background image

[5.4.3] Modifications of Sampling Tubes

There  may  be  applications  where  duct  widths  are  not  what  is 
specified  for  the  installation.  In  such  cases,  it  is  permissible  to 
modify a sampling tube that is longer than necessary to span the 
duct width.

NOTE:

 This procedure should only be used as a temporary fix. It 

is not intended as a permanent substitute for ordering the correct 
length tubes.

[5.4.4] Alternate Method of Sampling Tube Installation

The detector arrangement can also incorporate the remote mount-
ing of the sampling tube and/or exhaust tube. In this case both 
the detector, sampling tube and exhaust tube (if included) should 
be rigidly mounted to withstand the pressure and resonant vibra-
tions  caused  by  the  air  velocity.  The  location  of  the  detector’s 
sampling tube should be such that there is uniform airflow in the 
cross section area. 
An air tight connection shall be made between the sampling tube, 
exhaust tube and their corresponding ports on the detector hous-
ing. Upon selection of location in the system, pressure differential 
across  the  sampling  and  exhaust  ports  in  the  detector  housing 
shall  be  verified  to  be  within  the  allowable  range  of  the  detec-
tor.  This  is  accomplished  by  measuring  the  pressure  difference 
between the inlet and outlet ports on the detector housing using a 
manometer as described in Section 6 of this manual.
Use  a  0.193-inch  diameter  (#11)  drill  and  add  the  appropriate 
number  of  holes  so  that  the  total  number  of  holes  exposed  to 
the air flow in the duct is 10 to 12. Space the additional holes as 
evenly as possible over the length of the tube.

[5.5] Install The Filters 

To install the sampling tube filters, simply push the filters into the 
sampling and exhaust tube holes, as shown in 

Figure 6

. If a metal 

sampling tube is used, install the filters over the tube ends.

Figure 6. Sampling tube filter installation:

CAUTION

Filters require periodic cleaning or replacement, depending on the 
amount of dust and dirt accumulated. Visually inspect the filters 
at least quarterly; inspect them more often if the dust accumula-
tion  warrants  it.  See  Section  [6]  for  more  information.  Replace-
ment filters can be ordered from System Sensor, 3825 Ohio Ave., St. 
Charles, IL 60174. (Exhaust tube/intake tube filter P/N F36-09-11).

[5.6] Field Wiring Installation Guidelines

All wiring must be installed in compliance with the National Elec-
trical  Code  and  the  local  codes  having  jurisdiction.  Proper  wire 
gauges  should  be  used.  The  conductors  used  to  connect  smoke 
detectors to control panels and accessory devices should be color-
coded to prevent wiring mistakes. Improper connections can pre-
vent a system from responding properly in the event of a fire.

For  signal  wiring,  (the  wiring  between  interconnected  detectors 
or from detectors to auxiliary devices), it is usually recommended 
that single conductor wire be no smaller than 18 gauge. The duct 
smoke detector terminals accommodate wire sizes up to 12 gauge. 
The last foot of conduit should be flexible conduit (available in 
electrical supply houses), which facilitates easier installation and 
puts less strain on the conduit holes in the housing. Solid conduit 
connections may be used if desired.
Smoke  detectors  and  alarm  system  control  panels  have  specifi-
cations  for  allowable  loop  resistance.  Consult  the  control  panel 
manufacturer’s specifications for the total loop resistance allowed 
for  the  particular  model  control  panel  being  used  before  wiring 
the detector loop. 

Wiring Instructions 

The  DH100ACDCI  detectors  are  designed  for  easy  wiring.  The 
housing  provides  a  terminal  strip  with  clamping  plates.  Wiring 
connections  are  made  by  stripping  about  3⁄8-inch  of  insulation 
from the end of the wire, sliding the bare end under the plate, and 
tightening the clamping plate screw. 

[5.7] Perform Detector Check 

1.  Perform STANDBY AND TROUBLE TEST per Section [6.2.1].
2.   Perform  MAGNET  TEST  per  Section  [6.2.2.1].  The  RTS451 

test of Section [6.2.2.2] may substitute for this requirement. 

3.  Perform AIR FLOW TEST per Section [6.1.1].
4.  Perform SMOKE RESPONSE TEST per Section [6.1.2].
5.  Perform SENSITIVITY TEST per Section [6.2.3].

[5.8] Install The Cover 

Install the cover using the six screws that are captured in the hous-
ing  cover.  Be  certain  filters  are  installed  as  specified  in  Section 
[5.5]. Make sure that the cover fits into the base groove and that 
all gaskets are in their proper positions. Tighten the six screws.

[6] Duct Smoke Detector Maintenance And Test Procedures

Test and maintain duct smoke detectors as recommended in NFPA 
72. The tests contained in this manual were devised to assist main-
tenance personnel in verification of proper detector operation. 
Before  conducting  these  tests,  notify  the  proper  authorities  that 
the smoke detection system will be temporarily out of service. Dis-
able the zone or system under test to prevent unwanted alarms.

[6.1] Smoke Entry Tests
[6.1.1] Air Flow

To  verify  sufficient  sampling  of  ducted  air,  use  a  manometer  to 
measure the differential pressure created from air flow across the 
sampling tubes. The pressure should measure no less than 0.03 
inches of water and no greater than 1.4 inches of water. The air 
handler must be operating for this test.

[6.1.2] Smoke Response

To determine if smoke is capable of entering the sensing cham-
ber, visually identify any obstructions. Plug the exhaust and sam-
pling tube holes to prevent ducted air from carrying smoke away 
from the detector head, then blow smoke such as cigarette, cotton 
wick, or punk directly at the head to cause an alarm. REMEMBER 
TO REMOVE THE PLUGS AFTER THIS TEST, OR THE DETECTOR 
WILL NOT FUNCTION PROPERLY.

D100-68-00 

I56-1684-007R

H0400-00

Содержание DH100ACDCI

Страница 1: ...hut down These detectors are not designed for 2 wire applications For testing the alarm can be enabled by a magnet activated test switch or by the optional remote test station The duct smoke detector latches into alarm state when an alarm occurs A green LED flashes to indicate power a red LED signals local alarm indication and optional accessories offer a variety of annuncia tion capabilities The ...

Страница 2: ...les as indi cated in Figure 4 D100 68 00 2 I56 1684 007R 4 Figure 1 Exploded View Of Duct Smoke Detector Components FOAM GASKETS PLASTIC SAMPLING TUBE CONDUIT HOLES DETECTOR HOUSING TERMINAL STRIP DETECTOR COVER SAMPLING TUBE FILTERS PLASTIC SAMPLING TUBE SELF TAPPING SCREW POWER BOARD DETECTOR BOARD COVER MOUNTING SCREWS H0401 00 H0110 00 5 Installation Sequence 5 1 Verify Duct Air Flow Direction...

Страница 3: ...t the end opposite the duct smoke detector Figure 5 Tube mounting configurations with varying air flow direction AIR FLOW DIRECTION DETECTOR HOUSING DOTS INDICATE POSITION OF SAMPLING TUBE HOLES AIR FLOW DIRECTION DETECTOR HOUSING SAMPLING TUBE EXHAUST TUBE AIR FLOW DIRECTION EXHAUST TUBE SAMPLING TUBE SAMPLING TUBE EXHAUST TUBE DETECTOR HOUSING AIR FLOW DIRECTION DETECTOR HOUSING A B C D HORIZONT...

Страница 4: ... between interconnected detectors or from detectors to auxiliary devices it is usually recommended that single conductor wire be no smaller than 18 gauge The duct smoke detector terminals accommodate wire sizes up to 12 gauge The last foot of conduit should be flexible conduit available in electrical supply houses which facilitates easier installation and puts less strain on the conduit holes in t...

Страница 5: ... RTS451KEY is not required when these accessories are used with the DH100ACDCI detectors The functionality of the magnetic coil has been designed into the circuitry of the new In novair duct smoke detectors 6 2 2 3 SSK451 Multi Signaling Accessory The System Sensor SSK451 Multi Signaling accessory combines a sounder feature with a key activated test and reset function Green amber and red LEDs prov...

Страница 6: ...S ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR AUX CONTACT RATINGS 10A 30 VDC RESISTIVE 10A 250 VAC 100mA MINIMUM 5 VDC 1 4 HP 240 VAC 1 8 HP 120 VAC NOT INTENDED FOR CONNECTION TO CONTROL PANELS TROUBLE CONTACT RATING 2 0 A 30 VDC resistive 2 0 A 125 VAC resistive 120 VAC CAUTION Do not loop wire under termin...

Страница 7: ...ination of accessories may be used such that the given accessory loads are 60 mA or less in the standby state 110 mA or less in the alarm state TROUBLE n a n a n a n a 9mA Max D100 68 00 7 I56 1684 007R Figure 11 Wiring diagrams for optional accessories H0402 01 15 ALARM SIGNAL 3 14 2 RESET 11 TEST 20 AUX POWER 19 AUX POWER SSK451 FIELD INSTALLED JUMPER FOR TEMPORAL PATTERN SUPERVISORY CONTACT NO ...

Страница 8: ...60 Hz CURRENT REQUIREMENTS USING NO ACCESSORIES Max standby current 15 mA 35 mA RMS 25 mA RMS 15 mA RMS Max alarm current 70 mA 125 mA RMS 35 mA RMS 25 mA RMS CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contacts DPDT 10A 30 VDC 10A 250 VAC 1 4 HP 240 VAC 1 8 HP 120 VAC Trouble contacts SPDT 2 0A 30 VDC resistive 2 0A 125 VAC resistive Note Alarm auxiliary c...

Отзывы: