area Figure 6 FLOOR CUT OUT FOR STANDARD DUCT CONNECTORS C L C L C L 24 23 1 4 21...

Страница 10: ...own in Figure 14 page 10 Figure 15 page 11 1 Remove furnace outer door s and bottom fuel line knockout 2 Place furnace onto duct connector and center with floor opening 3 Slideontomountingplate Bottom...

Страница 11: ...must be made below the ceiling This furnace must never be connected to a chimney flue servicing a fireplace or other appliance designed to burn solid fuel NOTE If the roof jack crown is covered or blo...

Страница 12: ...furnace connections For replacement furnaces be sure the inner flue pipe connects over the furnace vent collar DO NOT use a smaller diameter inner flue pipe which could slide inside the furnace vent...

Страница 13: ...Oil Tofurnacewallthermostat 5 Transit mode weather cap to be removed and upper Roof Jack crown installed See Figure 23 Do Not Discard screws 6 PlaceupperRoofJack crown onthefluepipeassembly NOTE Make...

Страница 14: ...time Use of copper conductors is recommended Connecting Power Supply Wires 1 Remove the furnace control panel cover 2 Route wires 115 VAC through the strain relief on the left side of the furnace cont...

Страница 15: ...onnecting Thermostat Wires 1 Insert 24 volt wires through the plastic grommet just above the control panel 2 Connectthethermostatwirestothefurnacelowvoltage pigtails See Figure 25 3 Connect low voltag...

Страница 16: ...M1MC 056 56 000 19 3 4 115 1 60 103 127 8 9 14 20 10 9 18 8 M1MC 070 70 000 19 3 4 115 1 60 103 127 8 9 14 20 10 9 18 8 M1MC 077 77 000 19 3 4 115 1 60 103 127 8 9 14 20 10 9 18 8 M1MC 090 90 000 19...

Страница 17: ...y be used for gas supply systems Fuellineinstallationsotherthantypicalinstallations shown in Figure 26 page 18 Figure 27 page 19 must comply with the fuel piping provisions stated in the Federal Manuf...

Страница 18: ...e Pressure is reduced to 3 1 2 W C by the pressure regulator in the gas valve The maximum inlet pressure for the valve is 7 W C and the minimum inlet pressure is 4 5 W C For L P gas pressure to the ga...

Страница 19: ...A Two Line system should only be used if vertical lift exceeds 8 feet 1 Install the oil feed line as outlined in steps 1 6 below 2 Install the oil pump bypass plug in the bottom return port 3 Route th...

Страница 20: ...Direct Ignition Furnaces 1 Follow the instructions How to Shut Off Gas page 23 2 Disconnect the gas pipe union and the electrical wires connected to the gas valve 3 Remove the gas valve assembly a Re...

Страница 21: ...nace installation A flue gas sample may be taken from the heat exchanger which is located behind the hole of the top front of blower compartment 1 Turn off all electric power to the appliance 2 Remove...

Страница 22: ...i personne ne r pond appeler le service des incendies AVERTISSEMENT startup adjustments PLEASE READ ALL SAFETY INFORMATION BEFORE LIGHTING THE FURNACE WARNING Before placing the furnace in service it...

Страница 23: ...st setting 2 Turn off all electric power to the appliance before servicing unit 3 Set the furnace On Off Switch to OFF Honeywell Figure 30 Turn gas control knob clockwise to OFF Robertshaw Figure 31 P...

Страница 24: ...trol lever to ON 7 Turn electric power to the appliance ON 8 Set the thermostat to HEAT and or the desired temperature setting The furnace should light in approximately 45 seconds If the appliance wil...

Страница 25: ...ergized for a 30 second warm up period After warm up the gas valve opens NOTE The time for ignition is approximately 6 seconds after which the gas valve either remains open if flame is sensed or close...

Страница 26: ...to cut the electrical power to the furnace See Figure 33 Limit Control This furnace is protected by two high temperature safety limit switches The auxiliary upper limit switch and the high temperature...

Страница 27: ...RX1 scale Normalreadingshouldbe40 75ohms If above or below this rating at room temperature changeignitor 3 Check for continuity from ignitor receptacle to burner Control Module is Powered Ignitor won...

Страница 28: ...he igniter terminals and there is no ignition the igniter is likely defective and needs to be replaced 3 If the stops flashing burner turns on but the control locks out again check the cad cell If the...

Страница 29: ...ailed ignition Five flashes L1 neutral reversed or L1 voltage not present on L1 Flame Status A Yellow LED labeled Flame is provided to indicate flame status When flame is sensed the flame LED is lit I...

Страница 30: ...ceoperation Excessiveiceformationcould restrict the combustion air supply to the burner causing inefficient burner operation If excessive ice has formed on the air inlet or exhaust portions of the roo...

Страница 31: ...53 26 43 0 3 x x 1 4 3 M1BC 066 66 53 26 43 0 3 x x 1 2 4 M1BB 086 86 68 18 37 0 3 x x 1 4 3 M1BC 086 86 68 18 37 0 3 x x 1 2 4 M5SB 066 66 56 0 3 50 Gph x Burner Model AF 10 1 4 3 M5SC 066 66 56 0 3...

Страница 32: ...ut MBTUH 45 4 41 8 40 1 38 5 37 0 35 5 34 1 32 7 31 4 30 2 M1M 070 Orifice Size Nat Gas 24 25 26 27 27 28 28 29 29 30 Orifice Size LP 42 42 43 43 43 44 44 45 46 47 Output MBTUH 56 7 52 3 50 2 48 2 46...

Страница 33: ...44 220 439 84 43 214 429 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 1...

Страница 34: ...BLUE MED HI ORANGE MED LO WHITE RED LO BLACK HIGH BLUE MED HI WHITE 6 5 4 3 2 1 LEGENDS 115V FIELD 115V 24V FIELD 24V BLOWER MOTOR 4 SPEED NOTES 1 Incoming power must be polarized Observe color coding...

Страница 35: ...to Table 12 A C Blower Selection 5 If any of the original wire supplied with the appliance is replaced 105 C wire or equivalent 6 Use copper conductors only 7 Flash Codes Refer to Table 9 Control Modu...

Страница 36: ...lter s clean YES NO Flue connections tight YES NO Is there proper draft YES NO ATTENTION INSTALLERS Itisyourresponsibilitytoknowthisproductbetterthanyourcustomer This includes being able to install th...

Отзывы: