background image

- 7 -

I:\OFFICE\Web Site\distiller pdf\100CSCE.wpd

SECTION 3 

!

 OPERATION

3.1 BEFORE YOU START

The flow switch trip point adjustment requires qualified service personnel to access inside the enclosure (see
Sections 2.2).  Make sure the trip point has been properly adjusted prior to start of operation.

3.2 SWITCH SETTINGS

Typically Rheotherm flow switches come from the factory set up for a 10 to 1 flow rate range, and with the
trip level set approximately as requested by the customer.

When power is first turned on, the flow switch may indicate a high flow rate, even if there is no flow
occurring.  Correct indication of flow level will result after an initial period, which can extend to about forty
(40) seconds and depends on where the trip adjust is set.

For standard flow switches, the relay operates as stated below.  For nonstandard units, the operation is
described in SPECIAL INSTRUCTIONS (SECTION 6).

Low Flow Switch — The relay is energized (N.O. contact is 

closed

) and the LED is 

green

 when the

flow rate is 

above

 the trip level.  Therefore, the alarm condition (relay de-energizes) occurs when the

flow rate drops below the trip level or there is a loss of power to the sensor (N.O. contact is 

open

) and

LED color becomes 

red.

High Flow Switch — The relay operation is exactly as described above.  When used as a high flow
switch, the alarm condition is considered to be when the relay is energized (N.O. contact is 

closed).

3.3 GENERAL INFORMATION

The Rheotherm instrument is compensated for a wide range of both ambient and flowing media temperatures.
However, abrupt changes in the temperature of the flowing material can cause the instrument to read the flow
rate improperly, which could lead to an inappropriate tripping of the relay or a delay in reading loss of flow.
A proper reading is obtained only when the transducer is in thermal equilibrium with the material.  Typically,
a 20°F abrupt change in temperature may require 40 seconds to stabilize.

In general, the heater used in the transducer does not develop enough power to cause damage to the system
in the absence of flow.  This includes those used in liquids even if the line becomes empty and filled with air.
Special cases will be discussed in the section entitled SPECIAL INSTRUCTIONS (SECTION 6).

3.4 USE AS A LEVEL SWITCH (Insertion Probes only)

The probe switch design can be used to provide one point level switch indication.  When the probe tips
are submerged in liquid, the relay is energized and the LED is 

green

.  When the liquid level drops below

the probes and they are surrounded by air or vapor, the relay de-energizes and the LED turns 

red

.

Содержание Rheotherm 100CS

Страница 1: ...have been thus defective this warranty being expressly in lieu of all other warranties express or implied and all other obligation or liabilities on Intek s part The purchaser will assume all responsi...

Страница 2: ...START 7 3 2 SWITCH SETTINGS 7 3 3 GENERAL INFORMATION 7 3 4 USE AS A LEVEL SWITCH 7 SECTION 4 MAINTENANCE 8 4 1 GENERAL MAINTENANCE 8 4 2 SPARE PARTS 8 4 3 TROUBLE SHOOTING 9 TABLE I TROUBLE SHOOTING...

Страница 3: ...ndicating high and low flow conditions Key features of Rheotherm flow switches are Non intrusive flow monitoring For pipe sizes from 030 to inch flow sensing is done from outside the flow tube No movi...

Страница 4: ...ive transducer Example of Example of TU probe with probe with NPT fitting flange fitting 1 3 PRECAUTIONS 1 Use proper input power Check the label on the unit for the input power requirements 2 Use rea...

Страница 5: ...nstructionscoverinstallation operationandmaintenance ofRheothermflowswitches instandard configurations Any special information pertaining to your unit is covered under CUSTOM INFORMATION SECTION 6 Tim...

Страница 6: ...alling CAUTION The electronics box should never be rotated for any reason Straight run for a flow switch is not a requirement particularly for flow no flow indications but for best repeatability some...

Страница 7: ...el shall be properly grounded with an anti static device to prevent damage to components within the electrical enclosure The input power requirement is listed on the tag on the electronics enclosure m...

Страница 8: ...0 seconds and depends on where the trip adjust is set 2 4 ADJUSTING THE TRIP POINT Adjust the flow switch trip point as follows see Figure 2 for trip potentiometer location All adjustments must be mad...

Страница 9: ...O contact is open and LED color becomes red High Flow Switch The relay operation is exactly as described above When used as a high flow switch the alarm condition is considered to be when the relay i...

Страница 10: ...nts gas bubbles and non solubles can result in measurement below actual flow rates Periodic checks and cleaning should be performed to insure a clean pipe or probe surface It should be part of normal...

Страница 11: ...iometer clockwise until layer build up stabilizes After switch has been operating properly relay trips with flow above trip level and cannot be adjusted using SECTION 2 4 instructions Relay does not t...

Страница 12: ...ewed SECTION 4 3 TROUBLE SHOOTING and have questions please call our experienced engineers for assistance In many cases we can solve a problem over the phone Please provide as complete a description a...

Страница 13: ...CATION Model no Serial no Customer identification 6 2 CONFIGURATION The configuration of this unit as originally shipped from the factory Input Power 24 Vdc Line Connection 6 3 SPECIAL INSTRUCTIONS Re...

Страница 14: ...terface connector Enclosure lid 24 14 Ga Flow switch electronics Check enclosure label for proper input power For VDC input connect positive to H or terminal and negative to N or Figure 1 Model 100CS...

Отзывы: