Document Name : OIM AI-7X42 (Ver 1.2) Page 3 of 6

User can change the SP value using UP/ DOWN keys. Holding the key
will change the value at a faster rate. Press SET key to store the desired
value and move on to the next parameter.

0 C

o

LSPL ~ HSPL

CONTROL

SET POINT

PARA

METER

RANGE

DESCRIPTION

DEFAULT

DISPLAY

This parameter will be prompted if Output 2 is configured as...

Either absolute auxiliary control or as an alarm (High/Low) mode.
Either deviation auxiliary control or as a deviation alarm mode.
As a band alarm.

Î

Ï

Ð

LSPL ~ HSPL

-99 to 99 °C

2 to 99 °C

SET

POINT2

0 C

o

POWER UP:

At power on, following sequence will be prompted on the display for 1 sec. till it reaches to Home

display mode.

MODEL

VERSION

HOME

PV

VERSION

HOME

PV

PROGRAMMING

USER LIST :

To access the user list Press & Release SET key once.

(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)

(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)

CONTROL LIST :

SET & DOWN key simultaneously

To enter in this mode press

for 3 sec. User can then set

the control parameters.

PARA

METER

RANGE

DESCRIPTION

DEFAULT

DISPLAY

Proportional

Band

0.5

to

99.9°C

This parameter will be prompted only if selected control action is PID. It
sets bandwidth over which the output power is adjusted depending upon
the error (SV-PV). The value of this parameter is automatically set by Auto
tune function.

5.0 C

o

Integral

Time

0

to

9999 Sec.

This parameter will be prompted only if selected control action is PID. It
sets the time taken by PID algorithm to remove steady state error. Value
of this parameter is automatically set by Auto Tune function. If set to ‘0’,
this function will be disabled.

0 Sec.

Derivative

Time

0

to

300 Sec.

This parameter will be prompted only if selected control action is PID. It
defines how strongly the Controller will react to the rate of change of PV.
Value of this parameter is automatically set by Auto Tune function. If set to
‘0’, this function will be disabled.

0 Sec.

Cycle

Time

0.5

to

100.0 Sec.

This parameter will be prompted only if selected control action is PID.
User can set this value based on process being controlled & type of
Output being selected. For Relay O/P, cycle time should be more 12sec &
for SSR O/P, cycle time should be less than 10sec.

16.0 Sec.

Delay 1

0

to

500 Sec.

This parameter will be prompted only if selected control action is ON-OFF.
It sets the main output restart time where O/P once turned OFF will turn
ON only after restart time, regardless difference between PV & SP in Heat
or Cool mode. If set to '0', O/P will be switched without delay. Also, Delay
will be applicable in case of every power ON.

120 Sec.

This parameter will be prompted only it selected control mode for output2
is auxiliary control or an alarm. The value of this parameter sets the dead
band between on and off switching of output load.

Hysterisis 2

1 to 25 C

o

2 C

o

0

to

500 Sec.

This parameter will be prompted only if output 2 is configured as an
Auxiliary control output. In this mode, O/P once turned OFF will restart
only after set time regardless of the difference between PV and SP2. Time
delay is settable up to 500 seconds. If time delay is set to 0, there is no
delay between output switching.

0 Sec.

Delay 2

Control

Hysterisis

1 to 25 C

o

This parameter will be prompted only if selected control action is ON-OFF.
It sets the dead band between ON & OFF switching of the Output. Larger
value of hysterisis minimize the number of ON-OFF operation of load.
This increases life of actuators like contactors but also produces large
errors (between PV & SV).

2°C

0

1 ~ 9999

Set this parameter to 15 (Default LOCK CODE) to access Control List.
User has a choice to set different Lock Code via USER LOCK CODE in
Config. List.

LOCK
CODE

100 %.

OUTPUT

POWER

LIMIT

0.0 %

TO

100.0 %

This parameter will be prompted only if selected control action is PID. This
parameter will decide the maximum output power in % applied to the load

TUNE

OFFSET

50 %

to

100 %

100 %.

This parameter will be prompted only if selected control action is PID. This
parameter allows the User to carry out Auto Tuning function below the set
point. (If Tune offset is 50 % tuning will be carried out at 50 % of the set
point and if 100 % tuning will be carried out at 100% of the set point.)

.