INS-500 & INS-1000 • 5403645 • REV A • 6/17
A maintenance alert is noncritical to the operation of the nitrogen generator. The maintenance light will turn on and a maintenance
alert will appear on the IntelliGen
™
Display and IntelliView
™
website, and an e-mail will also be sent. The Trouble Horn will not
sound and the BMS will not trip. Maintenance alerts can be cleared by performing maintenance on the issue then going into the
"Maintenance Menu" and clearing the appropriate alert.
Maintenance Alerts and Actions
Maintenance Alert #1 - Standard Maintenance
Maintenance Alert #2 - Excess Nitrogen Demand (Sprinkler System Leak Rate Excessive)
Issue:
Maintenance Timer expired after 1,000 hours and the nitrogen generator needs maintenance.
Action:
1. Within 250 compressor operating hours, complete standard maintenance following the procedure in this manual.
2. Reset Maintenance Alert #1 by going into the Maintenance Menu on the display and following the procedure on page 22.
Issue:
Sprinkler system leak rate is greater than Leak Rate Warning Set Point. You have one week to address this before it turns
into a trouble alert.
Action:
1. Leak check nitrogen generator and sprinkler system. Repair leaks if found.
2. Adjust Leak Rate Warning Set Point. See page 35 for details.
Note:
Increased leak rates can cause excessive maintenance and damage to equipment.
3. Reset the Maintenance Alert #2 by going into the Maintenance Menu on the display.