background image

3 Electrical Connection 

Consider static electricity instructions (ESD)! See point 2. 

The technical requirements and regulations for wiring, electrical security, as well as project specific
and environmental and local conditions etc. must be observed when mounting.

Avoid any influence of external interferences by using shielded cables for the bus line, but do not
connect the shield.

When selecting and installing the cables you have to comply with the regulations concerning the
RS-485 bus installation. The installations have to be executed in line topology. Cable length and
type have to be considered as well.

Strip the cables as short as possible. It is important to ensure that bare wires, e.g. wire shields do not
come into contact with the mounted PCB (risk of short-circuit).

Recommended cable for field bus: J-Y(St)Y 2x2x0.8 LG (20 AWG) min 300V, loop resistance 73 

/km

(20.8 

/1000 ft).

Recommended cable for local bus (remote mounting): J-Y(St)Y 2x2x0.8 LG (20 AWG), min 300 V.

Use Copper conductors only if the terminal is only for connection to copper wire.

3.1 Wire Connection 

Open the cover.

Insert the field bus cable from above and connect it.

Remove terminal block X4 from BSB, connect cable according to connection diagram fig. 1.

Replug terminal carefully on the BSB at X4.

For remote sensor:

Insert and connect local bus cable at the basic and remote sensor board.

Remove terminal block X7 at sensor board, connect cable acc. to connection diagram fig. 1.

Replug terminals carefully on both sensor boards.

Close cover.

Connecting the 24 V field bus voltage to the local bus terminal X7 can destroy the 

DT6 

Basic Sensor Board completely!

 

4 Commissioning 

Only trained technicians should perform the following when commissioning: 

Check for correct mounting location.

Check that the 

DT6

 board is firmly seated in the housing.

Check if connection is correct according to connection diagram.

Check power voltage.

Install the 

SC2 

Sensor Cartridge(s) if not already installed ex works.

Check 

SC2 

Sensor Cartridge connector for correct engagement.

Address the 

DT6 

Basic Sensor Board (BSB).

Register the 

SC2 

Sensor Cartridge(s) at the 

DT6 

BSB.

Calibrate (if not already factory-calibrated).

Required instruments for commissioning (calibration): 

Service Tool STL6 or

DPT6

 

incl. EasyConfig

 Software 

and 

USB/RS-485 communication set:

Calibration: See 

SC2 

user manual.

INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com

Specifications subject to change without notice. | GASB2_03_E_0220 | USA 200306 | Page 5 of 15

DT6 – UserManual

Содержание PolyGard 2 DT6

Страница 1: ...Transmitters Serial No SB 03 User Manual Version February 2020 en ref optional remote sensor DR6 INTEC Controls 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC inteccontrols c...

Страница 2: ...5 Inspection and Service 9 5 1 Inspection 9 5 2 Service and Calibration 9 6 Troubleshooting 10 6 1 DT6 Basic Sensor Board 10 6 2 SC2 Sensor Cartridge Messages at the Tool Controller 10 7 Technical Dat...

Страница 3: ...local bus level is done via the STL6 Service Tool or with the DPT6 EasyConfig Software which is directly connected to the BSB The cable topology for the RS 485 field bus can be taken from the Guideli...

Страница 4: ...eight depends on the relative density of the gas type to be monitored Choose mounting location of the sensor according to the local regulations Consider ventilation conditions Do not mount the sensor...

Страница 5: ...SB connect cable according to connection diagram fig 1 Replug terminal carefully on the BSB at X4 For remote sensor Insert and connect local bus cable at the basic and remote sensor board Remove termi...

Страница 6: ...as type and defining the measurement range the SC is connected to the input Up to two different SC can be connected at the DT6 with a third to an attached remote DR6 The physical position of the SC do...

Страница 7: ...on you have to activate the mode Special Mode at the BSB only then the calibration menu is enabled During the special mode the BSB doesn t issue alerts Select the Sensor Cartridge to be calibrated by...

Страница 8: ...g the SC connector which leads to an immediate triggering of the error message Disconnect the SC connector from the BSB or the RSB error message will be activated Loosen the locknut Remove used SC Tak...

Страница 9: ...be documented The date for the next maintenance has to be affixed to the sensor 5 1 Inspection Gas sensors should be controlled regularly by a competent person according to EN 45544 4 The following ha...

Страница 10: ...h with registered ones Check SC data registration data for conformity Message at the Tool Controller 24 V DC voltage range 5 V DC voltage range Temp range WatchDog triggered Internal error Replace BSB...

Страница 11: ...B x D 94 x 130 x 57 mm 3 7 x 5 1 x 2 2 in Weight 0 3 kg 0 7 lb Protection class delivery status NEMA 4X IP 65 Installation Wall mounting Wire connection Field bus Local bus for SC Screw type terminal...

Страница 12: ...oard Local Bus only for Remote Sensor Board Field Bus 1 2 3 4 0 VDC 24 VDC Bus_A Bus_B Bus_B Bus_A 24 VDC 0 VDC Analog Output 4 20 mA 0 VDC Field Bus 1 2 3 500 Remove resistor if device is connected X...

Страница 13: ...rd with SC X 2 X 2 X 2 X 2 X 2 X2 X 3 X 3 X 3 SB_03 SB_03 SB_03 SB_03 SB_03 SB_03 X4 4 3 2 1 X4 4 3 2 1 X4 4 3 2 1 X7 3 2 1 X7 3 2 1 X7 3 2 1 X7 3 2 1 X7 3 2 1 X7 3 2 1 Basic Sensor Board Basic Sensor...

Страница 14: ...Mounting Mounting Mounting Mounting 115 mm 130 mm 180 mm D 4 mm INTEC Controls 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC inteccontrols com Specifications subject to chan...

Страница 15: ...de ANSI NFPA70 The equipotential bonding required also e g secondary potential to earth or grounding measures must be carried out in accordance with the respective project requirements It is important...

Отзывы: