background image

Customer Services (858) 578-7887 & (888) GO IN

TEC

IN

TEC

 Controls, 12700 Stowe Dr., Suite 1

0

0, Poway, CA 92064

Fax (858) 578-4633 & (888) FX IN

TEC

www.inteccontrols.com

Specification subject to change without notice.

Printed in USA 131119

Polygard® is a registered trademark of MSR

LGC/LG2-04

PolyGard

®

 Multi-Point Controller

User Manual - LGC/LG2-04 

Page 20

3.7.6  Time, Date 

Input and correction of the system time and date. Selection of the time and date format. 

Symbol Description Default 

Status

Function 

US 

Time format  US 

EU = Display time and date in EU format 

US = Display time and date in US format 

hh.mm.ss  Time 

hh.mm.ss = Input the correct time (EU format) 

hh.mm.ss am = Input the correct time (US format) 

TT.MM.JJ  Date 

TT.MM.JJ = Input the correct date (EU format) 

MM.TT.JJ = Input the correct date (US format) 

3.7.7  Analog Output  

The Controller has two analog outputs (AO) with 4 to 20 mA signal per control module. Each of the analog outputs 

can be assigned the signal of one or more sensor points. The assignment occurs in the menu „SP Setup“ for 

each SP. The sensor point sends the signal that is defined in the menu „C/A Mode“. 
The Controller determines from the signal of all assigned sensor points the minimum, the maximum or the average 

value and sends this value to the analog output. The determination of which value is sent is defined in this menu 

„Analog Output X“. The analog output can be calibrated with for 4 and 20 mA. In addition the AO can be adjusted 

with an ampere meter attached (measuring range 25 mA) then respective AO factor can be changed to adjust the 

analog  output  4  and/or  20  mA  .  During  AO  calibration  no  evaluation  is  made  of  the  sensor  point  signals.  This 

calibration is factory-set. The factors should only be changed if you have an accurate amp meter. 

Symbol Description Default 

Status

Function 

Max. 

Select 

Output mode  Max. 

Min.       = Spends the minimum value of all assigned SP 

Max.      = Spends the maximum value of all assigned SP 

Average = Spends the average value of all assigned SP 

4.0 

20.0 

Calibration 

4.0 

20.0 

4.0      = Calibration factor at 4 mA 

20.0    = Calibration factor at 20 mA 

3.7.8  Define the Failure Relay 

Define the Failure Relay. See also malfunction management (3.1) 

Symbol Description Default 

Status

Function 

05 

Failure Relay  R05 

R05 = Define the failure relay 

3.7.9  Power On Time 

Sensors need a warm up period, until the chemical process of the sensor reaches a stable condition. During this 

warm up period the current signal can lead to unwanted false alarm. Therefore the Controller starts reporting after 

switching on of the power supply and the delay On Time is passed. While this time runs off, the Controller does not 

report alarms. The power on status is displayed in the display. 

Symbol Description 

Default 

Status

Function 

30 s 

Power On Time  30 s 

XX = Define the Power On Time (sec.) 

3.7.10  Activation of expansions modules 

The Multi point Controller can have expansions modules; therefore only activate Expansions modules for every 

four sensor points in addition to the controller module.  

Specifications subject to change without notice. | USA 131119 | Page 20 of 30

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

LGC-LG2 – UserManual

Polygard® is a registered trademark of MSR | LGC/LG2-04

Specifications subject to change without notice. | USA 160104 | Page 20 of 30

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

LGC-LG2 – UserManual

PolyGard

®

 is a registered trademark of MSR-Electronic GmbH | LGC/LG2-04

INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com

Specifications subject to change without notice. | USA 200211 | Page 20 of 30

LGC-LG2 – UserManual

Содержание PolyGard LGC/LG2-04

Страница 1: ...1 2006 Specifications subject to change without notice USA 131119 Page 1 of 30 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC relevantsolutions com inteccontrols LGC LG2 UserM...

Страница 2: ...point Hysteresis 16 3 6 6 Delay time ON or OFF 16 3 6 7 Control Mode 16 3 6 8 Assigned SP Fault to Relay 16 3 6 9 Assigned Stage to Relay 17 3 6 10 Assigned SP Signal to analog Output 17 3 7 Menu Syst...

Страница 3: ...Notes and General Information 30 8 1 Intended product application 30 8 2 Installers responsibilities 30 8 3 Maintenance 30 8 4 Limited warranty 30 Specifications subject to change without notice USA 1...

Страница 4: ...to any compatible electronic analog control DDC PLC control or automation system The adjustable parameters and staged thresholds make this system very flexible for sensor measuring and control The co...

Страница 5: ...r Failure is detected or when Maintenance needed 2 2 Setting Change Parameters Desired menu window open Opens menu window if password approved the cursor jumps on the first position segment which can...

Страница 6: ...rvice technician A third code level permits activation or deactivation of sensor points SP A password must be re entered if 15 minutes goes by without the press of a push button All menu windows can b...

Страница 7: ...ay Status Display of the sensor values See Section 3 4 Sensor Readings Reading and change of the relay parameters See Section 3 5 Relay Setup Reading and change of sensor point parameters Activate or...

Страница 8: ...le after the removal of the cause Select Menu System Errors Example Failure SP 01 3 mA Malfunction Reset Malfunction Reset or Malfunction Ereased Cause not eliminated Acknowledgement not possible 3 1...

Страница 9: ...in the sequence they happen The sensor points are over laid where a stage has been exceeded Changes are not possible in this menu Symbol Description Function SP 01 Sensor Point SP Point No SX Stage S...

Страница 10: ...s In this menu you can display the current value CV and average value AV with sensor unit and type for each active sensor point SP as well as the define the mode of control CV or AV mode Symbol Descri...

Страница 11: ...Definition Relay Function Symbol Description Setting Status Function R 01 Relay No Selection Relay 0 Function 0 0 Relay Function steady 0 Relay Function flashing Periods time sec Impulse Break 1 1 Rel...

Страница 12: ...nment appropriate digital input The horn function is activated only if at least one of the two parameters time or digital input is set Special function Response After acknowledging the relay via Pushb...

Страница 13: ...R 01 Relay No Selection Relay DI ON External On 0 If digital input closed relay switch ON DI OFF External Off 0 If digital input closed relay switch OFF 3 6 Menu SP Setup Display and Change Parameters...

Страница 14: ...3 6 9 and 3 6 10 Measuring range 300 ppm SP Signal linear Threshold 1 100 ppm Threshold 2 100 ppm Threshold 3 200 ppm Threshold 4 200 ppm Threshold 5 300 ppm Hysteresis 15 ppm Delay ON time 0 s Delay...

Страница 15: ...ee the sensor manufacturing specifications The measuring range must agree with the signal 4 to 20 mA attached transmitters 4 mA Display 0 20 mA Display Measuring range max point 3 6 4 SP Signal Gas tr...

Страница 16: ...mbol Description Default Status Function SP 01 Sensor Point Selection SP No 0 s Delay Time ON 0 Concentration Stage Threshold Relay is only activated at expiration of the defined time sec 0 sec No Del...

Страница 17: ...al defined in the control mode current or average value is transmitted The assignment occurs in the menu assignment alarm alarm relay in the right place Analog output see also 3 7 2 3 7 Menu System Se...

Страница 18: ...ime 30 s EP Module 1 Not active EP Module 2 Not active EP Module 3 Not active EP Module 4 Not active EP Module 5 Not active Time hh mm ss Specifications subject to change without notice USA 131119 Pag...

Страница 19: ...J Input date for next maintenance 0853 Phone No Input the individual service phone No 3 7 4 Average Function The Controller calculates for each active sensing point the arithmetic average value from 1...

Страница 20: ...Description Default Status Function Max Select Output mode Max Min Spends the minimum value of all assigned SP Max Spends the maximum value of all assigned SP Average Spends the average value of all...

Страница 21: ...door Consider any unusual condition or requirements of the Customer 4 1 Electrical Connection Installation must be per local electrical codes with the consideration of the technical requirements of t...

Страница 22: ...onic GmbH LGC LG2 04 Specifications subject to change without notice USA 140924 Page 5 of 6 INTEC Controls 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC inteccontrols com FIE...

Страница 23: ...ate DC power supply ill 6 see previous page ill 4 Digital Inputs DI01 to DI04 X11 1 2 3 4 5 6 7 8 9 10 11 12 ill 5 Analog Outputs AO01 to AO02 X11 1 2 3 4 5 6 7 8 9 10 11 12 4 20 mA AO02 Com 4 20 mA A...

Страница 24: ...gnment of the relays to the individual stages must occur with start up unless arrangements have been made with the factory for programming All other parameters are to be examined and adapted to the lo...

Страница 25: ...P Signal Stage Setpoint 1 Stage Setpoint 2 Stage Setpoint 3 Stage Setpoint 4 Stage Setpoint 5 Hysteresis Delay ON time Delay OFF time C A Mode Assigned Failure Stage Assigned Stage Relay System Setup...

Страница 26: ...Default Energezid 0 s No 0 0 0 0 0 R01 R02 R03 R04 R05 6 3 Sensor Setup Stage Setpoints Hyst Delay time sec CV AV SP No SP Status Type Measur ing range SP Signal S1 S2 S3 S4 S5 ON OFF Default Not act...

Страница 27: ...wards communication to BAS Liquid Crystal Display LCD NEMA 4X controller enclosure Easy maintenance ORDERING INFORMATION Upwards Communication Options BACnet NRTL Performance Tested Certified Conforms...

Страница 28: ...ity intermitted 0 to 99 RH non condensing working pressure Atmospheric 10 SPECIFICATIONS Electric Power supply controller 24 VDC 15 20 50 60 Hz auto resettable fuse sensor s transmitter s 24 VDC from...

Страница 29: ...ay protection NEMA 4X IP65 installation Wall surface mounted or single gang electrical box Dimensions H x W x D 5 12 x 3 31 x 2 95 in 130 x 84 x 75 mm Cable entry 1 hole for 1 2 in conduit for wall su...

Страница 30: ...ons as provided in the user manual 8 3 Maintenance It is recommended that the PolyGard LGC LG2 04 performance check is done on a routine schedule Any performance deviations may be serviced based on ne...

Отзывы: