ILC LightLEEDer Operation Manual
Version 1C 3/14/17
1.0 Enclosure
The enclosures are neMA 1 rated and are supplied with a hinged locking or screw cover designed for surface or flush
mounting. every panel is provided with 4 pre-drilled holes for easy mounting onto the wall or Unistrut™ framing. en-
closures are available in 5 sizes to accommodate from 4 to 64 relays. enclosure sizes with 8 - 64 relays are configured
with relays on both sides of the enclosure for easy routing of wires from the circuit breaker box and the 4 size enclo-
sures relays are on the right side designed for distributed mounting. All enclosures include high voltage barriers to
separate Class 1, Class 2, and emergency wiring. see Table 1.1 for enclosure dimensions and relay quantities.
1.1 Transformer
• Multi-tap primary that will accept 120/277 VAC or 120/347 VAC.
• 24 VAC w/center tap secondary.
• 40VA of power
• equipped with an internal self-resetting fuses.
1.2 Controller Board
The controller provides the intelligence to control relays, monitor
inputs, and to communicate in various ways. The integrated
components include:
• Power supply used to convert the transformers 24 VAC into DC
voltage used by the entire panel.
• Real-Time clock provides all time controlled functions including
time of day, day of week, date, and day-light-saving time. It will
keep the time for at least 45 days without power to the CPU.
• non-volatile memory for storing programming information.
Retains data for up to 200 years without any power to the CPU.
• Data line communications through RJ45 connectors for communi-
cating with other panels and lightsync data line devices.
• UsB serial communications for programming and interfacing with
a personal computer.
• TCP/IP communications (optional) for programming and interfac-
ing with a personal computer over a lAn or the Internet.
• Relay override switches for “All On” or “All Off” operation of relays,
which is useful when no programming is present.
Enclosure Size
# of Relays
Width
Height
Depth
LightLEEDer
4
up to 4
14 Inches
11 Inches
6 Inches
LightLEEDer
8-16
up to 16
20 Inches
20 Inches
6 Inches
LightLEEDer
24-32
up to 32
20 Inches
29 Inches
6 Inches
LightLEEDer
40-48
up to 48
20 Inches
38 Inches
6 Inches
LightLEEDer
56-64
up to 64
20 Inches
48 Inches
6 Inches
Table 1.1 – ILC LightLEEDer Configurations
lighting Controller Details
Main Power
Switch
Terminal
block for
24VAC in
Power ON LED
USB Port
RJ45 Data Out
24VAC
secondary
120/277 VAC
or
120/347VAC
primary
TCP/IP (optional)
RJ45 Data In
RJ45 Local
Relay Override
Switches
LightLEEDer Controller Board
Power Distribution Board
Transformer