Service Menu
Function Block Number 20
20.
- TRANSMITTER SETTINGS -
To view or alter the Transmitter Settings selection press Enter when the TRANSMITTER
SETTINGS function block is displayed. In this function block use Enter to set each sub-
menu and return to the Tx Settings menu.
The Transmitter Settings are used to set functions related to the transmitter itself. These
include Cold Start, LCD Contrast, Unit Information, Change Password, Access code for
calibration, Hardware fitted Menu timeout, Date & Time and Reset Totaliser 2.
Cold Start: No (or Yes) is used to reset the 6004MF to default factory settings. This may
be used due to requiring a new starting point for programming or if an old unit is being
used on a new system and you want to clear all old programming data. Please note that
all your existing programming will be lost and you will have to re-enter all values and re-
commission the system. Note: You can also cold start by holding the enter key whilst
powering up.
Contrast: use side arrow for LCD screen contrast bar display.
Unit Information: use side arrow to display Model, Version and Serial number.
Change Password: use side arrow to display Change Password menu.
Access Code: use side arrow to display Access Code. Key in the Password to enter the
calibration menu and follow instructions for calibrating internal mV, Excitation Voltage, mA
outputs and Voltage outputs.
Hardware Options: use side arrow to List Hardware options fitted. These are Setpoints: 1-
6, SD card: No (or yes), GPS: No (or Yes).
Menu Timeout: No (or Yes) (Use No during commissioning)
Date & Time: use side arrow to display Date/Time menu. Date is YYYY:MM:DD, Time is
displayed as a 24 hour clock HH:MM:SS. Move highlight down and key in the values.
Press Enter to set and return to Tx Settings menu.
Reset Totaliser 2: No (or Yes) Caution! This is the 'non-resettable' totaliser. Press Enter to
reset and return to the Tx Settings menu.
When you have completed all changes to the block press Enter . This will move on to the
next block, in this case SETPOINT VALUES at the beginning of the service menu.
Pressing Clear will then take you to the Service Menu block and Clear again to RUN.