7. Trouble Shooting
If the UPS system does not operate correctly, first check the operating
information on the LCD display.
Please attempt to solve the problem using the table below. If the
problem still persists, consult your dealer.
7.1 Trouble Shooting According To Warning Indication
Problem Displayed
Possible cause
Remedy
Read EEPROM Error
UPS internal fault
Consult dealer.
Emergency Power Off
EPO connector is
open
Check the EPO connector
status
On Maintain Bypass
Maintain bypass
switch is open
Check the maintain bypass
switch status
Site Wiring Fault
Phase and neutral
conductor at input of
UPS system are
reversed
Reverse mains power wiring.
Battery Disconnected
Battery pack is not
connected correctly
Do the battery test to confirm.
Check the battery bank is
connected to the UPS.
Check the battery breaker is
turn on.
Low Battery Warning
Battery voltage is low
When audible alarm sounding
every second, battery is almost
empty.
Output Overload
Overload
Check the loads and remove
some non-critical loads.
Check if some loads are failed.
Fan Failure
Fan abnormal
Check if the fan is running
normally.
Charger Failure
The charge fails
Consult dealer.