Page 13
Intepro Systems
www.inteproate.com
PS 9000 3U Series
5 kW / 6.6 kW / 10 kW
Model 400 V
PS 9750-20
PS 9040-340 PS 9040-510 PS 9080-340 PS 9200-140
Analog interface
(1
Set value inputs
U, I, P
Actual value outputs
U, I
Control signals
DC on/off, remote control on/off
Status signals
CV, OVP, OT, OCP, OPP, PF, DC on/off
Galvanic isolation to the device
Max. 725 V DC
Sample rate of inputs
500 Hz
Insulation
Allowed float (potential shift) on the DC output:
Negative terminal to PE
Max. ±725 V DC
±400 V DC
±400 V DC
±400 V DC
±400 V DC
Positive terminal to PE
Max. ±1000 V DC
±400 V DC
±400 V DC
±400 V DC
±600 V DC
Miscellaneous
Cooling
Temperature controlled fans, front inlet, rear exhaust
Ambient temperature
0..50°C (32...122°F)
Storage temperature
-20...70°C (-4...158°F)
Humidity
< 80%, not condensing
Standards
EN 61010-1:2010
EMC TÜV approved acc. IEC 61000-6-2:2005 and IEC 61000-6-3:2006 Class B
Overvoltage category
2
Protection class
1
Pollution degree
2
Operational altitude
<2000 m (1,242 mi)
Digital interfaces
Featured
1x USB-B, 1x Ethernet
(2
, 1x GPIB (optional with option 3W)
Galvanic isolation from device
Max. 725 V DC
Connectors
Rear side
Share Bus, DC output, AC input, remote sensing, analog interface, USB-B, Ethernet
Dimensions
Enclosure (WxHxD)
19“ x 3 U x 609 mm (24”)
Total (WxHxD)
483 x 133 x 714 mm (19” x 5,2” x 28,1”)
Weight
≈
17 kg (37.5 lb)
≈
24 kg (52.9 lb)
≈
30 kg (66.1 lb)
≈
24 kg (52.9 lb)
≈
24 kg (52.9 lb)
Article number
(3
06230255
06230256
06230263
06230257
06230258
(1 For technical specifications of the analog interface see
„3.5.4.4 Analog interface specification“ on page 58
(2 Only in the standard version
(3 Article number of the standard EU version, devices with options will have a different number