background image

PARA

METER

DESCRIPTION

DEFAULT

DISPLAY

DEVIATION

ALARM

TYPE

Deviation Alarm : OP2 activates when PV exceeds SP1 ± set deviation value.

Band Alarm : OP2 activates when PV falls outside the band w.r.t. SP1 in either
direction.

Low Alarm : OP2 activates when PV<SP2.

High Alarm : OP2 activates when PV>SP2.

(Direct acting)

(Direct acting)

OUTPUT-2 ON

OUTPUT-2 OFF

SP2

PV

(Direct acting)

SP2

OUTPUT-2 OFF

OUTPUT-2 ON

PV

(Reverse acting)

OUTPUT-2 OFF

OUTPUT-2 ON

SP2

PV

(Direct acting)

SP2

OUTPUT-2 ON

OUTPUT-2 OFF

PV

(Reverse acting)

(Reverse acting)

(Reverse acting)

OUTPUT ON

SP2

PV

SP1

OUTPUT OFF

OUTPUT ON

OUTPUT ON

PV

SP1

SP2

SP2

OUTPUT OFF

OUTPUT OFF

OUTPUT OFF

PV

SP1

SP2

SP2

OUTPUT ON

OUTPUT OFF

SP2

PV

SP1

OUTPUT ON

Abs

This parameter will be prompted only if OUTPUT 2 is selected as an Auxiliary
control output. In this mode, User can set SP2 value independently. The instrument
works as 2-Set point Controller.

This parameter will be prompted only if OUTPUT 2 is selected as an Auxiliary
control output. In this mode, User can set SP2 value which is always related to SP.
User can set SP2 value with the deviation of ± 99°C w.r.t SP.

OUTPUT 2

MODE

SET

POINT 2

DSBL

This parameter allows the user to edit SP2 parameter in the USER list. Setting this
parameter to ENBL will allow the user to view as well edit the SP2 parameter in
USER list.

This parameter allows the user to edit SP2 parameter in the USER list. Setting this
parameter to DSBL will not allow the user to view as well edit the SP2 parameter in
USER list.

5

Document Name : OIM AI-7X42 (Ver 1.2) Page 5 of 6

PARA

METER

DESCRIPTION

DEFAULT

DISPLAY

PARA

METER

DESCRIPTION

DEFAULT

DISPLAY

15

Default USER LOCK CODE is 15 to access Control & Configuration List.
User has a choice to set its own USER LOCK CODE between 1 to 9999, this is to
prevent unauthorized access of Control & Configuration List.

USER
LOCK
CODE

TABLE 3 :

Below listed options will appear only if OP2 is selected as an Auxiliary control mode.

(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)

Heat

User can select heating logic in which OP2 will remain ON till PV < SP2.
(PV increases when output2 is ON.)

User can select cooling logic in which OP2 will remain OFF till PV < SP2.
(PV decreases when output2 is ON.)

OUTPUT 2

LOGIC

TABLE 4 :

Below listed parameters will appear only if OUTPUT 2 is selected as ALARM mode. In ALARM

mode, Controller continuously compares PV with either SP (for Deviation or Band alarm) or an independent
ALARM SP2 (for process high and process low Alarm). Alarm will occur when PV falls outside the set Alarm
limits. Also, OP2 will energize or de-energize under Alarm condition as per the Alarm logic(AL.LG) selected.
HYS2 in Control list decides when to switch OFF the Alarm. Instrument supports four types of Alarm as
described below : -

(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)

Отзывы: