PolyGard

®

 O

2

 Transmitter

User Manual - AT-1195 V3

Page 07

5.4  Option Relay Output 

The two relays are activated in dependence of the gas concentration. If the gas concentration exceeds the adjusted 

alarm  threshold,  the  corresponding  relay  switches  on.  If  the  gas  concentration  falls  below  the  threshold  minus 

hysteresis, the relay switches off again. 
The  contact  function  for  relay  2,  NC  (normally  closed)  or  NO  (normally  open),  can  be  selected  via  the  jumper 

NO/NC. See fig 1 and 3. Relay 1 is equipped with a change-over contact. 
Via  the  ModBus  interface  the  two  alarm  thresholds and the hysteresis are freely adjustable at the PC within the 

measuring range. The procedure can be read from the user manual “ModBus Software”. 
The following parameters are factory-set. 
Alarm threshold 1 = Relay 1:   19 (vol. %) 
Alarm threshold 2 = Relay 2:   17 (vol. %) 
Switching hysteresis:      1 (vol. %) 

6   Inspection and Service 

6.1  Inspections 

Inspection, service and calibration of the transmitters should be done by trained technicians and executed at regular 

intervals.  We  therefore  recommend  concluding  a  service  contract  with  IN

TEC

Controls  or  one  of  their 

authorized partners. 

6.2  Calibration 

(See section 5.1 and 5.2) 

At commissioning and at periodic intervals determined by the person responsible for the gas detection

 

system (recommendation every 

12

 months).

After exchange of the sensor

If in case of operational or climatic influences the sensitivity of the sensor falls below 30 % in operation,

calibration will not be possible any more. In this case the sensor has to be changed.

6.3  Exchange of Sensor Element 

Consider static electricity! See point 3. 
Sensor should always be installed without power applied: 

Unplug basic PCB AT1195 carefully from the bottom part.

Unplug old sensor element from the PCB.

Take the new sensor out of the original packing.

Plug the sensor element in the PCB at X7.

Replug the PCB AT1195 in the terminal blocks X4, X5 carefully.

Calibrate according to section 5.

Specifications subject to change without notice. | USA 150109 | Page 7 of 13

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

AT-1195_V3 – UserManual

Polygard® is a registered trademark of MSR | AT-1195_V3_UserManual

Specifications subject to change without notice. | USA 160104 | Page 7 of 13

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

AT-1195 V3 – UserManual

PolyGard

®

 is a registered trademark of MSR-Electronic GmbH | AT-1195_V3_UserManual

INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com

Specifications subject to change without notice. | USA 200211 | Page 7 of 13

AT-1195 V3 – UserManual

Содержание MSR PolyGard AT-1195 V3

Страница 1: ...9 Specifications subject to change without notice USA 150109 Page 1 of 13 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC relevantsolutions com inteccontrols AT 1195_V3 UserMan...

Страница 2: ...7 1 Analog Mode 8 8 Cross sensitivity Data 8 9 Technical Data 9 10 Figures 11 11 Notes and General Information 13 11 1 Intended Product Application 13 11 2 Installers Responsibilities 13 11 3 Maintena...

Страница 3: ...Cathode and anode are electrically contacted therefore due to the oxidation there is an electric current proportional to the oxygen partial pressure This current signal is linear to the oxygen concent...

Страница 4: ...in a duct system with a maximum air velocity of 10 m s 2000 ft min or less Mounting must be performed so that the probe openings are in line with the airflow 3 2 Installation Open the cover Unplug bas...

Страница 5: ...ter to control the gas flow to 150 ml min Calibration adapter with tube Calibration set CONKIT E CH LC See fig 5 Digital voltmeter with range 0 300 mV accuracy 1 Small screwdriver Note Prior to calibr...

Страница 6: ...tage Signal start 2 V 4 mA Control voltage mV 160 mV x test gas concentration O2 vol 40 mV measuring range O2 vol Signal start 0 V 0 mA Control voltage mV 200 mV x test gas concentration O2 vol measur...

Страница 7: ...heir authorized partners 6 2 Calibration See section 5 1 and 5 2 At commissioning and at periodic intervals determined by the person responsible for the gas detection system recommendation every 12 mo...

Страница 8: ...sure tension at X4 No reaction of the output signal in spite of gas concentration Signal Pin 4 not wired correctly Check the wiring 8 Cross sensitivity Data The cross sensitivity can be read from the...

Страница 9: ...oof Physical Enclosure2 Stainless steel V2A Enclosure colour2 Natural brushed Dimensions2 H x W x D 113 x 135 x 45 mm 5 35 x 4 5 x 1 8 in Weight2 Approx 0 5 kg 1 1 Ibs Protection class2 IP 55 Mounting...

Страница 10: ...rature 40 C Power supply 18 28 VDC AC Power consumption 0 2 A 5 VA Analog input Only for RS 485 mode 4 20 mA overload and short circuit proof input Power supply for external transmitter 24 VDC max 50...

Страница 11: ...3 0 VDC 4 20 mA 24 VDC X4 1 2 3 4 5 6 7 0 VDC 24 VDC_Out 24 VDC Analog_Out 4 20 mA_Inp Bus_A Bus_B X5 R1 2 3 4 5 1 R2 Option Relay NO NC Specifications subject to change without notice USA 150109 Page...

Страница 12: ...Relay R2 NO NC NC NO Option Manual Calibration Option Manual Addressing Position 4 3 2 1 5 4 3 2 1 1 2 3 4 5 6 7 X5 X4 Calibration adapter Fig 5 Type CONKIT E CH LC Specifications subject to change wi...

Страница 13: ...ent in the field may be implemented by a qualified technician and with the appropriate tools Alternatively the easily removable plug in transmitter card with the sensor may be returned for service to...

Отзывы: