5.    ELECTRICAL WIRING

Please select power source for indoor unit and outdoor 

unit respectively 
The power supply has specified branch circuit with leakage 

protector and manual switch.  

The outdoor unit model which corresponding to different outdoor

 unit power supply should refer to the nameplate

.(Please set all the 

Please put the connective wire system between indoor unit

and outdoor unit with the refrigerant system together.
Use 3-core shielded wire as indoor unit and outdoor unit signal 

wire. 
The installation should comply with local electric standard. 
Power wiring should be engaged by specialized electrician.

CAUTION

5.1   Outdoor Unit Wiring

10

The Specification of Power

CAUTION

Fig. 5-1

indoor unit power of one system into the same branch circuit.)

Table 5-1

48

50/60

220-240

198
264

40

33A

40

Soft star

15.5
0.17
1.52

36

50/60

220-240

198
264

28.75

24A

32

Soft star

9.45
0.17
1.52

28

50/60

220-240

198
264

21.25

18.1A

25

Soft start

9.45
0.08

1.0

56

50/60

220-240

198
264

40

33A

40

Soft star

15.5
0.17
1.52

42

50/60

220-240

198
264

35

29A

32

Soft star

15.5
0.17
1.52

Model

Capicity(

kBtu/h

)

Hz

Voltage

Min.(V)

Max.(V)

MCA

TOCA

MFA

MSC

RLA

kW

FLA

220-240V~ 1Ph 50/60Hz

Power 

Supply

Compressor

OFM

Power Source

PQE

PQE

PQE

L N

P Q E X Y E

Outdoor power supply

Indoors

Power supply

ODU

IDU

IDU

IDU

IDU

Please use the shielded wire, and the shield layer must be grounded.

On/Off switch

On/Off switch

Fuse

Fuse

Distribution box

Distribution box

Distribution box

Distribution box

Fuse

Fuse

Fuse

L N

L N

L N

PQE

L N

ODU electrical control system connection diagram

L N

XYE

Power supply of centralized controller

Centralized controller 

(optional)

A disconnection device having an air gap contact separation 

in all active conductors should be incorporated in the fixed 

wiring according to the National Wiring Regulation.

The reserved  function is indicated in broken line table, users 

can select  it  when necessary.

CAUTION

Indoor/Outdoor Unit Signal Wire

Connect the wire according to their numbers.
Wrong connection may cause malfunction .

Wiring Connection

Seal the wiring connection with the insulation material , or the 

condensing dew will be caused.

The air-conditioners can connect with Central Control Monitor 

(CCM). Before operation, please wiring correctly and set system 

address and network address of indoor units 

NOTE

Wiring Terminal Description

Fig. 5-2

 L      N

ODU power supply 

220V~240V 50/60Hz

Содержание BlackSeries DIVERSE MDV-V28W/DHN1(At)

Страница 1: ...DHN1 At MDVC V42W DHN1 At MDVC V48W DHN1 At MDVC V56W DHN1 At MDV V28W DHN1 At MDV V36W DHN1 At MDV V42W DHN1 At MDV V48W DHN1 At MDV V56W DHN1 At DIVERSE Thank you very much for purchasing our air c...

Страница 2: ...ce RCD with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule The power cord type designation is H05RN R H07RN F or above Ask an authorized dealer or qu...

Страница 3: ...mp Do not use refrigerant charged in the outdoor unit for air purge The refrigerant for air purge is not contained in the outdoor unit Electrical cabling Be sure to fix the power cables and indoor out...

Страница 4: ...ficient ventilation place Near a private power station or high Frequency equipment The insulation of the metal parts of the building and the air conditioner should comply with the regulation of Nation...

Страница 5: ...units refer to Fig 3 7 Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind refer to Fig 3 7 Since the gravity center of the unit is not a...

Страница 6: ...hile connect to the connecting pipes outside and then piping and wiring through this Pay attention to the piping the fat connecting pipe should out from the largest hole otherwise the pipes will be ru...

Страница 7: ...able 4 4 the air liquid side of L2 is 15 9 9 5 N1 28 N3 28 N5 28 N6 22 N2 28 N4 28 A B D E C a b c e f d L1 L2 L5 L3 L4 The straight distance between copper pipe turning and the contiguous branch pipe...

Страница 8: ...should not longer than 15m Indoor unit branch pipe The main pipes of indoor unit and the indoor unit branch pipe components The downstream inner units of the main pipe L2 are N1 N2 and its total capa...

Страница 9: ...h 20m 36 42kBtu h 20m 48 56kBtu h Drop HEIGHT between indoor unit and outdoor unit The first connect method Indoor Unit The First Line Branch Pipe Outdoor unit a A L2 L1 B C D E L3 L4 L5 b c d e f Fig...

Страница 10: ...er enters the pipes After the above vacuum drying of two hours use nitrogen to increase the pressure to 0 05 MPa vacuum breaking and use a vacuum pump to decrease the pressure to lower than 100 7kPa o...

Страница 11: ...u h Hz Voltage Min V Max V MCA TOCA MFA MSC RLA kW FLA 220 240V 1Ph 50 60Hz Power Supply Compressor OFM Power Source PQE PQE PQE L N P Q E X Y E Outdoor power supply Indoors Power supply ODU IDU IDU I...

Страница 12: ...ntroller Wired controller P Q E P Q E X Y E Please use the shielded wire and the shield layer must be grounded Note The wired controller and centralized controller in the dashed box are optional acces...

Страница 13: ...Wire controller The reserved wire control function is indicated in broken line table users can purchase the wire controller when necessary In broken line table users can purchase the wire controller...

Страница 14: ...ustomers in details Please press constraint cool button to carry out refrigerant recycling process Keep the low pressure above 0 2MPa other wise compressor may be burnt out Fig 7 1 NOTE 7 1 Important...

Отзывы: