Intertherm M1B Series Скачать руководство пользователя страница 11

11

RooF JacK InstallatIon

Required ceiling and roof cut-out openings must be 

carefully located to avoid misalignment of the furnace 

and Roof Jack. 

notE: 

Install only Roof Jack Assemblies 

listed in Table 4 on this heating appliance.

Roof Jack selection

1. Determine depth of ceiling cavity from center of roof 

opening to center of ceiling opening (Dimension A in 

Figure 16

).

2. Determine ceiling height and subtract height of furnace 

(Dimension B in 

Figure 16

).

3. Add  dimensions  A  +  B  (and  X  from 

Table 5, (page 

12)

 & 

Figure 6

  if  slant  deck  flashing  is  used).  The 

total length of [A] + [B] + [X] must be within the minimum 

and maximum range of the Roof Jack listed in 

Table 4

.

Application Notes

•  FAW, FAWT, SAW and SAWT Series Roof Jacks with a 

5” diameter inner vent pipe may be used with all models 

of M1 Series gas and M5 Series oil furnaces.

F = Flat Flashing: flexes from 0/12 to 1/12 roof slope. 

See 

Figure 17 (page 11)

.

S = Slant Flashing: 2.5/12 Slope flexes from 1/12 to

4/12 roof slope, 4/12 flexes from 3/12 to 5/12.

See 

Figure 18 (page 12)

.

•  Stainless steel roof jacks are available.

•  M1/M5 furnaces may be used with roof jacks as tall as 

170” (except M1M 056 & M1B 066 models, which are 

limited to 120”). An internal roof jack extension (p/n 

901935 - 10”, p/n 903107 - 18”) can be used to increase 

roof jack height. All connections inside the home must 

be made below the ceiling.

•  This furnace must never be connected to a chimney 

flue servicing a fireplace or other appliance designed 

to burn solid fuel.

notE:

 If the roof jack crown is covered or blocked 

with snow, the furnace will not operate properly. If the 

home is located in regions where snow accumulation 

exceeds 7” (HUD snowload zones) use an external roof 

jack extension (p/n 901937). Extensions are optional 

accessories and may be purchased through your 

NORDYNE distributor.

Figure 15

FUEL LINE HOLES

MTG. PLATE TABS

SLIDE FURNACE 

BACK AGAINST

MTG. PLATE

SECURE FURNACE 

WITH 2 FASTENERS 

AT FRONT CORNER HOLES

SUPPLY

AIR DUCT

Figure 15. “a” cabinet Furnace on coil cabinet

Figure 16

ROOF JACK

SLANT DECK 

FLASHING

PITCHED 

ROOF

CEILING

CEILING

CAVITY

Roof

Opening

"X" (SEE TABLE 5)

Flue Pipe

Combustion Air Pipe

56" or 76"

Furnace

“A”

“B”

Figure 16. ceiling cavity Depth

Figure 17

Figure 17. Example of Flat Jack with Flashing

ROOF JACK

SLANT DECK 

FLASHING

PITCHED 

ROOF

CEILING

ROOF

OPENING

"X" (SEE TABLE 5)

CEILING

CAVITY

CEILING

OPENING

Table 4

Table 4. Roof Jack assemblies

S

S

AW T

27 47 - 2

AW= ALL WEATHER

FLASHING

PITCH/12" RISE

0=FLAT

2=2.5/12

4=4/12

MIN. ADJ.

LENGTH

 F = FLAT FLASHING

  S = SLANT FLASHING

TYPE:

BLANK = NON-TRANSIT

T= TRANSIT MODE

MAX. ADJ.

LENGTH

FLUE STEEL TYPE

A= ALUMINIZED

S=STAINLESS

MoDEl nuMBER

aPPRoX. lEnGtH

BEloW FlasHInG

(F,S)AW(T)1523-(0,2,4)(A,S)

15” - 23”

(F,S)AW(T)2135-(0,2,4)(A,S)

21” - 35”

(F,S)AW(T)2747-(0,2,4)(A,S)

27” - 47”

(F,S)AW(T)3563-(0,2,4)(A,S)

35” - 63”

(F,S)AW(T)5195-(0,2,4)(A,S)

51” - 95”

Содержание M1B Series

Страница 1: ...gas suppliers instructions If you cannot reach your gas supplier call the fire department RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissements de s curit pourrait entra ner des blessure...

Страница 2: ...0 Flue Gas Sampling 21 startup adjustments 22 M1M Operating Instructions 23 How to Shut Off Gas Direct Ignition 23 M5S Operating Instructions 23 M1B Operating Instructions 23 How to Shut Off Gas Oil G...

Страница 3: ...on of the National Fuel Gas Code NFPA54 ANSIZ223 1 ortheNaturalGasandPropane Installation Code CAN CGA B149 1 CEg n rateurd airchauddoit treinstall conform ment aux instructions du fabricant et aux co...

Страница 4: ...equipment where the bottom of the vent terminal and the air intake is installed below four feet above grade the following requirements must be satisfied a Acarbonmonoxide CO detectorandalarmshallbe p...

Страница 5: ...the overall size of the furnace and the installation clearances listed in Table 1 and in Figure 4 page 6 Alcove installations minimum 18 clearance at front of furnace shall be provided for future serv...

Страница 6: ...t or side wall 2 a fully louvered door may be used CLOSET DOOR 6 152 mm 1 25 mm 0 Side Clearance to Furnace Cabinet or in closet door Figure 2 Closet Installation Figure 1 Alcove Installation Figure 4...

Страница 7: ...floor or ceiling registers serving the return air duct system must be at least 235 in2 At least one register should be located where it is not likely to be covered by carpeting boxes and other objects...

Страница 8: ...holesmustbecarefullylocated to avoid misalignment of the furnace and vent piping To locate standard ducts see Figure 6 page 9 For round ducts see Figure 7 1 Measure 10 from the rear wall or alcove and...

Страница 9: ...quirements for sealing ductwork vary from region to region Consult with local codes for requirements specific to your area Figure 6 FLOOR CUT OUT FOR STANDARD DUCT CONNECTORS C L C L C L 24 23 1 4 21...

Страница 10: ...own in Figure 14 page 10 Figure 15 page 11 1 Remove furnace outer door s and bottom fuel line knockout 2 Place furnace onto duct connector and center with floor opening 3 Slideontomountingplate Bottom...

Страница 11: ...must be made below the ceiling This furnace must never be connected to a chimney flue servicing a fireplace or other appliance designed to burn solid fuel NOTE If the roof jack crown is covered or blo...

Страница 12: ...furnace connections For replacement furnaces be sure the inner flue pipe connects over the furnace vent collar DO NOT use a smaller diameter inner flue pipe which could slide inside the furnace vent...

Страница 13: ...Oil Tofurnacewallthermostat 5 Transit mode weather cap to be removed and upper Roof Jack crown installed See Figure 23 Do Not Discard screws 6 PlaceupperRoofJack crown onthefluepipeassembly NOTE Make...

Страница 14: ...time Use of copper conductors is recommended Connecting Power Supply Wires 1 Remove the furnace control panel cover 2 Route wires 115 VAC through the strain relief on the left side of the furnace cont...

Страница 15: ...onnecting Thermostat Wires 1 Insert 24 volt wires through the plastic grommet just above the control panel 2 Connectthethermostatwirestothefurnacelowvoltage pigtails See Figure 25 3 Connect low voltag...

Страница 16: ...M1MC 056 56 000 19 3 4 115 1 60 103 127 8 9 14 20 10 9 18 8 M1MC 070 70 000 19 3 4 115 1 60 103 127 8 9 14 20 10 9 18 8 M1MC 077 77 000 19 3 4 115 1 60 103 127 8 9 14 20 10 9 18 8 M1MC 090 90 000 19...

Страница 17: ...y be used for gas supply systems Fuellineinstallationsotherthantypicalinstallations shown in Figure 26 page 18 Figure 27 page 19 must comply with the fuel piping provisions stated in the Federal Manuf...

Страница 18: ...e Pressure is reduced to 3 1 2 W C by the pressure regulator in the gas valve The maximum inlet pressure for the valve is 7 W C and the minimum inlet pressure is 4 5 W C For L P gas pressure to the ga...

Страница 19: ...A Two Line system should only be used if vertical lift exceeds 8 feet 1 Install the oil feed line as outlined in steps 1 6 below 2 Install the oil pump bypass plug in the bottom return port 3 Route th...

Страница 20: ...Direct Ignition Furnaces 1 Follow the instructions How to Shut Off Gas page 23 2 Disconnect the gas pipe union and the electrical wires connected to the gas valve 3 Remove the gas valve assembly a Re...

Страница 21: ...nace installation A flue gas sample may be taken from the heat exchanger which is located behind the hole of the top front of blower compartment 1 Turn off all electric power to the appliance 2 Remove...

Страница 22: ...i personne ne r pond appeler le service des incendies AVERTISSEMENT startup adjustments PLEASE READ ALL SAFETY INFORMATION BEFORE LIGHTING THE FURNACE WARNING Before placing the furnace in service it...

Страница 23: ...st setting 2 Turn off all electric power to the appliance before servicing unit 3 Set the furnace On Off Switch to OFF Honeywell Figure 30 Turn gas control knob clockwise to OFF Robertshaw Figure 31 P...

Страница 24: ...trol lever to ON 7 Turn electric power to the appliance ON 8 Set the thermostat to HEAT and or the desired temperature setting The furnace should light in approximately 45 seconds If the appliance wil...

Страница 25: ...ergized for a 30 second warm up period After warm up the gas valve opens NOTE The time for ignition is approximately 6 seconds after which the gas valve either remains open if flame is sensed or close...

Страница 26: ...to cut the electrical power to the furnace See Figure 33 Limit Control This furnace is protected by two high temperature safety limit switches The auxiliary upper limit switch and the high temperature...

Страница 27: ...RX1 scale Normalreadingshouldbe40 75ohms If above or below this rating at room temperature changeignitor 3 Check for continuity from ignitor receptacle to burner Control Module is Powered Ignitor won...

Страница 28: ...he igniter terminals and there is no ignition the igniter is likely defective and needs to be replaced 3 If the stops flashing burner turns on but the control locks out again check the cad cell If the...

Страница 29: ...ailed ignition Five flashes L1 neutral reversed or L1 voltage not present on L1 Flame Status A Yellow LED labeled Flame is provided to indicate flame status When flame is sensed the flame LED is lit I...

Страница 30: ...ceoperation Excessiveiceformationcould restrict the combustion air supply to the burner causing inefficient burner operation If excessive ice has formed on the air inlet or exhaust portions of the roo...

Страница 31: ...53 26 43 0 3 x x 1 4 3 M1BC 066 66 53 26 43 0 3 x x 1 2 4 M1BB 086 86 68 18 37 0 3 x x 1 4 3 M1BC 086 86 68 18 37 0 3 x x 1 2 4 M5SB 066 66 56 0 3 50 Gph x Burner Model AF 10 1 4 3 M5SC 066 66 56 0 3...

Страница 32: ...ut MBTUH 45 4 41 8 40 1 38 5 37 0 35 5 34 1 32 7 31 4 30 2 M1M 070 Orifice Size Nat Gas 24 25 26 27 27 28 28 29 29 30 Orifice Size LP 42 42 43 43 43 44 44 45 46 47 Output MBTUH 56 7 52 3 50 2 48 2 46...

Страница 33: ...44 220 439 84 43 214 429 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 1...

Страница 34: ...BLUE MED HI ORANGE MED LO WHITE RED LO BLACK HIGH BLUE MED HI WHITE 6 5 4 3 2 1 LEGENDS 115V FIELD 115V 24V FIELD 24V BLOWER MOTOR 4 SPEED NOTES 1 Incoming power must be polarized Observe color coding...

Страница 35: ...to Table 12 A C Blower Selection 5 If any of the original wire supplied with the appliance is replaced 105 C wire or equivalent 6 Use copper conductors only 7 Flash Codes Refer to Table 9 Control Modu...

Страница 36: ...lter s clean YES NO Flue connections tight YES NO Is there proper draft YES NO ATTENTION INSTALLERS Itisyourresponsibilitytoknowthisproductbetterthanyourcustomer This includes being able to install th...

Отзывы: