8.5.9 Compressor preheating functions
----Preheating permitting condition:
If T4(outdoor ambient temperature)
<
3
℃
and newly powered on or if T4
<
3
℃
and compressor has
stopped for over 3 hours, the compressor heating cable will work.
----Preheating mode:
A weak current flow through the coil of compressor from the wiring terminal of compressor, then the
compressor is heated without operation.
----Preheating release condition:
If T4
>
5
℃
or the compressor starts running, preheating function will stop.
8.5.10 Compressor crankcase heater
When T4<3
℃
and the compressor is not running, the crankcase heater will be active.
When T4
≧
5
℃
or the compressor starts up, the crankcase heater will stop work.