Intertherm M1B Series Скачать руководство пользователя страница 28

28

oil Gun - Honeywell R7184 or Beckett 7505 

controls only - M5s series.

Burner does not start with a call for heat

•  Check the electrical supply to furnace.

•  Verify the furnace door switch is in the 

ON

 position.

•  Check  for  line  voltage  (115  VAC)  at  the  oil  primary 

control.

•  Check indicator LED with burner off, no call for heat (no 

flame). See 

Table 9, (page 29)

.

-  If green LED indicator is on, the cad cell is seeing 

stray light or the cad cell of controller is defective.

-  If green LED indicator is off, go immediately to step 

5.

-  If LED indicator is flashing (red or green on Beckett 

7505 control), refer to the next step 1 below - Reset 

primary control.

•  Jumper 

T

 to 

T

 terminals on primary control.

-  If burner starts, check thermostat or limit wiring 

connections.

-  If burner does not start, turn off power. Check all 

wiring connections.

-  If burner does not start, replace primary control.

Burner starts & then locks out on safety with 
Honeywell R7184 LED indicator flashing ½ 
second on, ½ second off. For Beckett 7505 
control, the red LED will flash

1. Reset primary control: To reset the control from (soft) 

lockout, the button needs only to be pressed and 

released. If the R7184 control is in restricted mode, 

press and hold the button for 45 seconds - until the LED 

flashes once. If the 7505 control is in restricted mode, 

press and hold the button in for 15 seconds until the 

red  turns off and the yellow LED turns on.

notE:

 Restricted Lockout: If the control locks out three 

times in a row without a complete heat cycle between 

attempts, the lockout becomes a restricted (hard) lockout.

2. If  the  LED  indicator  stops  flashing  and  the  ignition 

remains off, the primary control could be defective. If 

line voltage is present at the igniter terminals, and there 

is no ignition, the igniter is likely defective and needs 

to be replaced.

3. If the  stops flashing, burner turns on, but the control 

locks out again, check the cad cell. If the cad cell is 

operational, replace the primary control.

4. If  the  LED  continues  to  flash  at  the  interval  listed 

above, verify that the control is not in restricted mode. 

If in restricted mode, reset it. If not in restricted mode, 

replace the control.

5. If the (LED indicator for R7184 control; green LED for 

7505 control) stays off while the flame is on, check the 

cad cell sighting for view of the flame.

6. If the burner locks out, check the cad cell resistance. 

See 

Table 8

.

7. If the burner stays running, the system is operational.

8. If the (LED indicator for R7184 control; green LED for 

7505 control) is off, check the cad cell assembly after 

disconnecting the line voltage.

Burner will not start and the LED indicator
is flashing at 2 seconds on, 2 seconds off
for R7184 (or green LED is flashing for 7505)

•  Hold the reset button down for 1 - 2 seconds. If LED 

indicator continues to flash, wait for 60 - 70 seconds. If 

it still continues to flash, replace the primary control.

• 

Honeywell R7184 control

: To check cad cell resistance, 

press and release the button during the run mode, with 

the igniter off. The LED will flash to indicate the cad cell 

resistance. For proper burner operation, it is important 

that the cad cell resistance is under 1600 Ohms. For 

cad cell resistance, see 

Table 8

.

• 

Beckett 7505 control

: To check cad cell resistance, 

unplug the cad cell leads (yellow wires) from the control. 

Measure the resistance with a meter in the conventional 

way  (when  a  flame  is  present).  For  proper  burner 

operation, it is important that the cad cell resistance is 

under 1,600 Ohms.

Table 8

Table 8. cad cell Resistance when  

sensing flame

lED FlasHEs (oHMs)

caD cEll REsIstancE

1

0-400

2

400-800

3

800-1600

4

>1600

Содержание M1B Series

Страница 1: ...gas suppliers instructions If you cannot reach your gas supplier call the fire department RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissements de s curit pourrait entra ner des blessure...

Страница 2: ...0 Flue Gas Sampling 21 startup adjustments 22 M1M Operating Instructions 23 How to Shut Off Gas Direct Ignition 23 M5S Operating Instructions 23 M1B Operating Instructions 23 How to Shut Off Gas Oil G...

Страница 3: ...on of the National Fuel Gas Code NFPA54 ANSIZ223 1 ortheNaturalGasandPropane Installation Code CAN CGA B149 1 CEg n rateurd airchauddoit treinstall conform ment aux instructions du fabricant et aux co...

Страница 4: ...equipment where the bottom of the vent terminal and the air intake is installed below four feet above grade the following requirements must be satisfied a Acarbonmonoxide CO detectorandalarmshallbe p...

Страница 5: ...the overall size of the furnace and the installation clearances listed in Table 1 and in Figure 4 page 6 Alcove installations minimum 18 clearance at front of furnace shall be provided for future serv...

Страница 6: ...t or side wall 2 a fully louvered door may be used CLOSET DOOR 6 152 mm 1 25 mm 0 Side Clearance to Furnace Cabinet or in closet door Figure 2 Closet Installation Figure 1 Alcove Installation Figure 4...

Страница 7: ...floor or ceiling registers serving the return air duct system must be at least 235 in2 At least one register should be located where it is not likely to be covered by carpeting boxes and other objects...

Страница 8: ...holesmustbecarefullylocated to avoid misalignment of the furnace and vent piping To locate standard ducts see Figure 6 page 9 For round ducts see Figure 7 1 Measure 10 from the rear wall or alcove and...

Страница 9: ...quirements for sealing ductwork vary from region to region Consult with local codes for requirements specific to your area Figure 6 FLOOR CUT OUT FOR STANDARD DUCT CONNECTORS C L C L C L 24 23 1 4 21...

Страница 10: ...own in Figure 14 page 10 Figure 15 page 11 1 Remove furnace outer door s and bottom fuel line knockout 2 Place furnace onto duct connector and center with floor opening 3 Slideontomountingplate Bottom...

Страница 11: ...must be made below the ceiling This furnace must never be connected to a chimney flue servicing a fireplace or other appliance designed to burn solid fuel NOTE If the roof jack crown is covered or blo...

Страница 12: ...furnace connections For replacement furnaces be sure the inner flue pipe connects over the furnace vent collar DO NOT use a smaller diameter inner flue pipe which could slide inside the furnace vent...

Страница 13: ...Oil Tofurnacewallthermostat 5 Transit mode weather cap to be removed and upper Roof Jack crown installed See Figure 23 Do Not Discard screws 6 PlaceupperRoofJack crown onthefluepipeassembly NOTE Make...

Страница 14: ...time Use of copper conductors is recommended Connecting Power Supply Wires 1 Remove the furnace control panel cover 2 Route wires 115 VAC through the strain relief on the left side of the furnace cont...

Страница 15: ...onnecting Thermostat Wires 1 Insert 24 volt wires through the plastic grommet just above the control panel 2 Connectthethermostatwirestothefurnacelowvoltage pigtails See Figure 25 3 Connect low voltag...

Страница 16: ...M1MC 056 56 000 19 3 4 115 1 60 103 127 8 9 14 20 10 9 18 8 M1MC 070 70 000 19 3 4 115 1 60 103 127 8 9 14 20 10 9 18 8 M1MC 077 77 000 19 3 4 115 1 60 103 127 8 9 14 20 10 9 18 8 M1MC 090 90 000 19...

Страница 17: ...y be used for gas supply systems Fuellineinstallationsotherthantypicalinstallations shown in Figure 26 page 18 Figure 27 page 19 must comply with the fuel piping provisions stated in the Federal Manuf...

Страница 18: ...e Pressure is reduced to 3 1 2 W C by the pressure regulator in the gas valve The maximum inlet pressure for the valve is 7 W C and the minimum inlet pressure is 4 5 W C For L P gas pressure to the ga...

Страница 19: ...A Two Line system should only be used if vertical lift exceeds 8 feet 1 Install the oil feed line as outlined in steps 1 6 below 2 Install the oil pump bypass plug in the bottom return port 3 Route th...

Страница 20: ...Direct Ignition Furnaces 1 Follow the instructions How to Shut Off Gas page 23 2 Disconnect the gas pipe union and the electrical wires connected to the gas valve 3 Remove the gas valve assembly a Re...

Страница 21: ...nace installation A flue gas sample may be taken from the heat exchanger which is located behind the hole of the top front of blower compartment 1 Turn off all electric power to the appliance 2 Remove...

Страница 22: ...i personne ne r pond appeler le service des incendies AVERTISSEMENT startup adjustments PLEASE READ ALL SAFETY INFORMATION BEFORE LIGHTING THE FURNACE WARNING Before placing the furnace in service it...

Страница 23: ...st setting 2 Turn off all electric power to the appliance before servicing unit 3 Set the furnace On Off Switch to OFF Honeywell Figure 30 Turn gas control knob clockwise to OFF Robertshaw Figure 31 P...

Страница 24: ...trol lever to ON 7 Turn electric power to the appliance ON 8 Set the thermostat to HEAT and or the desired temperature setting The furnace should light in approximately 45 seconds If the appliance wil...

Страница 25: ...ergized for a 30 second warm up period After warm up the gas valve opens NOTE The time for ignition is approximately 6 seconds after which the gas valve either remains open if flame is sensed or close...

Страница 26: ...to cut the electrical power to the furnace See Figure 33 Limit Control This furnace is protected by two high temperature safety limit switches The auxiliary upper limit switch and the high temperature...

Страница 27: ...RX1 scale Normalreadingshouldbe40 75ohms If above or below this rating at room temperature changeignitor 3 Check for continuity from ignitor receptacle to burner Control Module is Powered Ignitor won...

Страница 28: ...he igniter terminals and there is no ignition the igniter is likely defective and needs to be replaced 3 If the stops flashing burner turns on but the control locks out again check the cad cell If the...

Страница 29: ...ailed ignition Five flashes L1 neutral reversed or L1 voltage not present on L1 Flame Status A Yellow LED labeled Flame is provided to indicate flame status When flame is sensed the flame LED is lit I...

Страница 30: ...ceoperation Excessiveiceformationcould restrict the combustion air supply to the burner causing inefficient burner operation If excessive ice has formed on the air inlet or exhaust portions of the roo...

Страница 31: ...53 26 43 0 3 x x 1 4 3 M1BC 066 66 53 26 43 0 3 x x 1 2 4 M1BB 086 86 68 18 37 0 3 x x 1 4 3 M1BC 086 86 68 18 37 0 3 x x 1 2 4 M5SB 066 66 56 0 3 50 Gph x Burner Model AF 10 1 4 3 M5SC 066 66 56 0 3...

Страница 32: ...ut MBTUH 45 4 41 8 40 1 38 5 37 0 35 5 34 1 32 7 31 4 30 2 M1M 070 Orifice Size Nat Gas 24 25 26 27 27 28 28 29 29 30 Orifice Size LP 42 42 43 43 43 44 44 45 46 47 Output MBTUH 56 7 52 3 50 2 48 2 46...

Страница 33: ...44 220 439 84 43 214 429 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 1...

Страница 34: ...BLUE MED HI ORANGE MED LO WHITE RED LO BLACK HIGH BLUE MED HI WHITE 6 5 4 3 2 1 LEGENDS 115V FIELD 115V 24V FIELD 24V BLOWER MOTOR 4 SPEED NOTES 1 Incoming power must be polarized Observe color coding...

Страница 35: ...to Table 12 A C Blower Selection 5 If any of the original wire supplied with the appliance is replaced 105 C wire or equivalent 6 Use copper conductors only 7 Flash Codes Refer to Table 9 Control Modu...

Страница 36: ...lter s clean YES NO Flue connections tight YES NO Is there proper draft YES NO ATTENTION INSTALLERS Itisyourresponsibilitytoknowthisproductbetterthanyourcustomer This includes being able to install th...

Отзывы: