2-8
MDriveAC Plus Microstepping Hardware - Revision R031808
Relevant to Firmware Version 3.0.02
Switch Interface Example
Switch Interface
(Sinking)
Switch Interface
(Sourcing)
+
+5 to +24VDC
Optocoupler Reference
Enable Input
SPST
Switch
GND
+
Enable Input
+5 to +24VDC
Optocoupler Reference
GND
SPST
Switch
Enable Input
MDriveACPlus
Microstepping
MDriveACPlus
Microstepping
Figure 2.1.6: Switch Interface Example
Fault (Temperature Warning) Output
The MDriveAC Plus Microstepping features an Open-Drain Fault output located at Pin 19 of connector P1. This
is an impending over-temperature and over-temperature fault.
When the internal temperature of the MDriveAC Plus reaches the temperature specified by the WARN_TEMP
parameter, the output will pulse at 1 second intervals (1/2 second on, 1/2 second off). When an over-temperature
fault state is reached the output will latch on.
The output will remain in the latched condition until a power cycle, or new parameter set from the IMS SPI Mo-
tor Interface.
Fault Output
Input Type
Open Drain
Drain-Source Voltage
+5 to +24 VDC
Drain Current
50 mA
Table 2.1.3: Fault Output Specifications