7. CONTROL SOFTWARE 

 

 
Most of the models of this UPS family come with USB port to communicate with your PC. In that way UPS can 
be monitored and configured. Your PC can be shutdown automatically when a input AC failure is detected 
saving your information and providing a controlled shutdown. Event log and alarms can also be monitored from 
your PC. 

Control software can be downloaded from our website: www.integra-ups.com. We keep updated last updated 
version. User manual and installation manual is also available in our web. 
Our software is available in different versions for: Windows, Mac OSX, Linux and Unix. 
 

8. TROUBLE SHOOTING TABLE 

 

 

PROBLEM 

CAUSE 

SOLUTION 

UPS does not turn ON  
LED OFF 

ON button has not been properly 

activated. 

Push ON button during 2-3 seconds 

Very low battery level 

Keep UPS plugged to main service to 
recharge batteries 

Battery failure 

Contact service center to replace 
batteries 

UPS goes to battery mode 

even main source is OK 
Front LED flashing in green 
color. 
Intermitent BEEP alarm 
activated 

Input cable or plug is not 
connected to main source 

Check and plug properly 

Input breaker is activated (open) 

Check and reset input breaker 

Input breaker is activated 
frequently 

Equipments connected to UPS 
outlets overload UPS. 

Check and unplug equipment until 
overload condition is solved 

 
Continuous BEEP alarm. 
 

UPS is overloaded 

Check and unplug equipment until 
overload condition is solved 

UPS power off when AC 
main source fails  
(runtime = 0s) 

Low battery level because recent 
discharge 

Keep UPS plugged to main service to 
recharge batteries 

Battery failure 

Contact service center to replace 
batteries 

 
 
 

 

USER MANUAL - 

EPLUS 501/701/901

   

ENGLISH

 

________________________________________________________ 

www.integra-ups.com                                                                                                        1303-EPLUS 501/701/901-ENG   - 

3

 

 

2. QUALITY / PERFORMANCE / SAFETY 

 

 

SAFETY - LOW VOLTAGE DIRECTIVE (2006/95/EC) 

UPS Part 1-1: General & Safety UPS in accessible areas 

IEC/EN 62040-1 

ELECTROMAGNETIC COMPATIBILITY - EMC DIRECTIVE ( 2004/108/EC) 

UPS, Part 2, Electromagnetic Compatibility: 

IEC/EN 62040-2

  

    Low Freq. Conducted Disturbances & Signals: 

IEC/EN 61000-2-2 

    Electrostatic discharge immunity Test: 

IEC/EN 61000-4-2  

(Air: Level 3, Contact: Level 2) 

    Radiated radio Frequency immunity: 

IEC/EN 61000-4-3 (Level 3) 

    Electrical Fast Transient / burst immunity: 

IEC/EN 61000-4-4 (Level 3) 

    Surge immunity: 

IEC/EN 61000-4-5 

(L-L: Level 2, L-G: Level 3) 

UPS Part 3: Methods of operation, specifications and test requirement 

IEC/EN 62040-3 

IT Equipments. SAFETY. Part 1: General Requirements 

IEC/EN 60950-1 

IP PROTECTION 

IP20 (static) 

QUALITY MANAGEMENT: 

Manufactured under: 

ISO 9001 : 2000 

ENVIRONMENTAL MANAGEMENT: 

Manufactured under: 

ISO 14001 : 2004 

Any modification made by user or operator may affect compliance of the safety and performance certifications listed above. 

UPS manufacturer is not responsible of any modification made on the product or its accessories after it is manufactured.  

This product is designed to operate in domestic and commercial environment. CE standards apply for 230V models. 

 

 

3. BATTERIES MAINTENANCE 

 

 

Batteries capacity, in general (of all kinds), decreases with time and use. 

 

Our products contain high quality batteries only. 

 

Batteries useful life in our UPS is between 3 and 5 years, considering environment temperature under 

25ºC and optimal operational conditions. This time can be dramatically reduced by high temperature and 
other adverse operation condition. 

 

Batteries life expectancy may be also affected by other operation conditions such as electrical service 
quality as well as number and kind of equipments connected to UPS 

 

Batteries should be periodically tested to check capacity and assure and appropriate back up. 

 

* To enlarge batteries life expectancy it is recommendable to fully discharge UPS once every 3 months 
* During long UPS storage recharge batteries according to following table: 

 

STORAGE TEMPERATURE 

FREQUENCY 

RECHARGING TIME 

-25°C a +30°C 

Every 4 months 

4 h 

+30°C a +45°C 

Every 2 months 

4 h 

 