Fig. 4-5 Additional stability
4.3.2 Installation
Use cable cross section and protective device specification
Model
6k
10k
Protective earthing conductor
Min cross section
4mm
2
(10AWG)
10 mm
2
(6AWG)
Input L, N, G
Min conductor cross section
4mm
2
(10AWG)
10 mm
2
(6AWG)
Input breaker
50A/250VAC
80A/250VAC
Input fuse
60A/250VAC
90A/250AC
Output L,N,
Min conductor cross section
4mm
2
(10AWG)
10 mm
2
(6AWG)
External Battery Cabinet
Positive Pole(+), Negative pole(-),
Neutral Pole
Min conductor cross section
4mm
2
(10AWG)
10 mm
2
(6AWG)
External Battery Cabinet Fuse
in Positive Pole(+), Negative pole(-),
Neutral Pole
60A/240VDC
90A/240VDC
For safety, please cut off the mains power switch before
installation!