background image

14.02-13

Connecting the 2100-A

16

 to the 2100-R2.

1/

Power must be off before installing the 10 way ribbon cable and 2100-ARI board
supplied with the 2100-R2.

2/

Remove the cover off the 2100-A

16

.

3/

An exchange cover, with a precut slot for the ribbon cable, is available free of
charge from your supplier. P/N: 2100-A16-COVERSLOT.
Alternatively you may wish to modify the existing cover:

Cut a 1mm slot, 20mm deep, just below terminal numbers 1, 2 & 3.
Carefully smooth the edges of the cut so the ribbon cable does not get damaged.

4/

The 2100-ARI is supplied with the ribbon cable attached. Use antistatic precautions
when installing. Carefully orientate the 2100-ARI board as shown above. Locate the
two plastic standoffs over the corresponding holes in the 2100-A

16

, and the 10 pin

connector. Once all three are aligned, push the 2100-ARI firmly into the 2100-A

16

.

5/

Connect the other end of the cable to the 2100-R2. Ensure both ends of the cable are firmly connected.

6/

Slide the cable into the slot, and replace the cover on the 2100-A

16

.

7/

The 2100-R2 must be enabled in the programming dialogue boxes. Advanced ‘2100-R 2 Relay Expander’ options.
For detailed programming info, refer to
‘Programming 2100-Series Remote Station’ in the Microscan Manual.

8/

A 2100-R2 connected to the 2100-A

16

 must share the same power supply disconnect device and over current

device. Both units must be powered and unpowered at the same time to prevent indeterminate relay states.

2100-A

16

 Rev1.3 Relay Output Expansion - Using 2100-R2 Relay Expansion.

Output relay expansion is available using the 2100-R2, 16 relay output expansion module. This allows the 2100-A

16

 to

stand alone as a 16 channel controller / alarm unit. The 2100-R2 relay outputs can be used for any combination of
control and alarm functions. The control parameters for each of the 16 controllers is downloaded from user friendly
Microscan Software, and stored in permanent memory on the 2100-A

16

. These parameters include Setpoint (SV),

Output Switching Differential, Auto / Manual, Manual Output Setting, Dual Action Control, Single Action Control, Heat /
Cool, Heat Only, Cool Only. The 16 controller / alarms will operate unaffected by computer power downs, reboots, etc.
The relay outputs can also be accessed directly from the Scada.

A      B      B

INPUT 2

A      B      B

INPUT 1

 

1

 

2

 

3  

4

 

5

 

6

1x20mm

SLOT

.

.

H2 A16

Interface

H3 2ND

2100-R2

H2 A16

Interface

H3 2ND

2100-R2

2100-R2 Relay Expander

2100-R2 Relay Expander

2100-R2 Relay Expander

2100-R2 Relay Expander

2100-R2 Relay Expander

Serial No.

Serial No.

Serial No.

Serial No.

Serial No.

2100-ARI

2100-A

16

-R1.3

WARNING:

The 2100-ARI is STATIC SENSITIVE.
Only touch the edges of the PCB.

Ensure standoffs lock firmly into the 2100-A

16

 board.

2100-R2 Relay Expander

2100-R2 Relay Expander

2100-R2 Relay Expander

2100-R2 Relay Expander

2100-R2 Relay Expander

Serial No.

Serial No.

Serial No.

Serial No.

Serial No.

FIRST 2100-R2

SECOND 2100-R2

Содержание 2100-A16

Страница 1: ...INTECH Micro 2100 A16 REV 1 3 Installation Guide 14 01 1 TECHNOLOGY QUALITY A W A RD ISO9001 E G ISTE R RE D M ANU A T U R E R C F Z985...

Страница 2: ...nnection Page 12 2100 ME Memory Expansion Page 12 2100 R2 Relay Expansion Page 13 RS485 Serial Connection Page 14 RS422 Serial Connection Page 14 RS232 Serial Connection Page 15 RS232 Radio Modem Seri...

Страница 3: ...asy to Install z z z z z Compact DIN Rail Mount Enclosure Ordering Information 2100 A16 Rev1 X Standard Unit Analogue Inputs Pt100 0 100C Analogue Outputs 4 20mA RS485 Comms 85 264Vac dc Power Supply...

Страница 4: ...t note 3 Mineral Insulated Thermocouples With Isolated Junction Essential Cold Junction Comp 0 60C CJC Drift 0 03C C Typical for Input 1 Refer to notes under 2100 A16 Input Connection Diagram for T C...

Страница 5: ...for 1min General Specifications Unless otherwise stated in other input specifications Accurate to 0 1 FSO Typical Linearity Repeatability 0 1 FSO Typical Channel Separation 0 1 FSO Typical Ambient Dri...

Страница 6: ...B A B B A B B A B B A B B A B B A B B AO COM AO 1 AO 2 Relay COM Relay 1 Relay 2 DI COM DI 1 DI 2 DI 3 DI 4 H3 EXPANSION CONNECTOR J9 J10 J11 J12 J13 J14 J15 J16 J1 J2 J3 J4 J5 J6 J7 J8 H1 SUPPLY VOL...

Страница 7: ...i e c e r s i n o i t a t S n e h w e v i t c A X T a t a d l a i r e s g n i t t i m s n a r t s i n o i t a t S n e h w y l n o e v i t c A E X T a t a d t i m s n a r t o t y d a e r s i n o i t a...

Страница 8: ...sing a clean voltage free field contact Note 4 All cables must be screened and the screens earthed at one end only Note 5 Voltage free contact values must be brought in through tags in the Scada Softw...

Страница 9: ...6 The mounting orientation of the 2100 A16 eg vertical or horizontal affects the CJC accuracy of different inputs The affects are more noticeable on small temperature ranges For example mounting the 2...

Страница 10: ...relay can be configured for a Normally ON or Normally OFF output state E g for fail safe operation The Normally ON OFF settings are retained in software on power down but the relays are de energized...

Страница 11: ...1 61 AO 2 62 2 1 5 4 8 7 Fourth 2100 M 51 COM 53 Iout 60 CS COM 61 RESET 62 CLOCK 11 10 EXPO 3 26 COM 28 Iout 29 CS COM 30 RESET 31 CLOCK OR The analogue output mode is set in the Station Advanced Di...

Страница 12: ...Protective enclosure only to be opened by qualified personnel Remove ALL power sources before removing protective cover 14 02 12 2100 A16 Connection Example Diagram for Using the 2100 RL2 2 Relay Slav...

Страница 13: ...nt device Both units must be powered and unpowered at the same time to prevent indeterminate relay states 2100 A16 Rev1 3 Relay Output Expansion Using 2100 R2 Relay Expansion Output relay expansion is...

Страница 14: ...ration 24 23 21 22 1 Shimaden SD20 with RS422 option 3 9 5 Shimaden SR253 with RS485 option 2100 A16 Remote Station 70 71 72 73 74 IMPORTANT i All cables must be screened ii All screens must be connec...

Страница 15: ...me a unique station number before using the programme setup button in the Scada Software Requires Microscan Version 4 02 onwards For detailed programming info refer to Programming 2100 Series Remote S...

Страница 16: ...TX delay is zero the data is sent immediately upon receiving a command RX The period is specified in TXE units of 2 5ms i e 10units 25ms TX TXE delay TX delay 2100 A16 Delay Settings Table Mode 3 210...

Страница 17: ...e Scada COMMS allowing a PLC to read back data that the Scada will be showing Note 8 Digital inputs and digital outputs are not available in this mode 2100 A16 58 57 56 55 54 62 61 60 48 49 Bin SWITCH...

Страница 18: ...as an Intelligent Multiplexer Connection Example 1 Connection of a 2100 A16 to a PLC with open collectors commoned to 24V of an external power supply PLC Input Module Analogue Input No 1 Analogue Inp...

Страница 19: ...can be connected in this configuration provided the open collectors can handle the load For Binary Channel Selection the resistor 2 2k Up to two 2100 A16 can be connected in this configuration provid...

Страница 20: ...ithout notification 2100 A16 Rev 1 PLC RTX Fail Safe System The PLC uses one channel of the 2100 A16 to verify that the A16 is reading the channel correctly AO1 is working and the clock and reset BCD...

Страница 21: ...umper Settings Note 2 The retransmission modes of AO1 AO2 canbeusedwhentheModbusRTUprotocol is used Note 3 Rev 1 3 ONLY s e s s e r d d A l i o C l i o C x x 0 0 0 t u p u O l i o C x x 0 0 0 t u p u...

Страница 22: ...0 0 3 F F F 0 0 0 t i B 2 1 6 1 t u p n I 3 x u M 7 3 0 0 3 s d r o W 2 4 5 7 E E E I 1 1 t u p n I 7 9 0 0 3 F F F 0 0 0 t i B 2 1 1 t u p n I 4 x u M 9 3 0 0 3 s d r o W 2 4 5 7 E E E I 2 1 t u p n...

Страница 23: ...en inputs is 4 channels second Channels that are not scanned can be disabled via the station programming dialog boxes To speed up operation for multiplexer mode set the Scan Mode on the advanced dialo...

Страница 24: ...the sockets operations You may need to open the IP address and port numbers for the commands to go through We have found problems with Nortons system Works 2003 and found it necessary to disable emai...

Страница 25: ...have minimum free air space of 20mm Foreign matter must not enter or block the draft holes 3 Do not subject to vibration or excess temperature or humidity variations 4 Avoid mounting in cabinets with...

Страница 26: ...lve motors this may help to stabilise the input signal Use caution when doing this as unless the inputs are at the same potential large earth currents will flow through the 0V rail causing errors on A...

Страница 27: ...2 Once the above conditions have been met and the wiring checked apply power to the 2100 A16 the loops sensors 2100 Rs and 2100 Ms Allow a 5 minute warm up period longer for thermocouples refer to Inp...

Страница 28: ...not be air or gas tight 3 Check cables entering the RTD sensor head Thermocouple Inputs 1 Repeat 4 of commissioning Do it regularly at least once a month 2 Replace defective protection tubes even if...

Отзывы: