** If deviation is higher than 2Vac, we suggest to adjust voltage output in UPS by SETTING / CALIBRATION / INVERTER section
of configuration menu.
Setting:
Calibration:
Control
Bypass
Batt: 273.0 +0,0
Measurement
ECO
Inv: 220.0 +0,0
Information
Output
Chg: 273.0 +0,0
Setting
Battery
Alarm
Calibration
Others
13.- If AC output voltages are as expected, please set to "ON" external output breakers for all UPS progressively. Start with UPS
Nº 1, then UPS Nº2, etc. After that, all UPS outputs are connected in parallel.
14. Check to confirm there are no error or alarm messages on LCDs. At this moment all UPS are working in NORMAL Online
mode and connected in parallel.
15.- It is time to power on equipments connected to UPS output. Power on progressively one by one. Check on UPS LCDs how
power output rises meanwhile equipments are powered on.
** Once all output load is connected check power output is below 100%.
** At this moment, UPS parallel system is powering your system in NORMAL Online mode.