P/N 146626999-

1 (ML) • REV D • ISS 06MAY19 

8.  Close the cover. 
9.  Insert the screw and place the custom insert. 

For EN 50131 Grade 3 installations, do not use mounting 
position B. 

Jumper settings 

See Figure 5 for the jumper locations in the detector. 

J1: Not used 

J3 and J4: Dual loop setting 

This sets the alarm and tamper relays. It allows you to connect 
the detector to any control panel. Use jumpers 3 and 4. See 
Figure 7. 

Use Remote Test (RT) to test the detector from the control 
panel. The detector will activate the Alarm relay if the test 
result is positive, and the AM relay if the test result is negative. 

J6: Polarity setting of the control voltage (CV) 

On (factory default):  

• 

The detector is in Day mode (system disarmed) when the 
D/N input is connected to GND (terminal 1) 

• 

The detector is in Night mode (system armed) when the 
D/N input is connected to +12 V (terminal 2) 

• 

The detector is in Walk Test Off mode (LEDs are disabled) 
when the WT input is connected to GND (terminal 1) 

• 

The detector is on Walk Test On mode (LEDs are 
enabled) when the WT input is connected to +12 V 
(terminal 2) 

Off:  

• 

The detector is in Day mode (system disarmed) when the 
D/N input is connected to +12 V (screw terminal 2).  

• 

The detector is in Night mode (system armed) when the 
D/N input is connected to GND (terminal 1).  

• 

The detector is in Walk Test Off mode (LEDs are disabled) 
when the WT input is connected to +12 V (terminal 2). 

• 

The detector is on Walk Test On mode (LEDs are 
enabled) when the WT input is connected to GND 
(terminal 1). 

D/N and WT functionality 

The D/N input: 

• 

Controls the LED functionality together with the WT input. 

• 

Resets the alarm memory 

• 

Controls the AM relay functionality during the NIGHT 
mode together with SW1. 

The WT input controls the LED functionality together with the 
D/N input. 

When the detector is in the Day mode and Walk Test On 
mode, the LEDs of the detector can be activated. See “LED 
indication

” on page 5 for more information. 

During the Night mode the LEDs are always switched off. 

If a PIR intruder alarm if detected in the Night mode and the 
detector switches back to Day mode, the red LED starts 
flashing to indicate an alarm in memory. 

The alarm memory is reset by switching the detector to Night 
mode. 

DIP switch settings 

Factory default: 

 

SW 1: When to signal AM (anti-masking) or TF (technical 
fault) output 

On: Signals AM or TF only when the system is in Day mode 
(factory default). 
Off: Always signals AM or TF during Day and Night mode. 

SW 2: AM sensitivity 

On: Advanced AM sensitivity. The detector signals the AM 
area masking (factory default). 

Off: Standard AM sensitivity. The detector signals the AM area 
approaching. 

SW 3: Resetting the AM/TF output 

On: Auto reset. Resets the AM or TF status 40 seconds after a 
PIR alarm. 

Off: Authorized reset. Resets the AM or TF status after a PIR 
alarm when the system is in Day and Walk Test mode. The 
yellow LED will blink quickly. When the system is in Night 
status, the yellow LED will turn off and the system is reset 
(factory default). 

Notes 

• 

For the advanced setting (SW 2 is On) the source of AM 
alarm needs to be removed before AM reset is allowed. 

• 

If the AM alarm cannot be reset with an auto reset or 
authorized reset, disconnect the power supply and 
reconnect again.  

• 

A walk test should be performed to ensure the device 
settings are appropriate for its application.  

SW 4: Signalling AM or TF output 

On: Signals AM on both the AM and Alarm relays. Signals TF 
on the AM relay only (EN 50131). 
Off: Signals AM and TF on the AM relay (factory default). 

SW 5: Setting LEDs 

On: Enables both LEDs on the detector at all times (factory 
default). 
Off: Puts both LEDs under the control of the Walk Test and 
Day/Night input. This activates the memory feature of the 
detector. 

AM calibration 

During start-up the AM circuitry calibrates itself to its 
environment. It is important to make sure that there are no 
changes made to the environment within 1 m distance of the 
detector within 60 s after powering up, otherwise the detector 
may be vulnerable to false AM alarms and these alarms may 
be impossible to reset. 

ON

5

4

3

2

1

Содержание VE1120-D Series

Страница 1: ...stallation Sheet EN DE 1 2 3 4 1 2 3 20 0 m 65 ft 7 in optimum 2 4 m 7 ft 10 in 0 m 2 m 6 ft 6 in 4 m 13 ft 1 in 6 m 19 ft 8 in 8 m 26 ft 2 in 10 m 32 ft 9 in 12 m 39 ft 4 in 20 m range 65 ft 7 in 4 m 2 m 6 ft 6 in 4 m 13 ft 1 in 6 m 19 ft 8 in 8 m 26 ft 2 in 10 m 32 ft 9 in 12 m 39 ft 4 in 1 2 m 3 ft 11 in 4 m 13 ft 1 in ...

Страница 2: ...2 8 P N 146626999 1 ML REV D ISS 06MAY19 5 VE1120 D VE1120AM D J1 Not used J3 and J4 See Figure 7 J6 CV polarity CV polarity 6 J1 J6 J3 J4 J1 J3 J4 J6 ...

Страница 3: ...se screws in positions B or C Figure 3 To install a pry off tamper use position A or C 4 Wire the detector see Figures 3 and 7 5 Select the desired jumper and DIP switch settings see Figure 5 See Jumper settings on page 4 for more information 6 Remove the blinders and add the stickers if required see Figure 6 for an example 7 For ceiling mount applications that require a 90 coverage use the SB01 s...

Страница 4: ...During the Night mode the LEDs are always switched off If a PIR intruder alarm if detected in the Night mode and the detector switches back to Day mode the red LED starts flashing to indicate an alarm in memory The alarm memory is reset by switching the detector to Night mode DIP switch settings Factory default SW 1 When to signal AM anti masking or TF technical fault output On Signals AM or TF on...

Страница 5: ...C 32 to 120 F VE1120 D VE1120AM D Dimensions H x W x D 125 55 60 mm 4 92 x 2 16 x 2 36 in 125 65 60 mm 4 92 x 2 6 x 2 36 in Relative humidity 95 max noncondensing Weight 150 g IP IK rating IP30 IK02 Regulatory information Manufacturer PLACED ON THE MARKET BY UTC Fire Security Americas Corporation Inc 3211 Progress Drive Lincolnton NC 28092 USA AUTHORIZED EU REPRESENTATIVE UTC Fire Security B V Kel...

Страница 6: ...allationen gemäß EN 50131 Sicherheitsstufe 3 nicht Montageposition B Steckbrücken Einstellungen Siehe Abb 5 für die Anordnung der Steckbrücken im Melder J1 Nicht verwendet J3 und J4 Einstellung für Dual Meldegruppe Dient zur Einstellung des Alarm und Sabotagerelais Sie können damit den Melder an eine beliebige Einbruchmeldezentrale anschließen Verwenden Sie die Steckbrücken 3 und 4 Siehe Abb 7 Ver...

Страница 7: ... Technischer Fehler nur auf dem AM Relais EN 50131 Aus Signalisiert AM und TF auf dem AM Relais Werkseinstellung SW 5 Einstellen der LEDs Ein Aktiviert beide LEDs am Melder dauerhaft Werkseinstellung Aus Beide LEDs werden durch den Eingang für Gehtest WT und Tag Nacht D N gesteuert Dies aktiviert die Speicherfunktion des Melders AM Kalibierung Während des Startvorgangs kalibriert sich der AM Schal...

Страница 8: ...RISIERTE HÄNDLER ODER AUTORISIERTE WIEDERVERKÄUFER ÜBER DIE ERFORDERLICHE QUALIFIKATION UND ERFAHRUNG VERFÜGEN UM BRANDSCHUTZ ODER SICHERHEITSTECHNISCHE PRODUKTE ORDNUNGSGEMÄSS ZU INSTALLIEREN Weitere Informationen zu Haftungsausschlüssen sowie zur Produktsicherheit finden Sie unter https firesecurityproducts com policy product warning oder scannen Sie den QR Code Zertifizierung EU Richtlinien UTC...

Отзывы: