Owner’s & Installation manual
10. WIRING
CAUTION
The air conditioner should use separate power supply with rated voltage.
The external power supply to the air conditioner should have ground wiring, which is linked to the ground wiring of the indoor
and outdoor unit.
The wiring work should be done by qualified persons according to circuit drawing.
an all-pole disconnection device which has at least 3mm separation distance in all pole and a residual current device(RCD)with
the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule.
The appliance shall be installed in accordance with national wiring regulations.
Be sure to locate the power wiring and the signal wring well to avoid cross-disturbance.
Do not turn on the power until you have checked carefully after wiring.
AIR FLOW(CFM)
POWER
CIRCUIT BREAKER/FUSE(A)
INDOOR UNIT POWER
WIRING(mm
2
)
BELOW 20M
BELOW 50M
PHASE
FREQUENCY AND VOLT
1200
1-phase
220-240V~ 60Hz
15/15
Twisted pairwire
˖
2.5
Twisted pairwire
˖
6
2.5
Table 10-1
GROUND WIRING(mm
2
)
The power cord type designation is H05RN-F or above.