20
●
Front and rear doors—If the 42U rack includes closing front and rear doors, you must
allow 5,350 sq cm (830 sq in) of holes evenly distributed from top to bottom to permit
adequate airflow (equivalent to the required 64 percent open area for ventilation).
●
Side—The clearance between the installed rack component and the side panels of the
rack must be a minimum of 7 cm (2.75 in).
5.1.2 Temperature Requirements
To ensure continued safe and reliable equipment operation, install or position the system in
a well-ventilated, climate-controlled environment.
The maximum recommended ambient operating temperature (TMRA) for most server
products is 35°C (95°F). The temperature in the room where the rack is located must not
exceed 35°C (95°F).
CAUTION:
To reduce the risk of damage to the equipment when installing third-party
options:
●
Do not permit optional equipment to impede airflow around the server or to increase the
internal rack temperature beyond the maximum allowable limits.
●
Do not exceed the manufacturer’s TMRA.
5.1.3 Power Requirements
Installation of this equipment must comply with local and regional electrical regulations
governing the installation of information technology equipment by licensed electricians. This
equipment is designed to operate in installations covered by NFPA 70, 1999 Edition (National
Electric Code) and NFPA-75, 1992 (code for Protection of Electronic server/Data Processing
Equipment). For electrical power ratings on options, refer to the product rating label or the
user documentation supplied with that option.
WARNING:
To reduce the risk of personal injury, fire, or damage to the equipment, do not
overload the AC supply branch circuit that provides power to the rack. Consult the electrical
authority having jurisdiction over wiring and installation requirements of your facility.
Содержание NF5288M5
Страница 1: ...Inspur Yitian Supercomputer User Manual NF5288M5 ...
Страница 24: ...18 3 Remove the access panel 4 If there are cables under the air baffle pull them out 5 Remove the air baffle ...
Страница 82: ...76 8 4 Storage Select Storage on the navigation tree to open the storage interface At present the storage ...
Страница 86: ...80 ...
Страница 88: ...82 ...
Страница 89: ...83 BMC Settings ...
Страница 91: ...85 BMC Settings One key collect log One key collect log ...
Страница 92: ...86 ...
Страница 95: ...89 BMC Settings Restore factory defaults To restore BMC s configuration to factory state ...
Страница 96: ...90 ...