66
INOVANCE TECHNOLOGY EUROPE GmbH
MD800 EtherCAT Starting Guide_EN_v1.1_20211109.docx
When the inverter alarms E27.00, the inverter will process according to the set value of F9-51
(fault protection action selection).
13
User-defined fault 2
When the inverter alarms E28.00, the inverter will process according to the set value of F9-51
(fault protection action selection).
14-17
Multi-segment command terminal 1~4
Through 16 states of these four terminals, 16 speeds or 16 other commands can be set.
18-19
Acceleration/deceleration selection terminal 1~2
Through the 4 states of the two terminals, 4 kinds of acceleration and deceleration time can
be selected.
20
Prohibition of acceleration and deceleration
The inverter maintains the current running frequency (except for the stop command), and is
not affected by changes in the external input frequency.
21
Command source switching terminal 1
When the run command is set through the terminal (F0-02=1), the terminal selects this
function to switch between terminal control and keyboard control;
When setting the running command (F0-02=2), the terminal selects this function to switch
between communication control and keyboard control.
22
Command source switching terminal 2
It is used to switch between the terminal and the communication setting operation
command. If the terminal is used to control the running command, the system will switch off
when the terminal of this function is selected.
Change to communication control; if the communication control operation command is used,
the system will switch to terminal control when the terminal that selects this function is
valid.
23
Frequency command switching
Used to switch between different frequency command input methods. According to the
setting of F0-07 (frequency command superposition selection), the
Switch.
24
Frequency source X and preset frequency switch
The main frequency is switched to the preset frequency (F0-08).
25
Frequency source Y and preset frequency switch
The auxiliary frequency is switched to the preset frequency (F0-08).
26
Frequency modification enable
If the terminal is valid, it is allowed to modify the frequency; if the terminal is invalid, it is
forbidden to modify the frequency.
27
Counter input
In the counting technology function, the terminal selects this function to input counting
pulse.
28
Counter reset
In the counting technology function, the terminal selects this function to clear the counter
status.
29
Length count input
In the fixed-length technology function, the terminal selects this function to input the length
count.
30
Length reset
Use this terminal function in the fixed-length technology function to clear the length.
31
PID pause
PID is temporarily invalid, the inverter maintains the current output frequency and no longer
performs PID adjustment of the frequency source.
32
PID integration suspended
The integral adjustment function of PID is suspended, but the proportional adjustment and
differential adjustment functions of PID are still valid.
Содержание EtherCAT MD800
Страница 1: ...2021 INOVANCE TECHNOLOGY EUROPE V1 1 MD800 EtherCAT Starting Guide...
Страница 47: ...46 INOVANCE TECHNOLOGY EUROPE GmbH MD800 EtherCAT Starting Guide_EN_v1 1_20211109 docx...
Страница 50: ...49 INOVANCE TECHNOLOGY EUROPE GmbH MD800 EtherCAT Starting Guide_EN_v1 1_20211109 docx...
Страница 53: ...52 INOVANCE TECHNOLOGY EUROPE GmbH MD800 EtherCAT Starting Guide_EN_v1 1_20211109 docx Click OK...