PolyGard

®

 O

2

 Transmitter

User Manual - AT-1195 V3

Page 05

4.1  Wiring Connection

  

Open the cover. Unplug basic PCB carefully from terminal blocks X4 and X5.

Insert the cable and connect cable leads to terminal blocks. See fig. 1 and 2.

Replug the PCB in the terminal blocks X4, X5. Replace the cover.

5  Commissioning 

Consider commissioning instructions at any exchange of the sensor elements. 
Only trained technicians should perform the following: 

Check mounting location.

Select output signal form: Current or voltage, and starting point 0 or 20%. See fig. 4.

Check power voltage.

Check PCB AT03 for correct mounting at X4 and X5.

Check the sensor for proper mounting at the connectors X3 of the PCB AT-1195 V3.

Calibrate the transmitter (if not already factory-calibrated).

Required instruments for commissioning (calibration) of the transmitter: 

Test gas bottle with test gas O

2

 in the range of 

20.8% vol O

2

 in Nitrogen or Air Balance.

Gas pressure regulator with flow meter to control the gas flow to 150 ml/min.

Calibration adapter with tube. Calibration set 

CONKIT-E/CH-LC

. See fig. 5.

Digital voltmeter with range 0 – 300 mV, accuracy 1%.

Small screwdriver.

Note: 

Prior to calibration the sensor must be connected to the power supply and fully stabilised for at least 1 hour without 

interruption. 
Please observe proper handling procedures for test gas bottles! 

5.1  Calibration 

Depending on the version and the control mode there are two different possibilities to calibrate the transmitter: 

Manual calibration 

Manual calibration is only possible if the transmitter is equipped with the push-button “Zero” and the potentiometer 

“Gain” (= version for manual calibration). 

Specifications subject to change without notice. | USA 150109 | Page 5 of 13

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

AT-1195_V3 – UserManual

Polygard® is a registered trademark of MSR | AT-1195_V3_UserManual

Specifications subject to change without notice. | USA 160104 | Page 5 of 13

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

AT-1195 V3 – UserManual

PolyGard

®

 is a registered trademark of MSR-Electronic GmbH | AT-1195_V3_UserManual

INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com

Specifications subject to change without notice. | USA 200211 | Page 5 of 13

AT-1195 V3 – UserManual

Содержание MSR PolyGard AT-1195 V3

Страница 1: ...9 Specifications subject to change without notice USA 150109 Page 1 of 13 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC relevantsolutions com inteccontrols AT 1195_V3 UserMan...

Страница 2: ...7 1 Analog Mode 8 8 Cross sensitivity Data 8 9 Technical Data 9 10 Figures 11 11 Notes and General Information 13 11 1 Intended Product Application 13 11 2 Installers Responsibilities 13 11 3 Maintena...

Страница 3: ...Cathode and anode are electrically contacted therefore due to the oxidation there is an electric current proportional to the oxygen partial pressure This current signal is linear to the oxygen concent...

Страница 4: ...in a duct system with a maximum air velocity of 10 m s 2000 ft min or less Mounting must be performed so that the probe openings are in line with the airflow 3 2 Installation Open the cover Unplug bas...

Страница 5: ...ter to control the gas flow to 150 ml min Calibration adapter with tube Calibration set CONKIT E CH LC See fig 5 Digital voltmeter with range 0 300 mV accuracy 1 Small screwdriver Note Prior to calibr...

Страница 6: ...tage Signal start 2 V 4 mA Control voltage mV 160 mV x test gas concentration O2 vol 40 mV measuring range O2 vol Signal start 0 V 0 mA Control voltage mV 200 mV x test gas concentration O2 vol measur...

Страница 7: ...heir authorized partners 6 2 Calibration See section 5 1 and 5 2 At commissioning and at periodic intervals determined by the person responsible for the gas detection system recommendation every 12 mo...

Страница 8: ...sure tension at X4 No reaction of the output signal in spite of gas concentration Signal Pin 4 not wired correctly Check the wiring 8 Cross sensitivity Data The cross sensitivity can be read from the...

Страница 9: ...oof Physical Enclosure2 Stainless steel V2A Enclosure colour2 Natural brushed Dimensions2 H x W x D 113 x 135 x 45 mm 5 35 x 4 5 x 1 8 in Weight2 Approx 0 5 kg 1 1 Ibs Protection class2 IP 55 Mounting...

Страница 10: ...rature 40 C Power supply 18 28 VDC AC Power consumption 0 2 A 5 VA Analog input Only for RS 485 mode 4 20 mA overload and short circuit proof input Power supply for external transmitter 24 VDC max 50...

Страница 11: ...3 0 VDC 4 20 mA 24 VDC X4 1 2 3 4 5 6 7 0 VDC 24 VDC_Out 24 VDC Analog_Out 4 20 mA_Inp Bus_A Bus_B X5 R1 2 3 4 5 1 R2 Option Relay NO NC Specifications subject to change without notice USA 150109 Page...

Страница 12: ...Relay R2 NO NC NC NO Option Manual Calibration Option Manual Addressing Position 4 3 2 1 5 4 3 2 1 1 2 3 4 5 6 7 X5 X4 Calibration adapter Fig 5 Type CONKIT E CH LC Specifications subject to change wi...

Страница 13: ...ent in the field may be implemented by a qualified technician and with the appropriate tools Alternatively the easily removable plug in transmitter card with the sensor may be returned for service to...

Отзывы: