8.5.4 Compressor current limit protection
If the compressor current exceeds the current limit value for 10 seconds, the compressor frequency will be
limited as below table.
Cooling mode:
Current frequency(Hz)
Current limit value(A)
Frequency limit
COOL_F10
ICOOLLMT6
Decrease the frequency to COOL_F4 and run at
COOL_F4 for 3 minutes.
After that, the frequency will be adjusted according to the
capacity demand and rise to the upper level every 3
minutes
(When the frequency>COOL_F4 via capacity demand).
COOL_F9
ICOOLLMT5
COOL_F8
ICOOLLMT4
COOL_F7
ICOOLLMT3
COOL_F6
ICOOLLMT2
COOL_F5
ICOOLLMT1
If the current frequency is lower than COOL_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>ICOOL,the AC will display the failure for 30 seconds and stop. The AC will restart 3
minutes later.
Heating mode:
Current frequency(Hz)
Current limit value(A)
Frequency limit
HEAT_F12
IHEATLMT8
Decrease the frequency to HEAT_F4 and run at HEAT_F4
for 3 minutes.
After that, the frequency will be adjusted according to the
capacity demand and rise to the upper level every 3
minutes
(When the frequency>Heat_F4 via capacity demand).
HEAT_F11
IHEATLMT7
HEAT_F10
IHEATLMT6
HEAT_F9
IHEATLMT5
HEAT_F8
IHEATLMT4
HEAT_F7
IHEATLMT3
HEAT_F6
IHEATLMT2
HEAT_F5
IHEATLMT1
If the current frequency is lower than HEAT_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>IHEAT,the AC will display the failure for 30 seconds and stop. The AC will restart 3
minutes later.
8.5.5 Indoor / outdoor units communication protection
If the indoor units can not receive the feedback signal from the outdoor units for 2 minutes, the AC will stop
and display the failure.
8.5.6 High condenser coil temp. protection.
When T3>65
℃
for 3 seconds, the compressor will stop while the indoor fan and outdoor fan will continue.
When T3<52
℃
, the protection will release and the compressor will restart after 3 minutes.
8.5.7 Outdoor unit anti-freezing protection
When T2B<0
℃
for 250 seconds, the indoor unit capacity demand will be zero and resume to normal when
T2B>10
℃
.
8.5.8 Oil return
Running rules:
1.If the compressor frequency keeps lower than
RECOILINFRE
for 2 hours, the AC will rise the frequency
to
RECOILINFRE
for 3 min and then resume to former frequency.
2.During the oil return process, the EXV and indoor units keep the current running mode, the frequency will
not be limited by the compressor discharge temp. and the current.