INSTEON KeypadLinc Dimmer User’s Guide
Page 8 of 39
Installing KeypadLinc Dimmer
1. For best INSTEON Network performance, be sure you have properly installed at least two Access
Point Modules.
2. At the circuit breaker or fuse panel, disconnect the power for
all
of the circuits in the switch junction
box. Verify that power is off by trying to turn on the lights controlled by the switches.
3. Remove the faceplate from the switch junction box, and then unscrew the switch you are replacing
and pull it out from the junction box.
4. Disconnect the wires from the switch you are replacing. If the wires cannot be detached by
unscrewing them, cut the wires where they enter the switch, then strip ½” of insulation off the ends.
5. If you are installing KeypadLinc Dimmer into a standard
two-way circuit
(where only one switch
controls the load), follow the diagram below to identify and connect the LINE, LOAD, NEUTRAL, and
GROUND wires. If the colors of the wires do not match the diagram, be sure you have identified the
wires correctly before connecting them.
6. If you are installing KeypadLinc Dimmer into a
multi-way circuit
(where more than one switch
controls the same load), follow the instructions in the section titled
Installing KeypadLinc Dimmer in a
Multi-Way Circuit
to identify and connect the LINE, TRAVELER, NEUTRAL, and GROUND wires.
7. After you have connected all of the wires, ensure that all of the wire connectors are firmly attached
and that there is no exposed copper except for the GROUND wire.
8. Orient KeypadLinc Dimmer with the SET button on bottom, gently place it into the junction box, and
then screw it into place.
9. Turn the circuit breaker back on or re-install the fuse.
10. After the SET button illuminates, verify KeypadLinc Dimmer is working properly by turning the light on
and off.
11. Reinstall the trim plate.
NOTE
The NEUTRAL wire will not
normally be connected to the
switch you are replacing. If there is
no NEUTRAL wire in the junction
box, please consult an electrician
or call
SmartHome Tech Support
800-SMARTHOME
Main Panel
120 VAC
LINE
Usually Black
LOAD
Usually Red, Blue or Black
NEUTRAL
Usually White
GROUND
Bare Copper
LINE
Black
NEUTRAL
White
GROUND
Bare Copper
LOAD
Red
Light
Fixture(s)