Troubleshooting:
Malfunction of ODU memory chip
error
Replace the outdoor
mainboard
3.4.9 “H4” Overload
Error display:
ODU mainboard LED displayer
Error judgment condition and method:
When condensing pressure is higher than the protection value, system will report overload protection.
Possible reason:
Cooling ODU heat exchanger is blocked or heat exchange is bad.
Heating IDU heat exchanger is blocked or heat exchange is bad.
Operating temperature is too high.
System charging quantity is too much.