background image

INSTALLATION INSTRUCTIONS

3-phase R-410A Split System Heat Pump

506 01 5102 00

13

Figure 14

R-410A Required Liquid Line Temperature (

°

F) - Cooling Mode

Measured Liquid

Pressure (psig)

Rating Plate (required)

Subcooling Temperature (

°

F)

Measured Liquid

Pressure (psig)

Rating Plate (required)

Subcooling Temperature (

°

F)

6

8

10

12

14

16

6

8

10

12

14

16

251

78

76

74

72

70

68

364

104

102

100

98

96

94

259

80

78

76

74

72

70

374

106

104

102

100

98

96

266

82

80

78

76

74

72

384

108

106

104

102

100

98

274

84

82

80

78

76

74

395

110

108

106

104

102

100

283

86

84

82

80

78

76

406

112

110

108

106

104

102

291

88

86

84

82

80

78

416

114

112

110

108

106

104

299

90

88

86

84

82

80

427

116

114

112

110

108

106

308

92

90

88

86

84

82

439

118

116

114

112

110

108

317

94

92

90

88

86

84

450

120

118

116

114

112

110

326

96

94

92

90

88

86

462

122

120

118

116

114

112

335

98

96

94

92

90

88

474

124

122

120

118

116

114

345

100

98

96

94

92

90

SEQUENCE OF OPERATION

A. COOLING MODE

On a call for cooling, the thermostat makes circuits R-O,
R-Y, and R-G. Circuit R-O energizes reversing valve,
switching it to cooling position. Circuit R-Y energizes
contactor, starting outdoor fan motor and compressor.
Circuit R-G energizes indoor unit blower relay, starting
indoor blower motor.

When thermostat is satisfied, its contacts open,
de-energizing contactor and blower relay. Compressor
and motors stop.

NOTE:

 If indoor unit is equipped with a time-delay relay

circuit, the blower runs an additional length of time to
increase system efficiency. (Applies to both cooling and
heating modes.)

NOTE:

 Low ambient cooling feature allows unit to

operate safely in cooling mode down to 0

_

 F outdoor

ambient.

B. HEATING MODE

On a call for heating, the thermostat makes circuits R-Y
and R-G (circuit R-O is NOT made, and the reversing
valve stays in the de-energized, heating position). Circuit
R-Y energizes contactor, starting outdoor fan motor and
compressor. Circuit R-G energizes indoor blower relay,
starting blower motor. If the room temperature continues
to fall, circuit R-W2 is made through the second-stage
room thermostat bulb. Circuit R-W2 energizes a
sequencer, bringing on the first bank supplemental
electric heat and providing electrical potential to the
second heater sequencer (if used). If outdoor
temperature falls below the setting of the outdoor
thermostat (field-installed option), contacts close to
complete the circuit and bring on the second bank of
supplemental electric heat.

When the thermostat is satisfied, its contacts open,
de-energizing contactor, blower relay, and sequencer.
Compressor, motors, and heaters stop.

Содержание H4H3 Series

Страница 1: ...rd CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels WARNING Safety Lab...

Страница 2: ...oom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the unit Locate unit away fro...

Страница 3: ...lit System Heat Pump 506 01 5102 00 3 Figure 1 Clearances various examples Wall 6 24 Service Wall Wall Wall 6 6 Post Wall Wall 18 18 18 18 6 6 6 18 18 18 18 24 Service 24 Service 24 Service 24 Service...

Страница 4: ...on is not recommended on wood frame structures where low noise levels are required Supporting structure or platform for the unit must be level If installation is on a flat roof locate unit minimum 6 i...

Страница 5: ...refer to the Long Line Application Guideline document for additional instructions NOTE Line set actual length must not exceed 200 feet NOTE A crankcase heater must be used when the refrigerant line le...

Страница 6: ...d periods of unit shut down caus ing refrigerant slugging and possible compressor damage at start up If ANY section of the line set is buried under ground provide a minimum 6 vertical rise at the serv...

Страница 7: ...e set tube ends with emery cloth or steel brush Remove any grit or debris Insert line set tube ends into service valve tube stubs Apply heat absorbing paste or heat sink product between service valve...

Страница 8: ...TEM IF IT HOLDS DEEP VACUUM EVACUATE BREAK VACUUM WITH DRY NITROGEN WAIT EVACUATE CHARGE SYSTEM BREAK VACUUM WITH DRY NITROGEN EVACUATE WAIT I OPENING SERVICE VALVES Outdoor units are shipped with a r...

Страница 9: ...two power wires to Contactor and one power wire to Blue lead wire use wire nut Connect ground wire to Ground Lug Refer to Wiring Diagram on unit and Figure 9 Figure 9 208 230 V and 460 V Electrical Su...

Страница 10: ...INSTALLING OUTDOOR THERMOSTATS SYSTEMS WITH ONE OUTDOOR THERMOSTAT G R W3 C O R G R W 3 C E C W 2 Y W 2 O R C W 2 Y W 2 C L G Y E O R SYSTEMS WITHOUT OUTDOOR THERMOSTATS C G R W 2 C Y O R W 2 SUBBASE...

Страница 11: ...tdoor fan motor lead from OF2 on control board refer to Figure 13 Tape lead to prevent grounding 3 Restart unit in heating mode allowing frost to accumulate on outdoor coil 4 After a few minutes in he...

Страница 12: ...indoor temperature is between 70_ and 80_F S line set is less that 80 feet 1 Operate unit a minimum of 15 minutes before checking charge NOTE If outdoor unit has a 2 speed fan motor motor will operat...

Страница 13: ...s indoor unit blower relay starting indoor blower motor When thermostat is satisfied its contacts open de energizing contactor and blower relay Compressor and motors stop NOTE If indoor unit is equipp...

Страница 14: ...Stage Compressor Signal First Stage Compressor Signal 24 VAC for Thermostat Indicator 24 Volt Power 24 Volt Common 24 Volt Compressor Protection Function DC Compressor Solenoid ALERT LED TRIP LED DC...

Страница 15: ...restriction 2 If high pressure switch present go to Flash Code 2 information 3 Intermittent thermostat demand signal 4 System or control board defective Yellow ALERT Flash Code 4 Locked Rotor LOCKOUT...

Страница 16: ...nd signal is present If not R and C are reversed wired Verify voltage at contactor coil falls below 0 5VAC when off Review R 410A QUICK REFERENCE GUIDE R 410A refrigerant operates at 50 70 higher pres...

Отзывы: