background image

Table 1. Sampling tubes recommended for different 
duct widths:

 

Outside Duct Width 

Sampling Tube Recommended*

 

1 to 2 ft. 

ST-1.5 

 

 

 

2 to 4 ft. 

ST-3

 

4 to 8 ft. 

ST-5

 

8 to 12 ft. 

ST-10

*Must extend a minimum of two-thirds the duct width.

[5.4.1] Installation For Ducts Greater Than 1

1

2

 Feet 

But Less Than 8 Feet Wide

1.   

If the tube is longer than the width of the air duct

, drill a 3⁄4” 

hole  in  the  duct  opposite  the  hole  already  cut  for  the  sam-
pling tube. Make sure the hole is 1” to 2” below the inlet hole 
on the opposite side of the duct to allow moisture drainage 
away from the detector. 

If the tube is shorter than the width 

of the air duct

, install the end cap into the sampling tube as 

shown in 

Figure 4

. Sampling tubes over 3 ft. long must be 

supported at the end opposite the duct smoke detector.

2.   Slide the tube into the housing bushing that meets the air flow 

first. Position the tube so that the arrows point into the air flow. 

3.   Secure  the  tube  flange  to  the  housing  bushing  with  two  #6 

self-tapping screws.

4.   For  tubes  longer  than  the  width  of  the  air  duct,  the  tube 

should extend out of the opposite side of the duct. If there 
are more than 2 holes in the section of the tube extending 
out of the duct, select a different length using Table 1. Oth-
erwise, trim the end of the tube protruding through the duct 
so  that  1”  to  2”  of  the  tube  extend  outside  the  duct.  Plug 
this end with the end cap and tape closed any holes in the 
protruding section of the tube. Be sure to seal the duct where 
the tube protrudes.

NOTE:

 The sampling tube end cap is critical to the proper opera-

tion of the duct smoke detector. The end cap is needed to create 
the proper air flow to the sensor of the duct smoke detector.

Figure 4. Air duct detector sampling tube:

SAMPLING

TUBE

END CAP

AIR HOLES

ARROW

MUST FACE

INTO AIR FLOW

AIR FLOW DIRECTION

FLANGE

H0108-02

[5.4.2] Installation For Ducts More Than 8 Feet Wide

NOTE:

 To install sampling tubes in ducts more than 8 feet wide, 

work must be performed inside the air duct. Sampling of air in 
ducts wider than 8 feet is accomplished by using the ST-10 inlet 
sampling tube. If the tube is shorter than the width of the air duct, 
install the end cap into the sampling tube as shown in 

Figure 4

 

and support the end opposite the duct smoke detector.

Figure 5. Tube mounting configurations with varying 
air flow direction:

AIR FLOW

DIRECTION

DETECTOR

HOUSING

DOTS INDICATE POSITION OF

SAMPLING TUBE HOLES

AIR FLOW

DIRECTION

DETECTOR

HOUSING

SAMPLING

TUBE

EXHAUST

TUBE

AIR FLOW

DIRECTION

EXHAUST

TUBE

SAMPLING

TUBE

SAMPLING

TUBE

EXHAUST

TUBE

DETECTOR

HOUSING

AIR FLOW

DIRECTION

DETECTOR

HOUSING

A.

B.

C.

D.

HORIZONTAL MOUNTING OF HOUSING

VERTICAL MOUNTING OF HOUSING

 

NOTE: Only metal sampling tubes may be used on orientations 
C and D.

WARNING

In no case should more than 2 air inlet holes be cut off the tube. 
There must be a minimum of 10 holes in the tube exposed to the 
air stream.

Install the inlet tube as follows:

1.   Drill a 

3

4

˝ hole in the duct directly opposite the hole already 

drilled for the sampling tube. Make sure the hole is 1 to 2” 
below the inlet hole on the opposite side of the duct to allow 
for moisture drainage.

2.   Slide the sampling tube with the flange into the housing bush-

ing that meets the air flow first. Position the tube so that the 
arrow points into the air flow. Secure the tube flange to the 
housing bushing with two #6 self-tapping screws.

3.   From inside the duct, couple the other sections of the sam-

pling tube to the section already installed using the 1⁄2 inch 
conduit fittings supplied. Make sure that the holes on both of 
the air inlet tubes are lined up and facing into the air flow.

4.   Trim the end of the tube protruding through the duct so that 

1 to 2 inches of the tube extend outside the duct. Plug this 
end with the end cap and tape closed any holes in the pro-
truding section of the tube. Be sure to seal the duct when the 
tube protrudes.

NOTE:

 An alternate method to using the ST-10 is to use two ST-5 

sampling tubes. Remove the flange from one of the tubes and in-
stall as described above. After the installation, use electrical tape 
to close off some of the sampling holes so that there are a total 
of 10 to 12 holes spaced as evenly as possible across the width of 
the duct.

NOTE:

  Air  currents  inside  the  duct  may  cause  excessive  vibra-

tion, especially when the longer sampling tubes are used. In these 
cases a 3” floor flange (available at most plumbing supply stores) 
may be used to fasten the sampling tube to the other side of the 
duct. When using the flange/connector mounting technique, drill 
a 1 inch to 1

1

4

 inch hole where the flange will be used. 

D100-68-00 

I56-1684-007R

H0109-01

Содержание DH100ACDCI

Страница 1: ...hut down These detectors are not designed for 2 wire applications For testing the alarm can be enabled by a magnet activated test switch or by the optional remote test station The duct smoke detector latches into alarm state when an alarm occurs A green LED flashes to indicate power a red LED signals local alarm indication and optional accessories offer a variety of annuncia tion capabilities The ...

Страница 2: ...les as indi cated in Figure 4 D100 68 00 2 I56 1684 007R 4 Figure 1 Exploded View Of Duct Smoke Detector Components FOAM GASKETS PLASTIC SAMPLING TUBE CONDUIT HOLES DETECTOR HOUSING TERMINAL STRIP DETECTOR COVER SAMPLING TUBE FILTERS PLASTIC SAMPLING TUBE SELF TAPPING SCREW POWER BOARD DETECTOR BOARD COVER MOUNTING SCREWS H0401 00 H0110 00 5 Installation Sequence 5 1 Verify Duct Air Flow Direction...

Страница 3: ...t the end opposite the duct smoke detector Figure 5 Tube mounting configurations with varying air flow direction AIR FLOW DIRECTION DETECTOR HOUSING DOTS INDICATE POSITION OF SAMPLING TUBE HOLES AIR FLOW DIRECTION DETECTOR HOUSING SAMPLING TUBE EXHAUST TUBE AIR FLOW DIRECTION EXHAUST TUBE SAMPLING TUBE SAMPLING TUBE EXHAUST TUBE DETECTOR HOUSING AIR FLOW DIRECTION DETECTOR HOUSING A B C D HORIZONT...

Страница 4: ... between interconnected detectors or from detectors to auxiliary devices it is usually recommended that single conductor wire be no smaller than 18 gauge The duct smoke detector terminals accommodate wire sizes up to 12 gauge The last foot of conduit should be flexible conduit available in electrical supply houses which facilitates easier installation and puts less strain on the conduit holes in t...

Страница 5: ... RTS451KEY is not required when these accessories are used with the DH100ACDCI detectors The functionality of the magnetic coil has been designed into the circuitry of the new In novair duct smoke detectors 6 2 2 3 SSK451 Multi Signaling Accessory The System Sensor SSK451 Multi Signaling accessory combines a sounder feature with a key activated test and reset function Green amber and red LEDs prov...

Страница 6: ...S ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR AUX CONTACT RATINGS 10A 30 VDC RESISTIVE 10A 250 VAC 100mA MINIMUM 5 VDC 1 4 HP 240 VAC 1 8 HP 120 VAC NOT INTENDED FOR CONNECTION TO CONTROL PANELS TROUBLE CONTACT RATING 2 0 A 30 VDC resistive 2 0 A 125 VAC resistive 120 VAC CAUTION Do not loop wire under termin...

Страница 7: ...ination of accessories may be used such that the given accessory loads are 60 mA or less in the standby state 110 mA or less in the alarm state TROUBLE n a n a n a n a 9mA Max D100 68 00 7 I56 1684 007R Figure 11 Wiring diagrams for optional accessories H0402 01 15 ALARM SIGNAL 3 14 2 RESET 11 TEST 20 AUX POWER 19 AUX POWER SSK451 FIELD INSTALLED JUMPER FOR TEMPORAL PATTERN SUPERVISORY CONTACT NO ...

Страница 8: ...60 Hz CURRENT REQUIREMENTS USING NO ACCESSORIES Max standby current 15 mA 35 mA RMS 25 mA RMS 15 mA RMS Max alarm current 70 mA 125 mA RMS 35 mA RMS 25 mA RMS CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contacts DPDT 10A 30 VDC 10A 250 VAC 1 4 HP 240 VAC 1 8 HP 120 VAC Trouble contacts SPDT 2 0A 30 VDC resistive 2 0A 125 VAC resistive Note Alarm auxiliary c...

Отзывы: