BACnet Module (panel level)
BACnet is an open protocol developed by AshRAe for building automation and control systems. lightleeDer BACnet
MsTP or IP modules give you direct control of the panel. With the panel module, commands can be sent to the panel
to force relays On and OFF, force relays On and OFF with a timer option (blink, double blink, hID delay, Alarm On,
Alarm OFF, Pulse On, and Pulse OFF), monitor relay status, monitor input status, and enable/disable inputs.
Setup:
1. From the home screen, press
eDIT
(Networked Panels
connect to the Network Controller Node 00 as shown in
Section 3.0)
2. Press
2 times to scroll down
3. Press
OTheR DeVICes
4. Press
ADD-On MODUles
5. Press
ADD-On MODUle 1, 2, 3, or 4
6. Press
or
and select the PROTOCessOR option
ILC LightLEEDer Operation Manual
Version 1C 3/14/17
ILC LIGHTLEEDER
TUE 01/21/11
.
09:46:54 PM
.
EDIT
NODE 01
.
TIMERS
CLOCK
PRESETS
OTHER DEVICES
ADD-ON MODULES
DIMMER OUTPUTS
MOTOR OUTPUTS
ADD-ON MODULE 1
ADD-ON MODULE 2
ADD-ON MODULE 3
ADD-ON MODULE 4
ADD-ON MODULE 1
TYPE:PROTOCESSOR
EDIT
BACnet Module Setup
Press
eDIT, then
twice
Press
OTheR DeVICes
Press
ADD-On MODUles
Press
ADD-On MODUle 1, 2, 3, or 4
Appendix e
Press
or
and select
the PROTOCessOR option
LightLEEDer BACnet IP
Control Module
(Panel level)
2.0”
3.5”
Ribbon connector to panel
RJ45 to BACnet
termination
LightLEEDer BACnet MSTP
Control Module
(Panel level)
97013517
77013517A
RX
TX
PWR
-
C11
+
+
U1
+
C3
-
Y1
-
-
+
+
+
C6
C5
C7
C1
R1
C2
D2
R3
J3
2.0”
3.5”
Ribbon connector to panel
RS485 BACnet
cable termination
For a LightLEEDer BACnet point map go to:
http://ilc-usa.com/product_detail.php?pid=32