INSTALLATION INSTRUCTIONS

3-phase R-410A Split System Heat Pump

506 01 5102 00

9

ELECTRICAL WIRING

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in per‐
sonal injury or death.

Before installing, modifying or servicing system,
turn OFF the main (remote) electrical disconnect
device. There may be more than one disconnect
device.

Refer to unit rating plate for the required supply voltage.
Depending on the model, required supply voltage will be:

208/230 V, 3-phase, 60 Hz.

or

460 V, 3-phase, 60 Hz.

Outdoor units are approved for use with copper
conductors only. Do not use aluminum wire.

Refer to unit rating plate for minimum circuit ampacity and
circuit protection requirements.

Grounding

Permanently ground unit in accordance with the National
Electrical Code and local codes or ordinances. Use a
copper conductor of the correct size from the grounding
lug in control box to a grounded connection in the service
panel or a properly driven and electrically grounded
ground rod.

Supply Voltage Wiring Connections

Make all outdoor electrical supply (Line Voltage)
connections with raintight conduit and fittings. Most
codes require a disconnect switch outdoors within sight of
the unit. Consult local codes for special requirements.

Route electrical supply (Line Voltage) wiring through
knockout hole in bottom of Control Box.

Connect two power wires to Contactor and one power
wire to Blue lead wire (use wire nut). Connect ground wire
to Ground Lug. Refer to Wiring Diagram on unit and
Figure 9.

Figure 9

208/230 V and 460 V

Electrical Supply

(Line Voltage) Connections

DISCONNECT

PER NEC AND/OR

LOCAL CODES

CONTACTOR

GROUND

LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

11

13

L1

L3

L2

BLUE LEAD WIRE

Phase Monitor Relay Board

The Phase Monitor Board detects the sequence of the
three phase electrical system, and a relay breaks the Y
(call for cooling) control signal if the phasing is incorrect.
Additionally, the board will detect the loss of voltage on
any of the three phase inputs and break the Y signal in the
same way.

An LED on the board displays the following status:
Red LED ON -

Normal function, relay contact
closed.

Red LED Blinking - Abnormal function, relay contact

open.

Red LED OFF -

No 24 VAC control power present at
board.

NOTE:

 Units with Comfort Alert

t

 Diagnostics device

have phase monitor feature built in.

Figure 10

Phase Monitor Relay Board

Thermostat Wiring Connections

Route thermostat wiring through rubber grommet in
bottom of Control Box. Low voltage lead wires are
provided in the control box for connection to thermostat
wires (use wire nuts). Refer to Wiring Diagram on unit and
Figure 11 for low voltage wiring examples.

NOTE:

 Use No. 18 AWG (American Wire Gage)

color-coded, insulated (35 

°

C minimum) wire. If

thermostat is located more than 100 feet (30.5 m) from
unit as measured along the control voltage wires, use No.
16 AWG color-coded wires to avoid excessive voltage
drop.

Содержание H4H3 Series

Страница 1: ...rd CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels WARNING Safety Lab...

Страница 2: ...oom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the unit Locate unit away fro...

Страница 3: ...lit System Heat Pump 506 01 5102 00 3 Figure 1 Clearances various examples Wall 6 24 Service Wall Wall Wall 6 6 Post Wall Wall 18 18 18 18 6 6 6 18 18 18 18 24 Service 24 Service 24 Service 24 Service...

Страница 4: ...on is not recommended on wood frame structures where low noise levels are required Supporting structure or platform for the unit must be level If installation is on a flat roof locate unit minimum 6 i...

Страница 5: ...refer to the Long Line Application Guideline document for additional instructions NOTE Line set actual length must not exceed 200 feet NOTE A crankcase heater must be used when the refrigerant line le...

Страница 6: ...d periods of unit shut down caus ing refrigerant slugging and possible compressor damage at start up If ANY section of the line set is buried under ground provide a minimum 6 vertical rise at the serv...

Страница 7: ...e set tube ends with emery cloth or steel brush Remove any grit or debris Insert line set tube ends into service valve tube stubs Apply heat absorbing paste or heat sink product between service valve...

Страница 8: ...TEM IF IT HOLDS DEEP VACUUM EVACUATE BREAK VACUUM WITH DRY NITROGEN WAIT EVACUATE CHARGE SYSTEM BREAK VACUUM WITH DRY NITROGEN EVACUATE WAIT I OPENING SERVICE VALVES Outdoor units are shipped with a r...

Страница 9: ...two power wires to Contactor and one power wire to Blue lead wire use wire nut Connect ground wire to Ground Lug Refer to Wiring Diagram on unit and Figure 9 Figure 9 208 230 V and 460 V Electrical Su...

Страница 10: ...INSTALLING OUTDOOR THERMOSTATS SYSTEMS WITH ONE OUTDOOR THERMOSTAT G R W3 C O R G R W 3 C E C W 2 Y W 2 O R C W 2 Y W 2 C L G Y E O R SYSTEMS WITHOUT OUTDOOR THERMOSTATS C G R W 2 C Y O R W 2 SUBBASE...

Страница 11: ...tdoor fan motor lead from OF2 on control board refer to Figure 13 Tape lead to prevent grounding 3 Restart unit in heating mode allowing frost to accumulate on outdoor coil 4 After a few minutes in he...

Страница 12: ...indoor temperature is between 70_ and 80_F S line set is less that 80 feet 1 Operate unit a minimum of 15 minutes before checking charge NOTE If outdoor unit has a 2 speed fan motor motor will operat...

Страница 13: ...s indoor unit blower relay starting indoor blower motor When thermostat is satisfied its contacts open de energizing contactor and blower relay Compressor and motors stop NOTE If indoor unit is equipp...

Страница 14: ...Stage Compressor Signal First Stage Compressor Signal 24 VAC for Thermostat Indicator 24 Volt Power 24 Volt Common 24 Volt Compressor Protection Function DC Compressor Solenoid ALERT LED TRIP LED DC...

Страница 15: ...restriction 2 If high pressure switch present go to Flash Code 2 information 3 Intermittent thermostat demand signal 4 System or control board defective Yellow ALERT Flash Code 4 Locked Rotor LOCKOUT...

Страница 16: ...nd signal is present If not R and C are reversed wired Verify voltage at contactor coil falls below 0 5VAC when off Review R 410A QUICK REFERENCE GUIDE R 410A refrigerant operates at 50 70 higher pres...