background image

INSTALLATION INSTRUCTIONS

3-phase R-410A Split System Heat Pump

506 01 5102 00

5

REFRIGERATION SYSTEM

A. COMPONENT MATCHES

Check to see that the proper system components are in
place, especially the indoor coil.

R-410A outdoor units can only be used with R-410A
specific indoor coils. If there is a refrigerant mis-match,
consult the indoor coil manufacturer to determine if a
refrigerant conversion kit is available for the indoor coil.

This outdoor unit is designed for use only with indoor coils
that utilize a TXV refrigerant metering device. If any other
type of metering device is installed on the indoor coil,
consult the indoor coil manufacturer to determine if a TXV
conversion kit is available.

When installing a TXV on an indoor coil, follow the
instructions provided with the new TXV.

A typical TXV installation is shown in Figure 3.

!

CAUTION

PRODUCT DAMAGE HAZARD

Failure to follow this caution may result in product
damage.

Indoor coil and outdoor unit must be listed as a
certified combination (match) in the ARI Unitary
Directory of Certified Products.
Indoor coil must have R-410A specific, TXV refrig‐
erant metering device.

Figure 3

Typical TXV Installation

TXV

SENSING
BULB

EQUALIZER
TUBE

ÉÉ

ÉÉ

ÉÉ

ÉÉ

8  O'CLOCK

4  O'CLOCK

STRAP

SENSING BULB
(EITHER SIDE)

SUCTION

TUBE

INDOOR

COIL

SUCTION
TUBE

LIQUID
TUBE

B. REFRIGERANT LINE SETS

The refrigerant line set must be properly sized to assure
maximum efficiency and proper oil circulation.

Refer to Product Specifications and Long Line
Applications Guideline for line set sizing

.

NOTE:

 If the line set actual length is to exceed 80 feet, or

if there is more than 20 feet vertical separation between
outdoor and indoor units, refer to the Long Line
Application Guideline document for additional
instructions.

NOTE:

 Line set actual length must not exceed 200 feet.

NOTE:

 A crankcase heater must be used when the

refrigerant line length exceeds 80 feet.

If it is necessary to add refrigerant line in the field, use
dehydrated or dry, sealed, deoxidized, copper
refrigeration tubing. Do not use copper water pipe.

Do not remove rubber plugs or caps from copper tubing
until connections are ready to be made.

Be extra careful when bending refrigeration tubing.
Tubing can “kink” easily, and if this occurs, the entire
length of tubing must be replaced.

!

WARNING

PERSONAL INJURY HAZARD

Failure to follow this warning could result in per‐
sonal injury and/or death.

Relieve pressure and recover all refrigerant before
servicing existing equipment, and before final unit
disposal. Use all service ports and open all flow-
control devices, including solenoid valves.

!

CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in improp‐
er product operation.

Do not leave system open to atmosphere any lon‐
ger than absolutely required for installation. Inter‐
nal system components - especially refrigerant
oils - are extremely susceptible to moisture con‐
tamination. Keep ends of tubing sealed during
installation until the last possible moment.

C. ROUTING AND SUSPENDING REFRIGERANT

LINES

Run refrigerant lines as straight and direct as possible,
avoiding unnecessary bends and turns. Always insulate
the entire suction line. Both lines should be insulated
when routed through an attic or when routed through an
underground raceway.

When routing refrigerant lines through a foundation or
wall, do not allow refrigerant lines to come in direct
contact with the building structure.  Make openings large
enough so that lines can be wrapped with extra insulation.
Fill all gaps with RTV caulk. This will prevent noise

Содержание H4H3 Series

Страница 1: ...rd CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels WARNING Safety Lab...

Страница 2: ...oom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the unit Locate unit away fro...

Страница 3: ...lit System Heat Pump 506 01 5102 00 3 Figure 1 Clearances various examples Wall 6 24 Service Wall Wall Wall 6 6 Post Wall Wall 18 18 18 18 6 6 6 18 18 18 18 24 Service 24 Service 24 Service 24 Service...

Страница 4: ...on is not recommended on wood frame structures where low noise levels are required Supporting structure or platform for the unit must be level If installation is on a flat roof locate unit minimum 6 i...

Страница 5: ...refer to the Long Line Application Guideline document for additional instructions NOTE Line set actual length must not exceed 200 feet NOTE A crankcase heater must be used when the refrigerant line le...

Страница 6: ...d periods of unit shut down caus ing refrigerant slugging and possible compressor damage at start up If ANY section of the line set is buried under ground provide a minimum 6 vertical rise at the serv...

Страница 7: ...e set tube ends with emery cloth or steel brush Remove any grit or debris Insert line set tube ends into service valve tube stubs Apply heat absorbing paste or heat sink product between service valve...

Страница 8: ...TEM IF IT HOLDS DEEP VACUUM EVACUATE BREAK VACUUM WITH DRY NITROGEN WAIT EVACUATE CHARGE SYSTEM BREAK VACUUM WITH DRY NITROGEN EVACUATE WAIT I OPENING SERVICE VALVES Outdoor units are shipped with a r...

Страница 9: ...two power wires to Contactor and one power wire to Blue lead wire use wire nut Connect ground wire to Ground Lug Refer to Wiring Diagram on unit and Figure 9 Figure 9 208 230 V and 460 V Electrical Su...

Страница 10: ...INSTALLING OUTDOOR THERMOSTATS SYSTEMS WITH ONE OUTDOOR THERMOSTAT G R W3 C O R G R W 3 C E C W 2 Y W 2 O R C W 2 Y W 2 C L G Y E O R SYSTEMS WITHOUT OUTDOOR THERMOSTATS C G R W 2 C Y O R W 2 SUBBASE...

Страница 11: ...tdoor fan motor lead from OF2 on control board refer to Figure 13 Tape lead to prevent grounding 3 Restart unit in heating mode allowing frost to accumulate on outdoor coil 4 After a few minutes in he...

Страница 12: ...indoor temperature is between 70_ and 80_F S line set is less that 80 feet 1 Operate unit a minimum of 15 minutes before checking charge NOTE If outdoor unit has a 2 speed fan motor motor will operat...

Страница 13: ...s indoor unit blower relay starting indoor blower motor When thermostat is satisfied its contacts open de energizing contactor and blower relay Compressor and motors stop NOTE If indoor unit is equipp...

Страница 14: ...Stage Compressor Signal First Stage Compressor Signal 24 VAC for Thermostat Indicator 24 Volt Power 24 Volt Common 24 Volt Compressor Protection Function DC Compressor Solenoid ALERT LED TRIP LED DC...

Страница 15: ...restriction 2 If high pressure switch present go to Flash Code 2 information 3 Intermittent thermostat demand signal 4 System or control board defective Yellow ALERT Flash Code 4 Locked Rotor LOCKOUT...

Страница 16: ...nd signal is present If not R and C are reversed wired Verify voltage at contactor coil falls below 0 5VAC when off Review R 410A QUICK REFERENCE GUIDE R 410A refrigerant operates at 50 70 higher pres...

Отзывы: