P/N 146576999-
1 (ML) • REV D • ISS 08MAR19
5 / 10
LED indication
PIR
Red LED
Alarm relay
To reset
Start up
Closed
Automatically after 25 s
Low voltage
Open (Alarm)
Apply correct voltage
PIR intruder
alarm
Open (Alarm)
Automatically after 3 s
PIR/AM
Red
LED
Yellow
LED
Alarm
relay
AM
relay
To reset
Start up
Closed Closed Automatically
after 60 s
Low voltage
Open
(Alarm)
Open
(Alarm)
Apply correct
voltage
PIR intruder
alarm
Open
(Alarm)
Automatically
after 3 s
Latched PIR
(Memory)
Switch to Night
mode
AM alarm
Open*
(Alarm)
Open
(Alarm)
See DIP
switch 3
After AM reset
Switch to
Night mode
Technical fault
Open
(Alarm)
Do a successful
walk test
Continuously on
Normal blinking (1 Hz)
Fast blinking (4 Hz)
* Depends on the setting of the DIP switch SW4.
Specifications
EV1116-D
EV1116AM-D
Detector
PIR
PIR + AM
Signal processing
DSP
Range
16 m
Optical
11 high-density mirror curtains
Memory
Yes
Input power
9 to 15 VDC (12 V nominal)
Peak-to-peak ripple
2 V (at 12 VDC)
Detector start-up time
25 s
60 s
Normal current
4.4 mA
10 mA
Current in Alarm
1.2 mA
3.8 mA
Maximum current
(LED on)
11 mA
24 mA
Mounting height
1.8 m to 3.0 m
Target speed range
20 cm/s to 3 m/s
10 cm/s to 4 m/s
Alarm (NC) / Tamper relay
characteristic
80 mA
30 VDC, resistive
80 mA
30 VDC
Pry-off tamper
Optional
On-board (Yes)
AM relay characteristic
—
80 mA at 30 VDC
max.
PIR alarm time
3 s
Operating temperature
−10 to +55°C
Dimensions (H x W x D)
125 × 55 × 60 mm
125 × 65 × 60 mm
Relative humidity
95% max.
Weight
150 g
IP/IK rating
IP30 IK02
Regulatory information
Manufacturer
PLACED ON THE MARKET BY:
UTC Fire & Security Americas Corporation, Inc.
3211 Progress Drive, Lincolnton, NC, 28092, USA
AUTHORIZED EU REPRESENTATIVE:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
Product warnings
and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE
TO AND INSTALLATION BY QUALIFIED
PROFESSIONALS. UTC FIRE & SECURITY
CANNOT PROVIDE ANY ASSURANCE THAT
ANY PERSON OR ENTITY BUYING ITS
PRODUCTS,
INCLUDING ANY “AUTHORIZED
DEALER” OR “AUTHORIZED RESELLER”, IS
PROPERLY TRAINED OR EXPERIENCED TO
CORRECTLY INSTALL FIRE AND SECURITY
RELATED PRODUCTS.
For more information on warranty disclaimers and
product safety information, please check
https://firesecurityproducts.com/policy/product-
warning/
Certification
European Union
directives
UTC Fire & Security hereby declares that this
device is in compliance with the applicable
requirements and provisions of the Directive
2014/30/EU and/or 2014/35/EU. For more
information see www.utcfireandsecurity.com or
www.interlogix.com.
2012/19/EU (WEEE directive): Products marked
with this symbol cannot be disposed of as
unsorted municipal waste in the European Union.
For proper recycling, return this product to your
local supplier upon the purchase of equivalent
new equipment, or dispose of it at designated
collection points. For more information see:
www.utcfssecurityproducts.eu/recycle/
Contact information
www.utcfireandsecurity.com or www.interlogix.com
For customer support, see www.interlogix.com/customer-
support.
DE: Installationsdatenblatt
Einführung
Die EV1100-D-Serie umfasst die Bewegungsmelder EV1116-D
und EV1116AM-D PIR.
Die Melder verfügen über einen
patentierten Spiegel sowie Pyro- und
Signalverarbeitungstechnologie.
Installationsanleitung
Die Technologie in diesen Meldern dient zur Vermeidung
falscher Alarmmeldungen. Dennoch sollten Sie potenzielle
Instabilitätsfaktoren vermeiden (siehe Abb. 1), darunter:
•
Direkte Sonneneinstrahlung auf den Melder
•
Starke Zugluft am Melder
•
Hitzequellen innerhalb des Erfassungsbereichs des
Melders
•
Tiere innerhalb des Erfassungsbereichs des Melders