ILC LightLEEDer Operation Manual
Version 1C 3/14/17
Phase Monitoring Module Configuration and Wiring:
The lightleeDer panel provided with optional Phase Monitoring Module will require field wiring the phase “B” and
phase “C” un-switched normal power to the PMM.
1. Verify the PMM is installed and power from the transformer is connected to “FROM TRX 24VAC CT”
terminal.
2. The “TO RelAYs” terminal will feed the power distribution card. (see Figure 4)
3. normal un-switched phase “A” power will feed the panel transformer.
4. Phase “B” and “C” un-switched normal power will connect to the PMM terminals, along with a normal power
neutral.
5. Verify the disable jumpers are removed for phase “B” and “C” monitoring operation.
6. switch on the three circuits to be monitored and verify that the A, B, C phase status leD’s on the PMM are lit.
7. Test operation using the Test button to trigger the PMM.
Appendix M
PHASE
PHASE
NEUT
B
C
T
O RELA
Y
S
24V
A
C C
T
77013547A
C
POWER
B
A
NO
C
NC
TEST
B
C
FR
OM
TR
X
+
-
DISABLE
2.00
4.50
PHASE "B" STATUS LED
PHASE "B" INPUT TERMINAL
120/277 VAC
NEUTRAL TERMINAL
PHASE "C" INPUT TERMINAL
120/277 VAC
PHASE "C" STATUS LED
AUXILLARY OUTPUT
NORMALLY OPEN/CLOSED
1 AMP 30VDC
POWER INPUT 24VAC CT
FROM TRANSFORMER
CONTROLLED OUTPUT
TO RELAYS - RBOM AND
POWER DISTRIBUTION CARD
EMERGENCY CONTROL
TEST BUTTON
PHASE "A" STATUS LED
DISABLE JUMPERS
PHASE "B" AND "C"
RL
Y 2
RL
Y 4
RL
Y 6
24V
A
C C
T
24V
A
C C
T
24V
A
C C
T
24V
A
C C
T
24VAC CT
PHASE
PHASE
NEUT
B
C
77013547A
C
POWER
B
A
B
C
T
O RELA
Y
S
24V
A
C C
T
NO
C
NC
TEST
FR
OM
TR
X
-
+
J5
+
+
-
-
N
NE
AD
FF
O
O
LI
LO
CK
M
AL
LO
NOR
+
-
DISABLE
ON
NC
OFF
A
A
R5
R6
R7
R8
77013490 R1
TCP-IP
0
F
E
B
D
C
A
8 9
LS
OUT
Lighting Controls, Inc.
Power Distribution card
Power out to RBOM
Power from Transformer to PMM
Panel transformer
Normal power Phase "A"
120/277VAC - 24VAC CT
Switched output from PMM
to Power Distribution card
Power to ILC LightLEEDer
control processor input
Return from relay output
of PMM
Normal Power
Monitor Input
120VAC - 277VAC
Phase A
Neutral
Phase C
Note: Phase A
connects to
control
transformer.
Normal power connections
Phase "B and "C"
Figure 3 - Phase Monitoring Module detail
The Phase Monitoring Module is provided with mounting back plate and barriers for voltage division, along with
a monitoring input terminal label for phase B and C connections. When installing the PMM in the panel, it is nor-
mally mounted in upper right section taking up relay locations 2 & 4. The PMM can be installed in another area of
the panel, but the wiring leads for the 24VAC CT would need to be extended.
Figure 4 - Termination of 24VAC CT wiring to PMM