ALARM OUTPUT NOTIFICATION
To configure which events cause DVXNotify to trigger the normally open alarm
output, complete the following steps (you must be logged on to MasterControl
with Administrator or Supervisor permissions):
1.
Open the Plugin Properties window by clicking the MCPlugin icon in the
system tray, and then select the DVXNotify tab (refer to Figure 60).
2.
Make sure Disable Alarm Output Notification is not selected.
3.
Select the Minimum Latch Time—the minimum number of seconds that
the alarm output will be triggered when the selected events occur. If the
event is shorter than the Minimum Latch Time, the alarm output is trig-
gered for the duration of this setting (or until you click Reset Alarm Out-
put); if the event is longer than the Minimum Latch Time, the alarm out-
put is triggered for the duration of the event. Alternatively, you can se-
lect Manual Reset Required, which requires you to click Reset Alarm
Output to deactivate the alarm output.
4.
Under Delay Between Alarms, select the minimum amount of time (in sec-
onds) between output trigger activations. If a second alarm occurs be-
fore this amount of time has elapsed after the end of the first trigger, the
second alarm is ignored.
(continued)